Plan Review Notes
Plan Review Notes For Permit 06071848
Permit Number 06071848
Review Stop B
Sequence Number 1
Notes
Date Text
2006-08-04 00:00:00DENIED
  
 REVIEW FOR STRUCTURAL ONLY PHASE OF 5
 STORY PARKING GARAGE.
  
 1) THE PROPERTY CONTROL NUMBER LISTED ON
 THE APPLICATION IS INCORRECT. THE
 CORRECT PCN IS 74-43-43-29-22-000-0030.
  
 2) THE THRESHOLD INSPECTION PLAN
 INCORRECTLY LISTS CITY OF BOYNTON BEACH
 ADMINISTRATIVE AMENDMENTS TO 2004 FBC.
 THIS PROJECT IS LOCATED IN THE CITY OF
 WEST PALM BEACH.
  
 3) THE PROPERTY LINES SHOWN ON THE
 SURVEY HAVE NOT BE CHANGED. THEREFORE,
 BASED ON FIRE SEPARATION DISTANCES THE
 STRUCTURE DOES NOT COMPLY WITH FBC TABLE
 704.8 FOR ALLOWABLE AREA OF OPENINGS.
 SEE COMMENT #2 ON SECOND REVIEW FOR
 PERMIT #05120987.
  
 4) THE WALL OF THE BUSINESS OCCUPANCY
 THAT HAS BEEN REMOVED ON SHEET A2.1.3 IS
 STILL SHOWN ON SHEET S1.0 OF THE
 STRUCTURAL DRAWINGS. PLEASE COORDINATE
 ARCHITECTURAL CHANGES WITH STRUCTURAL.
  
 NOTE: APPROVAL OF STRUCTURAL PHASE DOES
 NOT INSURE THAT A PERMIT FOR THE ENTIRE
 STRUCTURE WILL BE ISSUED. ALL OF THE
 PLAN REVIEW COMMENTS MUST BE ADDRESSED
 TO THE SATISFACTION OF THE CONSTRUCTION
 SERVICES DEPARTMENT. THE CONTRACTOR WILL
 BE PROCEEDING AT THEIR OWN RISK.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  