Plan Review Notes
Plan Review Notes For Permit 06071887
Permit Number 06071887
Review Stop E
Sequence Number 3
Notes
Date Text
2007-06-03 14:31:18** UNSAT **
  
 1) NOTE: PLEASE CORRELATE PANEL *D* SIZE ON RISER AND
 PANEL SCHEDULE AS ONE SHOWS 60AMP AND THE OTHER
 80AMPS.
 FBC 106.1.2.
  
 2) NOTE: PLEASE SEE THE LOADS ON PANEL *A* FOR PANEL
 *D* DO NOT CORRELATE WITH THE ACTUAL LOADS ON PANEL
 *D*>
 PLEASE SEE 10KW SHOWN ON *A* AND 4.250KW ON *D*>
 PLEASE ADJUST.
 FBC 106.1.2, 106.3.5.4
 NEC 220
  
 3) NOTE: PLEASE CLARIFY THE CODES WHICH HAVE BEEN
 REVISED ON PLANS.
 PLEASE KNOW AS PERMIT WAS APPLIED FOR BEFORE DECEMBER
 8TH, 2006, THIS PLACES THE PLANS TO BE UNDER THE 2004
 FBC W/ 2005 REVISIONS AND THE 2002 NEC(NFPA-70). NOT
 THE 2005 NEC>
 PLEASE KNOW THIS WAS NOT A COMMENT ON THE PREVIOUS
 *PROVISO* AND SHOULD BE CHANGED BACKED T0 2002 NEC. **
 ONLY PERMITS APPLIED FOR AFTER THE DECEMBER 8TH, 2006
 DATE, PLACES PLANS UNDER THE 2005 NEC.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  