Plan Review Notes
Plan Review Notes For Permit 06071722
Permit Number 06071722
Review Stop E
Sequence Number 2
Notes
Date Text
2007-02-04 17:54:34******* UNSAT 2ND REVIEW ******
  
 *** PLEASE SEE THERE ARE ITEMS FROM THE PREVIOUS REVIEW
 WHICH STILL NEED TO BE ADDRESSED ALONG WITH NEW
 COMMENTS BASED ON CHANGES IN PLANS AND NEW INFORMATION
 AND/OR CHANGES MADE TO PLANS.
  
 **** IMPORTANT****
  
 ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM
 THE PREVIOUS REVIEW WITH A *NO*, *OK* OR *NO/OK*.
  
 A) A, NO WILL CONTAIN A FURTHER EXPLANATION AS TO WHY
 THE COMMENT MAY NOT HAVE BEEN FULLY ADDRESSED WITH THE
 PREVIOUS REVIEW NOTE BELOW WITH **PREVIOUS REVIEW NOTE
 #1**
  
 B) A, OK, WILL HAVE NO COMMENTS EXCEPT PERHAPS A
 REFERENCE TO SEE ** NEW NOTES*. THE PREVIOUS REVIEW
 NOTE WILL BE REMOVED.
  
 C) A, NO/OK, WILL HAVE FURTHER EXPLANATION AS PART OF
 THE COMMENT MAY HAVE BEEN ADDRESSED, HOWEVER NOT ALL.
 THE PREVIOUS REVIEW NOTE WILL BE NOTED **PREVIOUS
 REVIEW NOTE #1**
  
 D) NEW NOTES WILL BE ADDED TO THE END AND LABELED **
 NEW NOTES **
  
  
  
  
 1) NOTE: NO, PLEASE SEE NO INFORMATION SPEC ETC WAS
 SUBMITTED FOR ANY EQUIPMENT.
 110.3, 90.7, FBC 106.1.2 ETC
  
 ** PREVIOUS REVIEW NOTE REVIEW #1**
 PLEASE SUBMIT ALL MANUFACTURES SPECS/CUT SHEETS ON THE
 GEN, ATS AND DEPENDING ON PRIME MOVER WHETHER OR NOT A
 SUB BASE TANK IS BEING USED ETC.
 THIS INFORMATION REQUIRED FOR BOTH.
 FBC106.1.2 , NEC110.3,90.8 ETC
  
 2) NOTE: NO/OK PLEASE SEE SOMEINFORMATION WAS
 SUBMITTED FOR LOCATION HOWEVER AS SPECS ETC WAS NOT
 SUBMITTED, REVIEW FOR LOCATION CAN NOT BE CONFIRMED FOR
 CODE COMPLIANCE. PLEASE SEE COMMENTS FROM OTHER TRADES
 WHICH WILL AFFECT THIS.
 PLEASE PROVIDE FLOOD ELEVATION, AND PLEASE KNOW THAT
 BEFORE ANY FINAL, A FLOOD ELEVATION CERTIFICATE WILL BE
 REQUIRED ALSO.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1 **
 COULD NOT LOCATE A NEW SITE PLAN/SURVEY PLEASE INDICATE
 THE GEN LOCATION ON PLANS.IF IN A FLOOD ZONE PLEASE
 SEE BUILDING REVIEW COMMENTS AS ELEVATION IS REQUIRED A
 6" MIN ABOVE
 BFE.
 PLEASE ALSO KNOW A FLOOD ELEVATION CERTIFICATE WILL BE
 REQUIRED BEFORE FINAL.
  
 3) NOTE: NO/OK, PLEASE PROVIDE CONDUIT AND CONDUCTORS
 FROM FPL TRANSFORMER TO GUTTER. PLEASE CORRELATE
 EQUIPMENT SCHEDULE WITH RISER. PLEASE SEE NEW COMMENTS
 FOR ACCESS AND GROUNDING ELECTRODE CONDUCTOR.
 ** SEEMS TO MATCH UP WITH FIGURE 230.9 IN 230.2 OF THE
 2002 NEC HANDBOOK.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1 **
 PLEASE SEE 230.2 AS MORE THAN ONE SERVICE IS BEING
 SHOWN FOR THE ONE BUILDING, HOWEVER COULD NOT LOCATE ON
 PLANS HOW THE SECOND SERVICE BEING PROPOSED CAN BE
 GRANTED UNDER SPECIAL PERMISSION AT THIS TIME.
  
 4) NOTE: OK.
  
