Date |
Text |
2006-08-04 00:00:00 | ******DENIED****** |
| REFERENCE: FBC-2004 PLUMBING |
| |
| THE FOLLOWING CORRECTIONS ARE REQUIRED |
| ON THE ISOMETRIC PLUMBING RISER DIAGRAM |
| ON SHEET A-6 FOR PLUMBING PLAN REVIEW: |
| |
| 1. PER FBC-2004 CHAPTER 1, SECTION |
| 106.1.1 INFORMATION ON CONSTRUCTION |
| DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL |
| BE OF SUFFICIENT CLARITY TO INDICATE THE |
| LOCATION, NATURE AND EXTENT OF THE WORK |
| PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| CONFORM TO THE PROVISIONS OF THIS CODE |
| AND RELAVENT LAWS, ORDINANCES, RULES AND |
| REGULATIONS, AS DETERMINED BY THE |
| BUILDING OFFICIAL. NOTE: SHEET A-6 |
| ISOMETRIC PLUMBING RISER DOES NOT |
| REFLECT THE FLOOR PLAN IT INDICATES AN |
| EXTRA HALF BATH NOT INDICATED ON THE |
| FLOOR PLAN SHEET A-2. PLEASE SEE SHEET |
| A-6 CORRECTED PLMG. RISER DRAWING IN RED |
| INK FOR REFERENCE FOR RESUBMITTAL. |
| 2. IN BATH 3 THE LAVATORY IS INDICATED |
| WRONG. PLEASE REFERENCE THE CORRECTED |
| DRAWING IN RED INK ON SHEET A-6 FOR |
| RESUBMITTAL. |
| 3. RELIEF VENTS ARE REQUIRED FOR THE |
| SHOWER IN "HIS BATH" AND THE W.POOL IN |
| "HER BATH" PER FBC-2004 PLMG. TABLE |
| 906.1 AND SEC. 911.4 RELIEF VENT. PLEASE |
| REFERENCE THE CORRECTED DRAWING IN RED |
| INK ON SHEET A-6 FOR RESUBMITTAL. |
| 4. A VENT IS REQUIRED FOR THE BIDET IN |
| "HER BATH" PER FBC-2004 PLMG. |
| SEC.901.2.1. PLEASE REFERENCE THE |
| CORRECTED DRAWING IN RED INK FOR |
| RESUBMITTAL. |
| |
| **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN |
| RESUBMITTING, PLEASE REPLACE ONLY SHEETS |
| WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| ONLY. NOTE: ONLY ONE CORRECTED DRAWING |
| IN RED INK FOR REFERENCE FOR |
| RESUBMITTAL. |
| |
| END OF COMMENTS: |
| |
| REVIEW BY MIKE PERSON |
| (561) 805-6730 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |
| UNDER SUPERVISION OF K.STEVENS |
| (561) 805-6721 |
| |
| |