Date |
Text |
2007-02-04 17:54:34 | ******* UNSAT 2ND REVIEW ****** |
| |
| *** PLEASE SEE THERE ARE ITEMS FROM THE PREVIOUS REVIEW |
| WHICH STILL NEED TO BE ADDRESSED ALONG WITH NEW |
| COMMENTS BASED ON CHANGES IN PLANS AND NEW INFORMATION |
| AND/OR CHANGES MADE TO PLANS. |
| |
| **** IMPORTANT**** |
| |
| ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM |
| THE PREVIOUS REVIEW WITH A *NO*, *OK* OR *NO/OK*. |
| |
| A) A, NO WILL CONTAIN A FURTHER EXPLANATION AS TO WHY |
| THE COMMENT MAY NOT HAVE BEEN FULLY ADDRESSED WITH THE |
| PREVIOUS REVIEW NOTE BELOW WITH **PREVIOUS REVIEW NOTE |
| #1** |
| |
| B) A, OK, WILL HAVE NO COMMENTS EXCEPT PERHAPS A |
| REFERENCE TO SEE ** NEW NOTES*. THE PREVIOUS REVIEW |
| NOTE WILL BE REMOVED. |
| |
| C) A, NO/OK, WILL HAVE FURTHER EXPLANATION AS PART OF |
| THE COMMENT MAY HAVE BEEN ADDRESSED, HOWEVER NOT ALL. |
| THE PREVIOUS REVIEW NOTE WILL BE NOTED **PREVIOUS |
| REVIEW NOTE #1** |
| |
| D) NEW NOTES WILL BE ADDED TO THE END AND LABELED ** |
| NEW NOTES ** |
| |
| |
| |
| |
| 1) NOTE: NO, PLEASE SEE NO INFORMATION SPEC ETC WAS |
| SUBMITTED FOR ANY EQUIPMENT. |
| 110.3, 90.7, FBC 106.1.2 ETC |
| |
| ** PREVIOUS REVIEW NOTE REVIEW #1** |
| PLEASE SUBMIT ALL MANUFACTURES SPECS/CUT SHEETS ON THE |
| GEN, ATS AND DEPENDING ON PRIME MOVER WHETHER OR NOT A |
| SUB BASE TANK IS BEING USED ETC. |
| THIS INFORMATION REQUIRED FOR BOTH. |
| FBC106.1.2 , NEC110.3,90.8 ETC |
| |
| 2) NOTE: NO/OK PLEASE SEE SOMEINFORMATION WAS |
| SUBMITTED FOR LOCATION HOWEVER AS SPECS ETC WAS NOT |
| SUBMITTED, REVIEW FOR LOCATION CAN NOT BE CONFIRMED FOR |
| CODE COMPLIANCE. PLEASE SEE COMMENTS FROM OTHER TRADES |
| WHICH WILL AFFECT THIS. |
| PLEASE PROVIDE FLOOD ELEVATION, AND PLEASE KNOW THAT |
| BEFORE ANY FINAL, A FLOOD ELEVATION CERTIFICATE WILL BE |
| REQUIRED ALSO. |
| |
| ** PREVIOUS REVIEW NOTE REVIEW #1 ** |
| COULD NOT LOCATE A NEW SITE PLAN/SURVEY PLEASE INDICATE |
| THE GEN LOCATION ON PLANS.IF IN A FLOOD ZONE PLEASE |
| SEE BUILDING REVIEW COMMENTS AS ELEVATION IS REQUIRED A |
| 6" MIN ABOVE |
| BFE. |
| PLEASE ALSO KNOW A FLOOD ELEVATION CERTIFICATE WILL BE |
| REQUIRED BEFORE FINAL. |
| |
| 3) NOTE: NO/OK, PLEASE PROVIDE CONDUIT AND CONDUCTORS |
| FROM FPL TRANSFORMER TO GUTTER. PLEASE CORRELATE |
| EQUIPMENT SCHEDULE WITH RISER. PLEASE SEE NEW COMMENTS |