 5) NOTE:NO, PLEASE KNOW THAT AT THIS TIME BASED ON NO
 INFORMATION SUBMITTED FOR THE GENERATOR AND THE SERVICE
 ENTRANCE CONDUCTORS FROM THE FPL TRANSFORMER TO THE
 GUTTER, THE GROUNDING ELECTRODE CONDUCTOR SIZE CAN NOT
 BE VERIFIED, PLEASE ALSO SEE 250.66.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1 **
 PLEASECOMPLETE GROUNDING ELECTRODE SYSTEM AS REQUIRED
 PER 250.50.
  
 6) NOTE: NO, PLEASE KNOW AT THIS TIME THE CIRCUITING
 FOR SOME AREAS (STAIRS) WHICH WILL BE UNDER COMMENT #7
 CAN NOT BE VERIFIED.
 PLEASE ALSO SEE NEW COMMENTS.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1**
 PLEASE SHOW ALL CIRCUITING PLANS AND CORRELATE WITH THE
 SUBMITTED PANEL SCHEDULES AND PANEL SCHEDULES TO BE
 SUBMITTED.
 PLEASE SEE 700.12E FOR CIRCUITING OF
 EM/EXT LTS.
  
 7) NOTE: NO, PLEASE SEE THE STAIR AREAS ARE NOT
 COMPLETE AT THIS TIME. PLEASE SEE SOME ARE SHOWN WITH
 CONTROLS BY A PHOTO-CELL WHICH IS NOT PERMITTED. PLEASE
 SEE OTHER STAIRS WHICH ARE MISSING FROM PLANS ON NORTH
 SIDE OF BUILDING. PLEASE SEE THE CENTER STAIRS FROM
 SECOND FLOOR TO THE FIRST FLOOR SPECIFICALLY CONTAINS A
 NOTE WHICH MENTIONS THIS IS NOT AN EXIT.
 PLEASE KNOW THAT DURING AN EMERGENCY CONDITION OR THE
 PANIC THAT MAY OCCUR DURING A FIRE ETC, THE NORMAL
 BUILDING OCCUPANTS/EMPLOYEES OF THIS SECOND FLOOR WHO
 KNOW THIS IS A STAIR WHICH LEADS TO THE FIRST FLOOR
 WILL UTILIZE THIS AS AN EXIT. UNLESS THIS DOOR IS
 SEALED FROM THE OCCUPANTS SO THAT ACCESS IS NOT
 GRANTED, THEN IF ACCESS IS AVAILABLE THEN THIS STAIR
 WILL BE REQUIRED TO MEET 7.8.1.3 AND 7.9.2.
 PLEASE SEE THE BUILDING REVIEW NOTES WITH RESPECT TO
 THE STAIRS PLACING OCCUPANTS BACK INTO A BUILDING OR IN
 THIS CASE ANOTHER TENANT SPACE.
 PLEASE SEE NO PHOTO-METRICS WERE SUBMITTED FOR MINIMUM
 LEVELS FOR EGRESS PATHS ON FIRST FLOOR OR SECOND FLOOR.
 PLEASE SUBMIT AND BE AWARE OF ANY CHANGES FROM OTHER
 TRADES. CONSULTATION WILL BE FORTH COMING WITH THE FIRE
 MARSHAL FOR THE EXITS AND HOW THEY ARE LABELED.
 PLEASE ALSO KNOW THAT THE FAILURE OF ANY SINGLE OVER
 CURRENT PROTECTION DEVICE OR SWITCHING DEVICE CAN NOT
 LEAVE ANY EGRESS PATH IN TOTAL DARKNESS. PLEASE SEE AS
 STAIRS AS SHOWN WITH CONTROLS BY TIMERS/PHOTO-CELLS
 ETC, THESE DEVICES WOULD CREATE SUCH A LIFE SAFETY
 HAZARD. PLEASE SEE THE FAILURE OF THE DEVICE WOULD NOT
 TRIGGER THE EMERGENCY LIGHT TO COME ON AS THE CIRCUIT
 MAY STILL BE ENERGIZED.
 PLEASE SEE THE SELECTION OF THE TYPE OF OVER RIDE
 DEVICE SHOULD BE CHOSEN CAREFULLY AND WILL BE REQUIRED
 TO CONTAIN A SECOND MEANS OF BACK UP FOR CONTROL.
 PLEASE SEE EXIT FROM SOUTH STAIRS STILL DOES NOT
 PROVIDE DIRECTIONAL FOR EXIT WHEN EGRESS FROM STAIR
 DOOR.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1 **
 PLEASE CLARIFY WHERE THE LIGHTING IS FOR ALL STAIRS.
 PLANS APPEAR TO SHOW SOME LIGHTING IN CENTER STAIRWAY,
 HOWEVER NOT FOR OTHERS. PLEASE ALSO SEE STAIRS ARE
 BEING SHOWN ON TIMED SCHEDULE HOWEVER CONTROLS FOR
 LIGHTING OUTSIDE TIME SCHEDULING SHALL BE PROVIDED BY A
 MIN OF TWO METHODS,(OCCUPANCY SENSORS ON LTS, OCCUPANCY
 SENSORS IN STAIRS , TIMED DOOR CONTACTS ETC.) PLEASE
 KNOW, ENTERING INTO THE EXIT STAIR WAY AND HAVING THE
 LIGHTING SHUT OFF AND LEAVE IN TOTAL DARKNESS IS A LIFE
 SAFETY ISSUE.
 PLEASE ALSO PROVIDE BATTERY BACK UP FIXTURES.
 PLEASE ALSO SEE A MINIMUM OF 10 FT CANDLES IS REQUIRED
 UNDER NORMAL AND CAN BE RATED DOWN TO 1FT UNDER EM
 CONDITIONS. PLEASE PROVIDE PHOTO-METRICS. (CAN BE
 TYPICAL)
 PLEASE SEE EXITING FROM STAIRS ON SOUTH SIDE OF
 BUILDING SHOWS EGRESS INTO A HALL WAY WITH NO EXIT
 DIRECTIONAL.
 PLEASE SEE NFPA-101
 7.8,7.8.1.3,7.9,7.9.2.2 ETC.
 PLEASE SEE FIREREVIEW COMMENTS.
 FBC CHAPTER 13
  
