Plan Review Notes For Permit 06071885 |
Permit Number |
06071885 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-08-09 00:00:00 | **APPROVED** | | | | | | | | 1.) DUCT SMOKE DETECTORS SHALL INITIATE | | A GENERAL ALARM. | | | | 2.) FIRE ALARM SYSTEM IN CONJUNCTION | | WITH FIRE SPRINKLER SYSTEM TO BE | | MONITORED. | | | | 3.) WATERFLOW TO ACTIVATE GENERAL FIRE | | ALARM WITHIN 45 TO 60 SECONDS. | | | | 4.) TAMPER/SUPERVISORY SWITCH SHALL BE | | OPERATIONAL. | | | | 5.) UL CERTIFICATE FOR CENTRAL STATION | | SERVICE TO BE AT THE FACP AND A COPY | | SUBMITTED TO WPBFR BY FINAL FIRE ALARM | | INSPECTION. | | | | | | | | | | | | | | LT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|