Plan Review Notes
Plan Review Notes For Permit 06071887
Permit Number 06071887
Review Stop P
Sequence Number 1
Notes
Date Text
2006-08-04 00:00:00******DENIED******
 REFERENCE: FBC-2004 PLUMBING
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED
 ON THE ISOMETRIC PLUMBING RISER DIAGRAM
 ON SHEET A-6 FOR PLUMBING PLAN REVIEW:
  
 1. PER FBC-2004 CHAPTER 1, SECTION
 106.1.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL
 BE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE
 AND RELAVENT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE
 BUILDING OFFICIAL. NOTE: SHEET A-6
 ISOMETRIC PLUMBING RISER DOES NOT
 REFLECT THE FLOOR PLAN IT INDICATES AN
 EXTRA HALF BATH NOT INDICATED ON THE
 FLOOR PLAN SHEET A-2. PLEASE SEE SHEET
 A-6 CORRECTED PLMG. RISER DRAWING IN RED
 INK FOR REFERENCE FOR RESUBMITTAL.
 2. IN BATH 3 THE LAVATORY IS INDICATED
 WRONG. PLEASE REFERENCE THE CORRECTED
 DRAWING IN RED INK ON SHEET A-6 FOR
 RESUBMITTAL.
 3. RELIEF VENTS ARE REQUIRED FOR THE
 SHOWER IN "HIS BATH" AND THE W.POOL IN
 "HER BATH" PER FBC-2004 PLMG. TABLE
 906.1 AND SEC. 911.4 RELIEF VENT. PLEASE
 REFERENCE THE CORRECTED DRAWING IN RED
 INK ON SHEET A-6 FOR RESUBMITTAL.
 4. A VENT IS REQUIRED FOR THE BIDET IN
 "HER BATH" PER FBC-2004 PLMG.
 SEC.901.2.1. PLEASE REFERENCE THE
 CORRECTED DRAWING IN RED INK FOR
 RESUBMITTAL.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN
 RESUBMITTING, PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  