 8) NOTE: OK/NO, PLEASE SEE THE ELEVATOR MACHINE ROOM IS
 NOW SHOWN; HOWEVER PLEASE SEE 620.23 AND 24 FOR
 REQUIRED DEDICATED CIRCUITS. PLEASE SEE THESE ARE ON
 THE SAME CIRCUIT.
 PLEASE ALSO SEE NEW NOTES FOR ELEVATOR DISCONNECT.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1**
 COULD NOT LOCATE THE ELEVATOR MACHINE RM.? PLEASE SEE
 620.23, 620.24,
 700.16. ETC
 COULD NOT LOCATE THE MIN CIRCUITING FOR LTS, RECEPTS ,
 CAB ETC.
 PLEASE ALSO KNOW, A BATTERY BACK UP FIXTURE OF SOME
 SORT WILL BE REQUIRED IN THE ELEVATOR EQUIPMENT RM.
 7.8,7.9, 700.16
  
 9) NOTE: OK.
  
 10) NOTE: NO, PLEASE SEE PLANS INDICATE GFI BEING
 PROVIDED WITH THE EQUIPMENT WHICH IS NOT COMMON. PLEASE
 PROVIDE EQUIPMENT INFORMATION SHOWING THE TAP
 CONDUCTORS, OVER CURRENT PROTECTION, MEANS OF
 DISCONNECT ETC.
 IF THIS IS NOT THE CASE, PLEASE SUBMIT AND SHOW THE
 CIRCUITING FOR ALL ROOF TOP EQUIPMENT. CAN NOT RELY ON
 THE EQUIPMENT LEGEND AND PANEL SCHEDULES.
 110.3, 90.7, 240.21, 240.4, 310.16 ETC.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1**
 PLEASE SEE MISSING CIRCUITING ON ROOFTOP PLANS FOR
 UNITS AND GFI RECEPTS FOR ROOFTOPQUIPMENT.
 230.63,210.8
  
 11) NOTE: OK.
  
 12) NOTE: OK.
  
 13) NOTE: NO, PLEASE SEE THERE ARE ROOMS ON PLANS WHICH
 DO NOT INDICATE ANY DESIGNATIONS. PLEASE SEE NEW NOTES
 WITH RESPECT TO PANEL SCHEDULE(S) AND CIRCUITING ON
 PLANS.
 PLEASE SEE NEW NOTES FOR ROOMS WITH PANELS AND OTHER
 ELECTRICAL ROOMS.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1 **
 PLEASE PLACE ALL ROOM AND AREA DESIGNATIONS ON PLANS.
 UNABLE TO VERIFY SOME OF THESE ROOMS AT THIS TIME.
  