| FOR ACCESS AND GROUNDING ELECTRODE CONDUCTOR. |
| ** SEEMS TO MATCH UP WITH FIGURE 230.9 IN 230.2 OF THE |
| 2002 NEC HANDBOOK. |
| |
| ** PREVIOUS REVIEW NOTE REVIEW #1 ** |
| PLEASE SEE 230.2 AS MORE THAN ONE SERVICE IS BEING |
| SHOWN FOR THE ONE BUILDING, HOWEVER COULD NOT LOCATE ON |
| PLANS HOW THE SECOND SERVICE BEING PROPOSED CAN BE |
| GRANTED UNDER SPECIAL PERMISSION AT THIS TIME. |
| |
| 4) NOTE: OK. |
| |
| 5) NOTE:NO, PLEASE KNOW THAT AT THIS TIME BASED ON NO |
| INFORMATION SUBMITTED FOR THE GENERATOR AND THE SERVICE |
| ENTRANCE CONDUCTORS FROM THE FPL TRANSFORMER TO THE |
| GUTTER, THE GROUNDING ELECTRODE CONDUCTOR SIZE CAN NOT |
| BE VERIFIED, PLEASE ALSO SEE 250.66. |
| |
| ** PREVIOUS REVIEW NOTE REVIEW #1 ** |
| PLEASECOMPLETE GROUNDING ELECTRODE SYSTEM AS REQUIRED |
| PER 250.50. |
| |
| 6) NOTE: NO, PLEASE KNOW AT THIS TIME THE CIRCUITING |
| FOR SOME AREAS (STAIRS) WHICH WILL BE UNDER COMMENT #7 |
| CAN NOT BE VERIFIED. |
| PLEASE ALSO SEE NEW COMMENTS. |
| |
| ** PREVIOUS REVIEW NOTE REVIEW #1** |
| PLEASE SHOW ALL CIRCUITING PLANS AND CORRELATE WITH THE |
| SUBMITTED PANEL SCHEDULES AND PANEL SCHEDULES TO BE |
| SUBMITTED. |
| PLEASE SEE 700.12E FOR CIRCUITING OF |
| EM/EXT LTS. |
| |
| 7) NOTE: NO, PLEASE SEE THE STAIR AREAS ARE NOT |
| COMPLETE AT THIS TIME. PLEASE SEE SOME ARE SHOWN WITH |
| CONTROLS BY A PHOTO-CELL WHICH IS NOT PERMITTED. PLEASE |
| SEE OTHER STAIRS WHICH ARE MISSING FROM PLANS ON NORTH |
| SIDE OF BUILDING. PLEASE SEE THE CENTER STAIRS FROM |
| SECOND FLOOR TO THE FIRST FLOOR SPECIFICALLY CONTAINS A |
| NOTE WHICH MENTIONS THIS IS NOT AN EXIT. |
| PLEASE KNOW THAT DURING AN EMERGENCY CONDITION OR THE |
| PANIC THAT MAY OCCUR DURING A FIRE ETC, THE NORMAL |
| BUILDING OCCUPANTS/EMPLOYEES OF THIS SECOND FLOOR WHO |
| KNOW THIS IS A STAIR WHICH LEADS TO THE FIRST FLOOR |
| WILL UTILIZE THIS AS AN EXIT. UNLESS THIS DOOR IS |
| SEALED FROM THE OCCUPANTS SO THAT ACCESS IS NOT |
| GRANTED, THEN IF ACCESS IS AVAILABLE THEN THIS STAIR |
| WILL BE REQUIRED TO MEET 7.8.1.3 AND 7.9.2. |
| PLEASE SEE THE BUILDING REVIEW NOTES WITH RESPECT TO |
| THE STAIRS PLACING OCCUPANTS BACK INTO A BUILDING OR IN |
| THIS CASE ANOTHER TENANT SPACE. |
| PLEASE SEE NO PHOTO-METRICS WERE SUBMITTED FOR MINIMUM |
