Plan Review Notes
Plan Review Notes For Permit 06071722
Permit Number 06071722
Review Stop B
Sequence Number 8
Notes
Date Text
2008-01-31 08:05:00BUILDING PLAN REVIEW
 PERMIT: 06071722
 ADD: 2823 N AUSTRALIAN AVE
 CONT: HEDRICK BROTHERS
 TEL: (561) 718-9166
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT. IF YOUR PROJECT WILL REQUIRE A
 RESIDENT INSPECTOR OR IF YOUR PROJECT IS A THRESHOLD
 BUILDING REQUIRING A THRESHOLD INSPECTOR THEN (3) THREE
 SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED FOR PERMIT
 ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTSWEST PALM
 BEACH ADMINISTRATIVE CODE.
  
 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE2007 SUPPLEMENTS.
  
 2) THIS IS NEW WORK TO THE SCOPE OF THIS PERMIT OR
 REVISION PLEASE UPDATE VALUES IN THE JOB, ADDITIONAL
 PERMIT FEES MAY OCCUR.
 CITY OF WPB CODE OF ORDINANCES 3333-00.
  
 3) THE REVISION OR ADDITION TO THIS PERMIT DOES NOT
 INDICATE TO WHATWIND DESIGN THIS ADDITION WAS
 DESIGNED TO.1609.6.2 WIND DESIGN PROCEDURES
 1)THE BASIC WIND SPEED, V, SHALL BE
 DETERMINED IN ACCORDANCE WITH SECTION 1609.3. THE WIND
 SHALL BE ASSUMED TO COME FROM ANY HORIZONTAL
 DIRECTION.
  
 2) AN IMPORTANCE FACTOR, IW, SHALL BE
 DETERMINED IN ACCORDANCE WTIH SECTION1609.5.
  
 3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4.
  
 4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT,
 * SHALL BE DETERMINED FROM TABLE 1609.6.2.1(4)
  
 5) DETERMINE IF ADDITION IS TO BE DESIGNED AS
 PARTIALLY OPEN OR ENCLOSED. 1609.1.4.1./ 1609.2
 DEFINITIONS.
  
 4)FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES, 3 IF THRESHOLD OR RESIDENT INSPECTOR
 OF PRODUCT TESTING REPORTS, MISSING REPORTS ARE AS
 FOLLOWS:
 1) BUTLER ROOF SYSTEM
 1609.7.1 ROOF DECK.
 THE ROOF DECK SHALL BE DESIGNED TO WITHSTAND THE WIND
 PRESSURES DETERMINED UNDER EITHER THE PROVISIONS OF
 SECTION 1609.6 FOR BUILDINGS WITH A MEAN ROOF HEIGHT
 NOT EXCEEDING 60 FEET (18 288 MM) OR SECTION 1609.1.1
 FOR BUILDINGS OF ANY HEIGHT.
  
 5)PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 6)WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 NOTE: THIS ADDITION WILL STILL BY DEFINITION BE
 CONSIDERED A "ENCLOSED WALKWAY" LESS THAN 30 FEET WIDE
 CONNECTING TWO BUILDINGS.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  