 14) NOTE:NO? PLEASE SEE AS SOME OF THE ROOM
 DESIGNATIONS ARE MISSING IT IS NOT CLEAR IF THERE IS AN
 IT ROOM.IT DOES NOT APPEAR THERE WILL BE TRUE IT
 ROOM, HOWEVER PLEASE COMPLETE NOTE #13 ABOVE AND THIS
 SHOULD ALLEAVIATE THIS COMMENT.
 ** PREVIOUS REVIEW NOTE REVIEW #1
 PLEASE SEE PLANS MENTIONS "IT" ROOM ON SECOND FLR.
 PLEASE SEE NFPA-75 AND NFPA-70(NEC) 645 FOR
 REQUIREMENTS.
  
 15) NOTE: OK.
  
 16) NOTE: NO, PLEASE SEE THERE ARE A FEW NOTES
 PERTAINING TO THE ENERGY CALCULATIONS AND LIGHTING
 PERFORMANCE CALCULATIONS.
 A ) PLEASE SEE THE ENERGY CALCULATIONS ARE THE ONES
 PREVIOUSLY SUBMITTED WHICH WERE SIGNED BY THE PREVIOUS
 BUILDING CONTRACTOR WHICH IS NO LONGER APART OF THIS
 PROJECT. PLEASE OBTAIN NEW SIGNATURES.
 B) PLEASE SEE THAT NO LIGHTING PERFORMANCE TABLES,
 CHARTS, LEVELS ETC WERE SUBMITTED AND METHOD *A* DOES
 NOT PROVIDE THIS INFORMATION. PLEASE ALSO CLARIFY THE
 USE OF METHOD *A*, AS THE A-SHEETS INDICATE A LEVEL 3
 ALTERATION, HOWEVER PLEASE SEE NEW NOTES FOR THIS AS
 THIS IS A CHANGE IN OCCUPANCY AND DOES APPEAR TO FALL
 UNDER A LEVEL 3 ALTERATION. PLEASE SEE FBC CHAPTER
 13-101.3
 C) PLEASE SEE SOME AREAS IN THE INPUT DATA REPORT WHICH
 INDICATES MANUAL CONTROLS, HOW IS THIS POSSIBLE IF ALL
 LIGHTING CONTAINS AUTOMATED CONTROLS?
  
 **PLEASE SEE NEW NOTES PERTAINING TO LIGHTING
 CONTROLS.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1**
 PLEASE SEE 13-415.2.ABC.1, TABLES 415.2.C.1, 415.2.B.1
  
 17) NOTE: NO, PLEASE SEE RISER SHOWS THE SECOND FLOOR
 ATS AS BEING LABELED WITH THE SAME DESIGNATION AS THE
 FIRST FLOOR ATS.
 PLEASE SEE THE ELEVATOR CIRCUITS WHICH IS SHOWN AS
 225AMPS IN PANEL M-2, YET THE EQUIPMENT LEGEND SHOWS
 200AMP DISCONNECT?
 PLEAS ADJUST AND COORDINATE.
 240.4, 310.16.
 106.1.2 ADMIN SECTION.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1 **
 PLEASE SEE "EQUIPMENT CO-ORDINATION SCHEDULE", PLEASE
 SEE MAINS DISCONNECTS WHICH ARE INDEED MAINS AND PLEASE
 ALSO SEE MAINS FOR EACH FLR ALSO BEING LABELED AS
 "MAINS" 1 AND 2.
 PLEASE ADJUSTED IDENTIFICATION ACCORDINGLY.
 230.2E
  
  
 ***** NEW NOTES *****
  
 18) NOTE: PLEASE SEE ACCESS FOR THE MAIN DISCONNECT AND
 GENERATOR DISCONNECT AND EQUIPMENT FOR THE POWER FOR
 THE SECOND FLOOR TENANT APPEARS TO ONLY BE ACCESSED
 THROUGH THE FIRST FLOOR TENANT SPACE. PLEASE SEE A
 REDESIGN WILL BE REQUIRED AS ACCESS TO THIS EQUIPMENT
 IS REQUIRED FOR THIS 2ND FLOOR TENANT AT ALL TIMES.
 (OUTSIDE DOOR) ETC 240.24B ETC
  
 19) NOTE: PLEASE SEE PREVIOUS NOTES WITH RESPECT TO
 ROOM DESIGNATIONS, PLEASE SEE ROOM/AREA WHERE PANEL
 *S3* IS LOCATED.
 110.26, 408.7, 240.24D
  
