2007-02-13 09:03:01 | REVISION DENIED |
| REFERENCE: FBC-2004 PLUMBING; FBC-2004 CHAPTER 1, CITY |
| OF WEST PALM BEACH AMENDMENTS; FLORIDA ADMINISTRATIVE |
| CODE; |
| |
| THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING |
| PLAN REVIEW ON THE REVISION TO MEET CODE COMPLIANCE: |
| |
| 1]FAC-61G1-16.004 TITLE BLOCK: |
| A TITLE BLOCK MUST APPEAR ON ALL |
| ARCHITECTURAL OR INTERIOR DESIGN |
| DRAWINGS AND SPECIFICATION |
| IDENTIFICATION SHEETS. THE TITLE BLOCK |
| MUST, AT A MINIMUM, CONTAIN THE |
| FOLLOWING INFORMATION: |
| (1) FIRM NAME, ADDRESS, AND TELEPHONE |
| NUMBER. |
| (2) FIRM LICENSE NUMBER. |
| (3) NAME OR IDENTIFICATION OF PROJECT. |
| (4) DATE PREPARED. |
| (5) A SPACE FOR THE SIGNATURE AND DATED |
| SEAL. |
| (6) A SPACE FOR THE PRINTED NAME OF THE |
| PERSON SEALING THE DOCUMENT. |
| NOTE: ON THE SUBMITTED REVISION THE FIRM LICENSE NUMBER |
| IS MISSING, PLEASE CORRECT AND RESUBMIT. |
| |
| 2]PER FBC-2004 CHAPTER 1 SECTION 106.1.1 INFORMATION |
| ON CONSTRUCTION |
| DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL |
| BE OF SUFFICIENT CLARITY TO INDICATE THE |
| LOCATION, NATURE AND EXTENT OF THE WORK |
| PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| CONFORM TO THE PROVISIONS OF THIS CODE |
| AND RELAVENT LAWS, ORDINANCES, RULES AND REGULATIONS, |
| AS DETERMINED BY THE |
| BUILDING OFFICIAL. |
| NOTE: THE FOLLOWING INFORMATION NEEDS TO BE ON THE |
| RESUBMITTED REVISION: |
| A} PLEASE IDENTIFY ALL FIXTURES, LAUNDRY TRAY IS NOT |
| IDENTIFIED, PLEASE CORRECT AND RESUBMIT. |
| B} DISHWASHER IS MISSING FROM THE KITCHEN SINK, PLEASE |
| CORRECT AND RESUBMIT. |
| |
| 3] PERFBC-2004 CHAPTER 1, SECTION 106.3.5.4 |
| RESIDENTIAL (ONE AND TWO |
| FAMILY) SUBMIT A PLUMBING SANITARY |
| ISOMETRIC RISER DIAGRAM INDICATING ALL |
| WASTE, VENTS, TRAPS WITH SIZES, AND |
| CLEANOUT LOCATIONS. |
| NOTE: THE FOLLOWING INFORMATION NEEDS TO BE INDICATED |
| ON THE RESUBMITTED REVISION: |
| A} NOT ALL PIPES OR TRAPS ARE SIZED, PLEASE CORRECT |
| AND RESUBMIT. |
| |
| 4] PER FBC-2004 PLUMBING, SECTION 708 THE FOLLOWING |
| NEEDS TO BE INDICATED ON THE RESUBMITTED REVISION. |
| (A) 708.7 MINIMUM SIZE. CLEANOUTS SHALL |
| BE THE SAME NOMINAL SIZE AS THE PIPE |
| THEY SERVE UP TO 4 INCHES (102MM) |
| CLEANOUT FOR WASHING MACHINE SHALL BE THREE INCH (3"), |
| PLEASE INDICATE THIS ON THE RESUBMITTED REVISION. |
| (B) 708.9 ACCESS. ACCESS SHALL BE |
| PROVIDED TO ALL CLEANOUTS. |
| CLEANOUT FOR THE WASHING MACHINE SHALL BE FOUR FEET |
| ABOVE FINNISH FLOOR (4' A.F.F.), PLEASE INDICATE THIS |
| ON THE RESUBMITTED REVISION. |
| |
| 5] PER FBC-2004 PLUMBING, SECTION 1002.1: TRAPS ARE |
| REQUIRED FOR ALL FIXTURES, PLEASE INDICATE THEM ON THE |
| RESUBMITTED REVISION (EXCEPTION: FIXTURES WITH INTEGRAL |
| TRAPS (WATER CLOSETS) NEED NOT BE INDICATED ON THE |
| RESUBMITTED REVISION.) |
| |
| **********IMPORTANT INFORMATION |
| IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| PLEASE REPLACE ONLY SHEETS |
| WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| ONLY. NOTE: ONLY ONE CORRECTED DRAWING |
| IN RED INK FOR REFERENCE FOR |
| RESUBMITTAL. |
| |
| END OF COMMENTS: |
| |