2007-03-01 18:41:51 | *****DENIED***** |
| |
| |
| THE FOLLOWING COMMENTS FROM THE PREVIOUS FIRE PLAN |
| REVIEW STILL NEED TO BE ADDRESSED: |
| |
| |
| 02.PLEASE CLEARLY IDENTIFY EMERGENCY LIGHTING IN ALL |
| COMPONENTS OF MEANS OF EGRESS INCLUDING STAIRS.NO |
| EMERGENCY LIGHTING NOTICED IN THE STAIRWAYS ON SHEET |
| A1.01 |
| |
| 05.CLASSROOMS AND SIMILAR SPACES SHALL MEET THE |
| REQUIREMENTS FOR RESCUE WINDOWS.PLEASE INDICATE ON |
| THE PLAN SHEET A5.01 |
| |
| 07.NEW DAMPER INSTALLATIONS SHALL BE DROP TESTED |
| PRIOR TO THE FINAL INSPECTION.PLEASE INDICATE ON THE |
| PLANS |
| |
| 10.THE FIRE ALARM PANEL SHALL BE ACCESSIBLE FOR |
| EMERGENCY PERSONNEL.SIGNAGE TO BE DISPLAYED ON |
| ELECTRICAL ROOM DOOR INDICATING FIRE ALARM CONTROL |
| PANEL (FACP) INSIDE.PLEASE INDICATE ON THE PLANS |
| |
| NEW COMMENTS: |
| |
| AA.IT IS INDICATED THAT THE BUILDING IS 100%FIRE |
| SPRINKLERED.PROVIDE A LAYOUT OF THIS FIRE SPRINKLER |
| SYSTEM.SEPARATE SHOP DRAWINGS AND PERMITS WILL BE |
| REQUIRED FOR ANY FIRE SPRINKLER INSTALLATION OR |
| REMODEL. |
| |
| BB.ON SHEET A2.01, IT APPEARS THAT THE EXIT ACCESS |
| CORRIDOR WILL BE COMPROMISED WHEN THE DOOR(S) TO THE |
| STORAGE ROOM [109] AND THE MECHANICAL ROOM [102] ARE |
| OPENED AT THE SAME TIME.AS PER NFPA 101- 7.2.1.4.4* : |
| DURING ITS SWING , ANY DOOR IN A MEANS OF EGRESS SHALL |
| NOT LEAVE LESS THAN ONE-HALF OF THE REQUIRED WIDTH OF |
| AN AISLE, A CORRIDOR, OR A PASSAGEWAY WHEN FULLY OPEN. |
| |
| CC.ON SHEET A1.01, VERIFY AND /OR INSTALL A |
| DIRECTIONAL EXIT SIGN LIGHT INDICATING THE EXIT ONCE |
| PERSON(S) ARE IN THE CORRIDOR BETWEEN BUIDING #2 AND |
| BUILDING #1. |
| |
| DD. THERE SEEMS TO BE A DISCREPANCY AS REFERNCE TO A AN |
| EXIT DOOR LOCATED AT THE MIDDLE STAIRWAY ON THE SECOND |
| FLOOR.IT IS INDICATED AS AN EXIT ON SHEET A1.01, BUT |
| IS INDICATED ON SHEET E3.02 THAT IT IS NOT AN EXIT. |
| PLEASE CLARIFY. |
| |
| |
| |
| TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| LETTER INDICATING HOW/WHERE (ON THE PLAN) EACH COMMENT |
| WAS ADDRESSED |
| |
| |
| CAPT. MICHAEL A. WILLIAMS |
| FIRE PLAN REVIEW |
| 561-805-6722 |
| |