 20) NOTE: PLEASE SEE FBC CHAPTER 13, 13-415.1.ABC.1.1,
 .1.2 AND .1.3.
 A) PLEASE PROVIDE THE TIME OF DAY SCHEDULING FOR LC
 PANELS.
 B) PLEASE SEE WOMEN'S BATHROOM ON FIRST FLOOR WHICH
 CONTAINS A DEVICE*S UC*WHICH IS NOT ON ANY SYMBOL
 LEGEND. ?
 C) PLEASE SEE A SWITCH WITH A DESIGNATION OF *S M*
 WHICH IS NOT ON ANY SYMBOL LEGEND.?
 D) PLEASE PROVIDE ALL MAXIMUM TIMES ON OVER
 RIDES/OCCUPANCY SENSORS/TIMER TYPE DEVICES.
 E) PLEASE SEE OC TYPE IS 30 MINUTES MAX AND TIMER TYPES
 ARE 4HRS MAX.
 F) PLEASE SEE HALL AREAS WHICH CONTAIN OVER RIDE
 DEVICES WHICH ARE SHOWN AS *S M*, DO THESE PROVIDE
 COMPLETE COVERAGE OF THE ENTIRE HALL WAY AREA BEING
 OVER RIDDEN WHEN TIMED SCHEDULING IS OFF. AS THIS
 DEVICE APPEARS TO BE A MOTION TYPE DEVICE, PLEASE
 VERIFY AS LOCATING *NIGHT LIGHTS* ON PLANS COULD NOT BE
 FOUNDIN THE EVENT OF THESE DEVICES NOT BEING ABLE TO
 DETECT THE OCCUPANT AND LEAVING THE OCCUPANT IN TOTAL
 DARKNESS.
 PLEASE SEE LS 101 7.8 AND 7.9 FOR THIS AS NOTED ABOVE
 IN THE PREVIOUS REVIEW NOTE #7.
  
 21) NOTE: PLEASE SEE PANEL SCHEDULE SHOULD BE MORE
 DETAILED FOR ROOMS AND AREAS WHICH THEY FEED. PLEASE
 SEE THE BELOW IS TAKEN FROM THE COMMENTARY FROM THE
 HANDBOOK IN 408.4. PLEASE SEE ALL THE CIRCUITS WHICH
 ONLY INDICATE *RECEPTACLES* AND NOT TO ANY ROOMS/OFFICE
 DESIGNATIONS.
 * REQUIRES THAT THE IDENTIFICATION FOR EVERY CIRCUIT
 SUPPLIED BY A PANELBOARD OR SWITCHBOARD BE LEGIBLE AND
 CLEARLY STATE THE SPECIFIC PURPOSE FOR WHICH THE
 CIRCUIT IS USED. CIRCUITS USED FOR THE SAME PURPOSE
 MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR EXAMPLE,
 SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY OUTLETS IN
 THE KITCHEN, DINING ROOM, AND KITCHEN COUNTERTOPS.
 IDENTIFYING THE CIRCUITS AS SMALL APPLIANCE BRANCH
 CIRCUITS IS NOT ACCEPTABLE; INSTEAD, THEY SHOULD BE
 IDENTIFIED AS ``KITCHEN WALL RECEPTACLES,'' ``DINING
 ROOM FLOOR RECEPTACLE,'' OR ``KITCHEN COUNTERTOP
 RECEPTACLES LEFT OF SINK.'' CIRCUIT DIRECTORIES
 CONTAINING MULTIPLE ENTRIES WITH ONLY ``LIGHTS'' OR
 ``OUTLETS'' DO NOT PROVIDE THE SUFFICIENT DETAIL
 REQUIRED BY THIS SECTION.
  
 22) NOTE: PLEASE SEE THAT ANY COMMON AREA BRANCH
 CIRCUITS SHALL BE REQUIRED TO BE FED FROM A HOUSE PANEL
 OF SOME TYPE, NOT FROM A TENANT PANEL.
 *GEN ROOM*, *MAIN ELECTRICAL ROOM*.
 104.6 FBC ADMIN SECTION.
  
 23) NOTE: PLEASE SEE ATTACHED NOTICE TO FS 553.80(2)(B)
 IS GIVEN AT THIS TIME WITH RESPECT TO CODE COMMENTS.
 PLEASE KNOW THAT THIS IS ONLY GIVEN AS A NOTICE AT THIS
 TIME.
  
 ** PLEASE KNOW AS THERE IS INFORMATION NOT YET
 SUBMITTED, COMMENTS MAY NOT BE COMPLETE AT THIS TIME.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved