2006-08-02 00:00:00 | ****** UNSAT ***** |
| |
| |
| **** IMPORTANT ***** |
| |
| PLEASE SEE PERMIT APPLICATION FROM |
| CONTRACTOR IS IN FACT A COLORED |
| PHOTO-COPY OF AN ORIGINAL APPLICATION. |
| PLEASE KNOW ALL SIGNATURES FOR ALL |
| CONTRACTORS SHALL BE ORIGINAL. THIS IS A |
| COPY FOR ENTIRE APPLICATION INCLUDING |
| BACK WITH NOTARY ETC. |
| THIS PERMIT APPLICATION WILL BE RETAINED |
| BY THIS OFFICE AND COMPARED TO ALL OTHER |
| SUBMITTED APPLICATIONS FOR PAST SINGLE |
| FAMILY HOUSE PLANS SUBMITTED. PLEASE |
| KNOW, ANY PAST APPLICATIONS FOUND ALSO |
| TO BE COLORED PHOTO-COPIES WILL REQUIRE |
| ALL NEWORIGINALS TO BE SUBMITTED. |
| SUBMITTING DOCUMENTATION WHICH WAS A |
| COPY OF AN ORIGINAL FOR PERMITTING IN |
| WHICH THE SUB CONTRACTORS HAVE NOT |
| SIGNED IS IN VIOLATION OF CONTRACTING |
| LAWS AND FLORIDA STATUES FOR RECORD OF |
| LEGAL DOCUMENTATION. PLEASE KNOW THIS |
| MAY BE TURNED OVER TO THE STATE |
| LICENSING BOARD. |
| |
| |
| 1) NOTE: PLEASE BE SURE THT FOLLOWING |
| CODES ARE REFLECTED ON PLANS. |
| 2002 NFPA-70 (NEC), NFPA-72 2002. |
| PLANS DO SHOW ARC FAULT FOR 210.12B PER |
| 2002, HOWEVER PLANS SHOULD HAVE THE CODE |
| REFLECTED INTO DESIGN ON COVER SHEET AS |
| A MINIMUM. |
| |
| 2) NOTE: PLEASE HAVE PLANS NOTE SD'S |
| INSTALLED PER NFPA-72 11.5.1.1, 11.8.3 |
| PLEASE SEE TWO AREAS ON PLANS REDLINED. |
| ONE FOR SD LOCATED OUTSIDE GUEST SUITE |
| IS REQUIRED WITHIN 3' OF THE PEAK ON A |
| SLOPED CEILING. |
| PLEASE CALRIFY THE LOCATION OF THE SD |
| OUTSIDE THE MASTER BEDRM. |
| PLEASE SEE THIS SEEMS TO BE SHOWN |
| OUTSIDE HOME THEATRE.? |
| |
| 3) NOTE: PLEASE CORRELATE ALL KW |
| RATINGS FOR HEAT STRIPS IN AHU'S. PLEASE |
| SEE MECHANICAL PLANS INDICATE ALL UNITS |
| AS 10KW. IF SO PLEASE SEE 424.3B FOR AHU |
| #3. |
| |
| 4) NOTE: PLEASE CLARIFY THE LOADS ON ANY |
| CONTINUOUS LOADS IF THEY ARE ALREADY |
| FIGURED AT 125%. (POOL PUMP, RECIR PUMP) |
| 215.3,230.42 |
| |
| 5) NOTE: PLEASE SEE 408.4, A MIN PANEL |
| SCHEDULE DENOTING ALL CIRCUITS AND |
| CORRELATION WITH ROOM AND AREA |
| DESIGNATIONS IS REQUIRED AT THIS TIME. |
| PLEASE KNOW, IT IS KNOWN THAT THE |
| CIRCUITS WILL MOST LIKELY BE REVISED |
| DURING THE CONSTRUCTION AND MAY BE |
| REVISED AT A LATER DATE ALONG WITH ANY |
| OTHER REVISIONS. |
| PLEASE SEE EXAMPLE. IE: LIVING RM LTS, |
| MASTER BEDRM RECEPTS, BATH #4 RECEPTS |
| ETC. |
| FBC 106.1.2 |
| |
| 6) NOTE: PLEASE SEE PLANS FOR MISSING |
| REQUIRED DISCONNECTING MEANS FOR CU'S. |
| PLEASE SEE 440.11 AND 110.26 |
| |
| 7) NOTE: PLEASE CLARIFY BRANCH CIRCUIT |
| TO REFRIGERATOR(S). PANEL SCHEDULE |
| MENTIONS "2" AND ON A 2-POLE BRKR AND |
| 3KW LOAD?? |
| PLEASE CLARIFY AS ONLY ONE FRIG IS SHOWN |
| .? |
| PLEASE CLARIFY AND ADJUST. |
| 106.1.2 |
| |
| ** BEFORE RESUBMITTING PLANS AND ONCE |
| ALL REVIEWS ARE DONE. PLEASE BE SURE TO |
| COMPLETELY REMOVE ALL OLD/VOIDED SHEETS |
| AND ONLY INSERT THE NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND |
| STAMPING. PLEASE SUBMIT ONLY ONE COPY OF |
| THE OLD/VOIDED SHEETS FOR REFERENCE. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CITY OF WEST PALM BEACH |
| CONSTUCTION SERVICES DEPT. |
| 561-805-6717 |
| [email protected] |