| LEVELS FOR EGRESS PATHS ON FIRST FLOOR OR SECOND FLOOR. |
| PLEASE SUBMIT AND BE AWARE OF ANY CHANGES FROM OTHER |
| TRADES. CONSULTATION WILL BE FORTH COMING WITH THE FIRE |
| MARSHAL FOR THE EXITS AND HOW THEY ARE LABELED. |
| PLEASE ALSO KNOW THAT THE FAILURE OF ANY SINGLE OVER |
| CURRENT PROTECTION DEVICE OR SWITCHING DEVICE CAN NOT |
| LEAVE ANY EGRESS PATH IN TOTAL DARKNESS. PLEASE SEE AS |
| STAIRS AS SHOWN WITH CONTROLS BY TIMERS/PHOTO-CELLS |
| ETC, THESE DEVICES WOULD CREATE SUCH A LIFE SAFETY |
| HAZARD. PLEASE SEE THE FAILURE OF THE DEVICE WOULD NOT |
| TRIGGER THE EMERGENCY LIGHT TO COME ON AS THE CIRCUIT |
| MAY STILL BE ENERGIZED. |
| PLEASE SEE THE SELECTION OF THE TYPE OF OVER RIDE |
| DEVICE SHOULD BE CHOSEN CAREFULLY AND WILL BE REQUIRED |
| TO CONTAIN A SECOND MEANS OF BACK UP FOR CONTROL. |
| PLEASE SEE EXIT FROM SOUTH STAIRS STILL DOES NOT |
| PROVIDE DIRECTIONAL FOR EXIT WHEN EGRESS FROM STAIR |
| DOOR. |
| |
| ** PREVIOUS REVIEW NOTE REVIEW #1 ** |
| PLEASE CLARIFY WHERE THE LIGHTING IS FOR ALL STAIRS. |
| PLANS APPEAR TO SHOW SOME LIGHTING IN CENTER STAIRWAY, |
| HOWEVER NOT FOR OTHERS. PLEASE ALSO SEE STAIRS ARE |
| BEING SHOWN ON TIMED SCHEDULE HOWEVER CONTROLS FOR |
| LIGHTING OUTSIDE TIME SCHEDULING SHALL BE PROVIDED BY A |
| MIN OF TWO METHODS,(OCCUPANCY SENSORS ON LTS, OCCUPANCY |
| SENSORS IN STAIRS , TIMED DOOR CONTACTS ETC.) PLEASE |
| KNOW, ENTERING INTO THE EXIT STAIR WAY AND HAVING THE |
| LIGHTING SHUT OFF AND LEAVE IN TOTAL DARKNESS IS A LIFE |
| SAFETY ISSUE. |
| PLEASE ALSO PROVIDE BATTERY BACK UP FIXTURES. |
| PLEASE ALSO SEE A MINIMUM OF 10 FT CANDLES IS REQUIRED |
| UNDER NORMAL AND CAN BE RATED DOWN TO 1FT UNDER EM |
| CONDITIONS. PLEASE PROVIDE PHOTO-METRICS. (CAN BE |
| TYPICAL) |
| PLEASE SEE EXITING FROM STAIRS ON SOUTH SIDE OF |
| BUILDING SHOWS EGRESS INTO A HALL WAY WITH NO EXIT |
| DIRECTIONAL. |
| PLEASE SEE NFPA-101 |
| 7.8,7.8.1.3,7.9,7.9.2.2 ETC. |
| PLEASE SEE FIREREVIEW COMMENTS. |
| FBC CHAPTER 13 |
| |
| 8) NOTE: OK/NO, PLEASE SEE THE ELEVATOR MACHINE ROOM IS |
| NOW SHOWN; HOWEVER PLEASE SEE 620.23 AND 24 FOR |
| REQUIRED DEDICATED CIRCUITS. PLEASE SEE THESE ARE ON |
| THE SAME CIRCUIT. |
| PLEASE ALSO SEE NEW NOTES FOR ELEVATOR DISCONNECT. |
| |
| ** PREVIOUS REVIEW NOTE REVIEW #1** |
| COULD NOT LOCATE THE ELEVATOR MACHINE RM.? PLEASE SEE |
| 620.23, 620.24, |
| 700.16. ETC |
| COULD NOT LOCATE THE MIN CIRCUITING FOR LTS, RECEPTS , |
| CAB ETC. |
| PLEASE ALSO KNOW, A BATTERY BACK UP FIXTURE OF SOME |
| SORT WILL BE REQUIRED IN THE ELEVATOR EQUIPMENT RM. |
| 7.8,7.9, 700.16 |
| |
| 9) NOTE: OK. |
| |
| 10) NOTE: NO, PLEASE SEE PLANS INDICATE GFI BEING |
| PROVIDED WITH THE EQUIPMENT WHICH IS NOT COMMON. PLEASE |
| PROVIDE EQUIPMENT INFORMATION SHOWING THE TAP |
| CONDUCTORS, OVER CURRENT PROTECTION, MEANS OF |
| DISCONNECT ETC. |
| IF THIS IS NOT THE CASE, PLEASE SUBMIT AND SHOW THE |
| CIRCUITING FOR ALL ROOF TOP EQUIPMENT. CAN NOT RELY ON |
| THE EQUIPMENT LEGEND AND PANEL SCHEDULES. |
| 110.3, 90.7, 240.21, 240.4, 310.16 ETC. |
| |
| ** PREVIOUS REVIEW NOTE REVIEW #1** |
| PLEASE SEE MISSING CIRCUITING ON ROOFTOP PLANS FOR |
| UNITS AND GFI RECEPTS FOR ROOFTOPQUIPMENT. |
| 230.63,210.8 |
| |
| 11) NOTE: OK. |
| |
| 12) NOTE: OK. |
| |
| 13) NOTE: NO, PLEASE SEE THERE ARE ROOMS ON PLANS WHICH |
| DO NOT INDICATE ANY DESIGNATIONS. PLEASE SEE NEW NOTES |
| WITH RESPECT TO PANEL SCHEDULE(S) AND CIRCUITING ON |
| PLANS. |
| PLEASE SEE NEW NOTES FOR ROOMS WITH PANELS AND OTHER |
| ELECTRICAL ROOMS. |
| |
| ** PREVIOUS REVIEW NOTE REVIEW #1 ** |
| PLEASE PLACE ALL ROOM AND AREA DESIGNATIONS ON PLANS. |
| UNABLE TO VERIFY SOME OF THESE ROOMS AT THIS TIME. |
| |
| 14) NOTE:NO? PLEASE SEE AS SOME OF THE ROOM |
| DESIGNATIONS ARE MISSING IT IS NOT CLEAR IF THERE IS AN |
| IT ROOM.IT DOES NOT APPEAR THERE WILL BE TRUE IT |
| ROOM, HOWEVER PLEASE COMPLETE NOTE #13 ABOVE AND THIS |
| SHOULD ALLEAVIATE THIS COMMENT. |
| ** PREVIOUS REVIEW NOTE REVIEW #1 |
| PLEASE SEE PLANS MENTIONS "IT" ROOM ON SECOND FLR. |
| PLEASE SEE NFPA-75 AND NFPA-70(NEC) 645 FOR |
| REQUIREMENTS. |
| |
| 15) NOTE: OK. |
| |
| 16) NOTE: NO, PLEASE SEE THERE ARE A FEW NOTES |
| PERTAINING TO THE ENERGY CALCULATIONS AND LIGHTING |
| PERFORMANCE CALCULATIONS. |
| A ) PLEASE SEE THE ENERGY CALCULATIONS ARE THE ONES |
| PREVIOUSLY SUBMITTED WHICH WERE SIGNED BY THE PREVIOUS |
| BUILDING CONTRACTOR WHICH IS NO LONGER APART OF THIS |
| PROJECT. PLEASE OBTAIN NEW SIGNATURES. |
| B) PLEASE SEE THAT NO LIGHTING PERFORMANCE TABLES, |
| CHARTS, LEVELS ETC WERE SUBMITTED AND METHOD *A* DOES |
| NOT PROVIDE THIS INFORMATION. PLEASE ALSO CLARIFY THE |
