Plan Review Notes
Plan Review Notes For Permit 06071830
Permit Number 06071830
Review Stop E
Sequence Number 2
Notes
Date Text
2006-09-28 00:00:00 
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 SAME COMMENTS AS LAST REVIEW
  
 1} PLEASE NOTE A DISCONNECT IS REQUIRED
 PER 225.31 AND 32. INDICATE LOCATION ON
 THE RISER AND SITE PLAN. THE TRANSFER
 SWITCH MAY NOT MEET THIS REQUIREMENT,
 SEE SPECS BEFORE SUBMITTING. SHOULD BE
 LOCATED WHERE THE JUNCTION BOX IS SHOWN.
 THIS DISCONNECT IS NOT REQUIRED TO HAVE
 OVERCURRENT PROTECTION.
  
 2} SUBMIT A SITE PLAN AND LOCATE ALL
 THE SERVICE AND GENERATOR GEAR ON SAME
 SO THAT COMPLIANCE WITH 230.72
 (GROUPING), 225.31-39 FOR THE
 DISCONNECTING MEANS REQUIREMENTS AND
 250.32 FOR GROUNDING CAN BE REVIEWED.
  
 3} PROVIDE A LOAD CALCULATION FOR THE
 LOAD INTENDED TO BE SERVED. 215.5. THE
 GENERATOR HAS A RATED OUTPUT OF 52.5
 AMPS PER SPEC'S. THE CALCULATION
 REQUIRED IS FOR THE CIRCUITS IN THE 16
 CIRCUIT GENERATOR PANEL. 702.5 CAPACITY
 AND RATING.
 AN OPTIONAL STANDBY SYSTEM SHALL HAVE
 ADEQUATE CAPACITY AND RATING FOR THE
 SUPPLY OF ALL EQUIPMENT INTENDED TO BE
 OPERATED AT ONE TIME. OPTIONAL STANDBY
 SYSTEM EQUIPMENT SHALL BE SUITABLE FOR
 THE MAXIMUM AVAILABLE FAULT CURRENT AT
 ITS TERMINALS. THE USER OF THE OPTIONAL
 STANDBY SYSTEM SHALL BE PERMITTED TO
 SELECT THE LOAD CONNECTED TO THE SYSTEM.
  
 4} THE PERSON RESPONSIBLE FOR THE PLAN
 MUST PRINT AND SIGN THEIR NAME TO
 SAME.106.3.4.2 FBC, AS AMENDED.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  
  
  
  