Plan Review Notes For Permit 06071887 |
Permit Number |
06071887 |
|
Review Stop |
E |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2007-06-03 14:31:18 | ** UNSAT ** | | | | 1) NOTE: PLEASE CORRELATE PANEL *D* SIZE ON RISER AND | | PANEL SCHEDULE AS ONE SHOWS 60AMP AND THE OTHER | | 80AMPS. | | FBC 106.1.2. | | | | 2) NOTE: PLEASE SEE THE LOADS ON PANEL *A* FOR PANEL | | *D* DO NOT CORRELATE WITH THE ACTUAL LOADS ON PANEL | | *D*> | | PLEASE SEE 10KW SHOWN ON *A* AND 4.250KW ON *D*> | | PLEASE ADJUST. | | FBC 106.1.2, 106.3.5.4 | | NEC 220 | | | | 3) NOTE: PLEASE CLARIFY THE CODES WHICH HAVE BEEN | | REVISED ON PLANS. | | PLEASE KNOW AS PERMIT WAS APPLIED FOR BEFORE DECEMBER | | 8TH, 2006, THIS PLACES THE PLANS TO BE UNDER THE 2004 | | FBC W/ 2005 REVISIONS AND THE 2002 NEC(NFPA-70). NOT | | THE 2005 NEC> | | PLEASE KNOW THIS WAS NOT A COMMENT ON THE PREVIOUS | | *PROVISO* AND SHOULD BE CHANGED BACKED T0 2002 NEC. ** | | ONLY PERMITS APPLIED FOR AFTER THE DECEMBER 8TH, 2006 | | DATE, PLACES PLANS UNDER THE 2005 NEC. | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|