| USE OF METHOD *A*, AS THE A-SHEETS INDICATE A LEVEL 3 |
| ALTERATION, HOWEVER PLEASE SEE NEW NOTES FOR THIS AS |
| THIS IS A CHANGE IN OCCUPANCY AND DOES APPEAR TO FALL |
| UNDER A LEVEL 3 ALTERATION. PLEASE SEE FBC CHAPTER |
| 13-101.3 |
| C) PLEASE SEE SOME AREAS IN THE INPUT DATA REPORT WHICH |
| INDICATES MANUAL CONTROLS, HOW IS THIS POSSIBLE IF ALL |
| LIGHTING CONTAINS AUTOMATED CONTROLS? |
| |
| **PLEASE SEE NEW NOTES PERTAINING TO LIGHTING |
| CONTROLS. |
| |
| ** PREVIOUS REVIEW NOTE REVIEW #1** |
| PLEASE SEE 13-415.2.ABC.1, TABLES 415.2.C.1, 415.2.B.1 |
| |
| 17) NOTE: NO, PLEASE SEE RISER SHOWS THE SECOND FLOOR |
| ATS AS BEING LABELED WITH THE SAME DESIGNATION AS THE |
| FIRST FLOOR ATS. |
| PLEASE SEE THE ELEVATOR CIRCUITS WHICH IS SHOWN AS |
| 225AMPS IN PANEL M-2, YET THE EQUIPMENT LEGEND SHOWS |
| 200AMP DISCONNECT? |
| PLEAS ADJUST AND COORDINATE. |
| 240.4, 310.16. |
| 106.1.2 ADMIN SECTION. |
| |
| ** PREVIOUS REVIEW NOTE REVIEW #1 ** |
| PLEASE SEE "EQUIPMENT CO-ORDINATION SCHEDULE", PLEASE |
| SEE MAINS DISCONNECTS WHICH ARE INDEED MAINS AND PLEASE |
| ALSO SEE MAINS FOR EACH FLR ALSO BEING LABELED AS |
| "MAINS" 1 AND 2. |
| PLEASE ADJUSTED IDENTIFICATION ACCORDINGLY. |
| 230.2E |
| |
| |
| ***** NEW NOTES ***** |
| |
| 18) NOTE: PLEASE SEE ACCESS FOR THE MAIN DISCONNECT AND |
| GENERATOR DISCONNECT AND EQUIPMENT FOR THE POWER FOR |
| THE SECOND FLOOR TENANT APPEARS TO ONLY BE ACCESSED |
| THROUGH THE FIRST FLOOR TENANT SPACE. PLEASE SEE A |
| REDESIGN WILL BE REQUIRED AS ACCESS TO THIS EQUIPMENT |
| IS REQUIRED FOR THIS 2ND FLOOR TENANT AT ALL TIMES. |
| (OUTSIDE DOOR) ETC 240.24B ETC |
| |
| 19) NOTE: PLEASE SEE PREVIOUS NOTES WITH RESPECT TO |
| ROOM DESIGNATIONS, PLEASE SEE ROOM/AREA WHERE PANEL |
| *S3* IS LOCATED. |
| 110.26, 408.7, 240.24D |
| |
| 20) NOTE: PLEASE SEE FBC CHAPTER 13, 13-415.1.ABC.1.1, |
| .1.2 AND .1.3. |
| A) PLEASE PROVIDE THE TIME OF DAY SCHEDULING FOR LC |
| PANELS. |
| B) PLEASE SEE WOMEN'S BATHROOM ON FIRST FLOOR WHICH |
| CONTAINS A DEVICE*S UC*WHICH IS NOT ON ANY SYMBOL |
| LEGEND. ? |
| C) PLEASE SEE A SWITCH WITH A DESIGNATION OF *S M* |
| WHICH IS NOT ON ANY SYMBOL LEGEND.? |
| D) PLEASE PROVIDE ALL MAXIMUM TIMES ON OVER |
| RIDES/OCCUPANCY SENSORS/TIMER TYPE DEVICES. |
| E) PLEASE SEE OC TYPE IS 30 MINUTES MAX AND TIMER TYPES |
