Plan Review Notes
Plan Review Notes For Permit 06071887
Permit Number 06071887
Review Stop E
Sequence Number 1
Notes
Date Text
2006-08-02 00:00:00****** UNSAT *****
  
  
 **** IMPORTANT *****
  
 PLEASE SEE PERMIT APPLICATION FROM
 CONTRACTOR IS IN FACT A COLORED
 PHOTO-COPY OF AN ORIGINAL APPLICATION.
 PLEASE KNOW ALL SIGNATURES FOR ALL
 CONTRACTORS SHALL BE ORIGINAL. THIS IS A
 COPY FOR ENTIRE APPLICATION INCLUDING
 BACK WITH NOTARY ETC.
 THIS PERMIT APPLICATION WILL BE RETAINED
 BY THIS OFFICE AND COMPARED TO ALL OTHER
 SUBMITTED APPLICATIONS FOR PAST SINGLE
 FAMILY HOUSE PLANS SUBMITTED. PLEASE
 KNOW, ANY PAST APPLICATIONS FOUND ALSO
 TO BE COLORED PHOTO-COPIES WILL REQUIRE
 ALL NEWORIGINALS TO BE SUBMITTED.
 SUBMITTING DOCUMENTATION WHICH WAS A
 COPY OF AN ORIGINAL FOR PERMITTING IN
 WHICH THE SUB CONTRACTORS HAVE NOT
 SIGNED IS IN VIOLATION OF CONTRACTING
 LAWS AND FLORIDA STATUES FOR RECORD OF
 LEGAL DOCUMENTATION. PLEASE KNOW THIS
 MAY BE TURNED OVER TO THE STATE
 LICENSING BOARD.
  
  
 1) NOTE: PLEASE BE SURE THT FOLLOWING
 CODES ARE REFLECTED ON PLANS.
 2002 NFPA-70 (NEC), NFPA-72 2002.
 PLANS DO SHOW ARC FAULT FOR 210.12B PER
 2002, HOWEVER PLANS SHOULD HAVE THE CODE
 REFLECTED INTO DESIGN ON COVER SHEET AS
 A MINIMUM.
  
 2) NOTE: PLEASE HAVE PLANS NOTE SD'S
 INSTALLED PER NFPA-72 11.5.1.1, 11.8.3
 PLEASE SEE TWO AREAS ON PLANS REDLINED.
 ONE FOR SD LOCATED OUTSIDE GUEST SUITE
 IS REQUIRED WITHIN 3' OF THE PEAK ON A
 SLOPED CEILING.
 PLEASE CALRIFY THE LOCATION OF THE SD
 OUTSIDE THE MASTER BEDRM.
 PLEASE SEE THIS SEEMS TO BE SHOWN
 OUTSIDE HOME THEATRE.?
  
 3) NOTE: PLEASE CORRELATE ALL KW
 RATINGS FOR HEAT STRIPS IN AHU'S. PLEASE
 SEE MECHANICAL PLANS INDICATE ALL UNITS
 AS 10KW. IF SO PLEASE SEE 424.3B FOR AHU
 #3.
  
 4) NOTE: PLEASE CLARIFY THE LOADS ON ANY
 CONTINUOUS LOADS IF THEY ARE ALREADY
 FIGURED AT 125%. (POOL PUMP, RECIR PUMP)
 215.3,230.42
  
 5) NOTE: PLEASE SEE 408.4, A MIN PANEL
 SCHEDULE DENOTING ALL CIRCUITS AND
 CORRELATION WITH ROOM AND AREA
 DESIGNATIONS IS REQUIRED AT THIS TIME.
 PLEASE KNOW, IT IS KNOWN THAT THE
 CIRCUITS WILL MOST LIKELY BE REVISED
 DURING THE CONSTRUCTION AND MAY BE
 REVISED AT A LATER DATE ALONG WITH ANY
 OTHER REVISIONS.
 PLEASE SEE EXAMPLE. IE: LIVING RM LTS,
 MASTER BEDRM RECEPTS, BATH #4 RECEPTS
 ETC.
 FBC 106.1.2
  
 6) NOTE: PLEASE SEE PLANS FOR MISSING
 REQUIRED DISCONNECTING MEANS FOR CU'S.
 PLEASE SEE 440.11 AND 110.26
  
 7) NOTE: PLEASE CLARIFY BRANCH CIRCUIT
 TO REFRIGERATOR(S). PANEL SCHEDULE
 MENTIONS "2" AND ON A 2-POLE BRKR AND
 3KW LOAD??
 PLEASE CLARIFY AS ONLY ONE FRIG IS SHOWN
 .?
 PLEASE CLARIFY AND ADJUST.
 106.1.2
  
 ** BEFORE RESUBMITTING PLANS AND ONCE
 ALL REVIEWS ARE DONE. PLEASE BE SURE TO
 COMPLETELY REMOVE ALL OLD/VOIDED SHEETS
 AND ONLY INSERT THE NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND
 STAMPING. PLEASE SUBMIT ONLY ONE COPY OF
 THE OLD/VOIDED SHEETS FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]