2006-09-28 00:00:00 | |
| NONCOMPLIANT |
| |
| PLEASE MAKE THE FOLLOWING CORRECTIONS |
| FOR CODE COMPLIANCE AND RESUBMIT FOR |
| REVIEW. |
| |
| SAME COMMENTS AS LAST REVIEW |
| |
| 1} PLEASE NOTE A DISCONNECT IS REQUIRED |
| PER 225.31 AND 32. INDICATE LOCATION ON |
| THE RISER AND SITE PLAN. THE TRANSFER |
| SWITCH MAY NOT MEET THIS REQUIREMENT, |
| SEE SPECS BEFORE SUBMITTING. SHOULD BE |
| LOCATED WHERE THE JUNCTION BOX IS SHOWN. |
| THIS DISCONNECT IS NOT REQUIRED TO HAVE |
| OVERCURRENT PROTECTION. |
| |
| 2} SUBMIT A SITE PLAN AND LOCATE ALL |
| THE SERVICE AND GENERATOR GEAR ON SAME |
| SO THAT COMPLIANCE WITH 230.72 |
| (GROUPING), 225.31-39 FOR THE |
| DISCONNECTING MEANS REQUIREMENTS AND |
| 250.32 FOR GROUNDING CAN BE REVIEWED. |
| |
| 3} PROVIDE A LOAD CALCULATION FOR THE |
| LOAD INTENDED TO BE SERVED. 215.5. THE |
| GENERATOR HAS A RATED OUTPUT OF 52.5 |
| AMPS PER SPEC'S. THE CALCULATION |
| REQUIRED IS FOR THE CIRCUITS IN THE 16 |
| CIRCUIT GENERATOR PANEL. 702.5 CAPACITY |
| AND RATING. |
| AN OPTIONAL STANDBY SYSTEM SHALL HAVE |
| ADEQUATE CAPACITY AND RATING FOR THE |
| SUPPLY OF ALL EQUIPMENT INTENDED TO BE |
| OPERATED AT ONE TIME. OPTIONAL STANDBY |
| SYSTEM EQUIPMENT SHALL BE SUITABLE FOR |
| THE MAXIMUM AVAILABLE FAULT CURRENT AT |
| ITS TERMINALS. THE USER OF THE OPTIONAL |
| STANDBY SYSTEM SHALL BE PERMITTED TO |
| SELECT THE LOAD CONNECTED TO THE SYSTEM. |
| |
| 4} THE PERSON RESPONSIBLE FOR THE PLAN |
| MUST PRINT AND SIGN THEIR NAME TO |
| SAME.106.3.4.2 FBC, AS AMENDED. |
| |