| ARE 4HRS MAX. |
| F) PLEASE SEE HALL AREAS WHICH CONTAIN OVER RIDE |
| DEVICES WHICH ARE SHOWN AS *S M*, DO THESE PROVIDE |
| COMPLETE COVERAGE OF THE ENTIRE HALL WAY AREA BEING |
| OVER RIDDEN WHEN TIMED SCHEDULING IS OFF. AS THIS |
| DEVICE APPEARS TO BE A MOTION TYPE DEVICE, PLEASE |
| VERIFY AS LOCATING *NIGHT LIGHTS* ON PLANS COULD NOT BE |
| FOUNDIN THE EVENT OF THESE DEVICES NOT BEING ABLE TO |
| DETECT THE OCCUPANT AND LEAVING THE OCCUPANT IN TOTAL |
| DARKNESS. |
| PLEASE SEE LS 101 7.8 AND 7.9 FOR THIS AS NOTED ABOVE |
| IN THE PREVIOUS REVIEW NOTE #7. |
| |
| 21) NOTE: PLEASE SEE PANEL SCHEDULE SHOULD BE MORE |
| DETAILED FOR ROOMS AND AREAS WHICH THEY FEED. PLEASE |
| SEE THE BELOW IS TAKEN FROM THE COMMENTARY FROM THE |
| HANDBOOK IN 408.4. PLEASE SEE ALL THE CIRCUITS WHICH |
| ONLY INDICATE *RECEPTACLES* AND NOT TO ANY ROOMS/OFFICE |
| DESIGNATIONS. |
| * REQUIRES THAT THE IDENTIFICATION FOR EVERY CIRCUIT |
| SUPPLIED BY A PANELBOARD OR SWITCHBOARD BE LEGIBLE AND |
| CLEARLY STATE THE SPECIFIC PURPOSE FOR WHICH THE |
| CIRCUIT IS USED. CIRCUITS USED FOR THE SAME PURPOSE |
| MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR EXAMPLE, |
| SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY OUTLETS IN |
| THE KITCHEN, DINING ROOM, AND KITCHEN COUNTERTOPS. |
| IDENTIFYING THE CIRCUITS AS SMALL APPLIANCE BRANCH |
| CIRCUITS IS NOT ACCEPTABLE; INSTEAD, THEY SHOULD BE |
| IDENTIFIED AS ``KITCHEN WALL RECEPTACLES,'' ``DINING |
| ROOM FLOOR RECEPTACLE,'' OR ``KITCHEN COUNTERTOP |
| RECEPTACLES LEFT OF SINK.'' CIRCUIT DIRECTORIES |
| CONTAINING MULTIPLE ENTRIES WITH ONLY ``LIGHTS'' OR |
| ``OUTLETS'' DO NOT PROVIDE THE SUFFICIENT DETAIL |
| REQUIRED BY THIS SECTION. |
| |
| 22) NOTE: PLEASE SEE THAT ANY COMMON AREA BRANCH |
| CIRCUITS SHALL BE REQUIRED TO BE FED FROM A HOUSE PANEL |
| OF SOME TYPE, NOT FROM A TENANT PANEL. |
| *GEN ROOM*, *MAIN ELECTRICAL ROOM*. |
| 104.6 FBC ADMIN SECTION. |
| |
| 23) NOTE: PLEASE SEE ATTACHED NOTICE TO FS 553.80(2)(B) |
| IS GIVEN AT THIS TIME WITH RESPECT TO CODE COMMENTS. |
| PLEASE KNOW THAT THIS IS ONLY GIVEN AS A NOTICE AT THIS |
| TIME. |
| |
| ** PLEASE KNOW AS THERE IS INFORMATION NOT YET |
| SUBMITTED, COMMENTS MAY NOT BE COMPLETE AT THIS TIME. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |