Plan Review Notes
Plan Review Notes For Permit 06071722
Permit Number 06071722
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2007-03-01 18:41:51*****DENIED*****
  
  
 THE FOLLOWING COMMENTS FROM THE PREVIOUS FIRE PLAN
 REVIEW STILL NEED TO BE ADDRESSED:
  
  
 02.PLEASE CLEARLY IDENTIFY EMERGENCY LIGHTING IN ALL
 COMPONENTS OF MEANS OF EGRESS INCLUDING STAIRS.NO
 EMERGENCY LIGHTING NOTICED IN THE STAIRWAYS ON SHEET
 A1.01
  
 05.CLASSROOMS AND SIMILAR SPACES SHALL MEET THE
 REQUIREMENTS FOR RESCUE WINDOWS.PLEASE INDICATE ON
 THE PLAN SHEET A5.01
  
 07.NEW DAMPER INSTALLATIONS SHALL BE DROP TESTED
 PRIOR TO THE FINAL INSPECTION.PLEASE INDICATE ON THE
 PLANS
  
 10.THE FIRE ALARM PANEL SHALL BE ACCESSIBLE FOR
 EMERGENCY PERSONNEL.SIGNAGE TO BE DISPLAYED ON
 ELECTRICAL ROOM DOOR INDICATING FIRE ALARM CONTROL
 PANEL (FACP) INSIDE.PLEASE INDICATE ON THE PLANS
  
 NEW COMMENTS:
  
 AA.IT IS INDICATED THAT THE BUILDING IS 100%FIRE
 SPRINKLERED.PROVIDE A LAYOUT OF THIS FIRE SPRINKLER
 SYSTEM.SEPARATE SHOP DRAWINGS AND PERMITS WILL BE
 REQUIRED FOR ANY FIRE SPRINKLER INSTALLATION OR
 REMODEL.
  
 BB.ON SHEET A2.01, IT APPEARS THAT THE EXIT ACCESS
 CORRIDOR WILL BE COMPROMISED WHEN THE DOOR(S) TO THE
 STORAGE ROOM [109] AND THE MECHANICAL ROOM [102] ARE
 OPENED AT THE SAME TIME.AS PER NFPA 101- 7.2.1.4.4* :
 DURING ITS SWING , ANY DOOR IN A MEANS OF EGRESS SHALL
 NOT LEAVE LESS THAN ONE-HALF OF THE REQUIRED WIDTH OF
 AN AISLE, A CORRIDOR, OR A PASSAGEWAY WHEN FULLY OPEN.
  
 CC.ON SHEET A1.01, VERIFY AND /OR INSTALL A
 DIRECTIONAL EXIT SIGN LIGHT INDICATING THE EXIT ONCE
 PERSON(S) ARE IN THE CORRIDOR BETWEEN BUIDING #2 AND
 BUILDING #1.
  
 DD. THERE SEEMS TO BE A DISCREPANCY AS REFERNCE TO A AN
 EXIT DOOR LOCATED AT THE MIDDLE STAIRWAY ON THE SECOND
 FLOOR.IT IS INDICATED AS AN EXIT ON SHEET A1.01, BUT
 IS INDICATED ON SHEET E3.02 THAT IT IS NOT AN EXIT.
 PLEASE CLARIFY.
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE (ON THE PLAN) EACH COMMENT
 WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  