Plan Review Notes For Permit 06071722
Permit Number 06071722
Review Stop P
Sequence Number 1
Notes
Date Text
2006-08-22 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 NFPA 99C
  
 1. ALL ARCHITECTURAL SHEETS. THE ADDRESS
 OF THE ARCHITECTURAL BUSINESS ON THE
 TITLE BLOCK DOES NOT REFLECT THE ADDRESS
 SHOWN ON THE RECORDS AT DBPR. (SEE
 ATTACHED SHEET). PER FAC 61G1-16.004(1)
 THE ADDRESS MUST BE SHOWN IN THE TITLE
 BLOCK. FS 481-2055.
  
 2. ALL ARCHITECTURAL SHEETS. THE SEAL
 SHALL CONTAIN THE REGISTRATION NUMBER OF
 THE ARCHITECT. NO NUMBER HAS BEEN
 IMPRESSED ON THE SHEETS IN THE SEAL. FAC 61G1-16.002(1)
 & FS 481.2055.
  
 3. SHTS A2.01 & A2.02 THE FIRST FLOOR
 FINISH SCHEDULE FOR ROOMS 103, 104, 118,
 (WOMEN, UNISEX HDCP, & MEN TOILET ROOMS)
 AS WELL AS ROOMS 202, 205, 208, & 210
 TOILET ROOMS INDICATE PAINTED MR GWB FOR
 THE WALLS. PLEASE SHOW HOW THIS COMPLIES
 WITH SECTION 1210.2 REQUIREMENTS FOR
 WALLS TO BE HARD & NON-ABSORBENT.
  
 4. SHT A2.01 THE BREAK ROOM SINK AND SHT
 A2.02 THE STAFF LOUNGE SINK SHALL BE
 ACCESSIBLE. SUBMIT DETAILS SHOWING
 COMPLIANCE WITH SECTION 11-4.24 AND ALL SUBSECTIONS.
 (FORWARD APPROACH REQUIRED,
 AND NO CABINET DOORS ALLOWED IN CLEAR
 FLOOR SPACE).
  
 5. SHT A6.01 UNISEX TOILET ROOM - 104
 SHOW THE CLEAR FLOOR SPACE FOR THE W/C
 AND LAV, AND SHOW THE TURNING AREA.
 SECTIONS 11-4.16.2, 11-4.16.3, AND
 11-4.22.3.
  
 6. SHT A6.01 DETAILS 1, 2, 3, & TOILET
 ACCESSORY LEGEND REFERENCE COMPLIANCE
 WITH 1997 EDITION ACCESSIBILITY. DESIGN
 REQUIRED TO BE COMPLIANT WITH FBC-2004
 CHAPTER 11. PLEASE CHANGE REFERENCE.
  
 7. SUBMIT A DETAIL SHOWING COMPLIANCE
 WITH SECTION 11-4.15 AND ALL SUBSECTIONS
 FOR THE DRINKING FOUNTAINS.
  
 8. SHTS P3.1 & P3.2 AND RPZV BACKFLOW IS
 REQUIRED ON THE WATER SERVICE AS CLOSE
 TO THE METER AS POSSIBLE, ON PRIVATE
 PROPERTY. SECTION 608.13.2 AND MUNICIPAL
 ORDINANCE 2853-95.
  
 9. SHT P3.2 FULL OPEN VALVES SHALL BE
 INSTALLED ON THE BASE OF EVERY WATER
 RISER PIPE, AND ON THE TOP OF EVERY
 WATER DOWN-FEED PIPE. SECTION 606.1(3) & 606.1(4).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]