Plan Review Notes For Permit 06071722
Permit Number 06071722
Review Stop M
Sequence Number 5
Notes
Date Text
2007-12-07 16:33:52** MECHANICAL REVISION TO PAGE M-3 **
 *** DENIED ***
 1) PAGE M-3 PACKAGED ROOF TOP SCHEDULE SHOWS THE A/C
 SYSTEMS AS 12 SEER, PER 2004 FBC 13-407.1.ABC.3.2.1 THE
 MINIMUM SEER IS 13. WAS EER INTENDED. PLEASE CORRECT.
  
 2) PAGE M-3 SPLIT SYSTEM SCHEDULE SHOWS SYSTEM #4 AS
 12.75 SEER, PER 2004 FBC 13-407.1.ABC.3.2.1 THE MINIMUM
 SEER IS 13. PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;