Plan Review Notes
Plan Review Notes For Permit 06071722
Permit Number 06071722
Review Stop MEDGAS
Sequence Number 1
Notes
Date Text
2007-12-20 15:46:00REVISION DENIED
 REFERENCE: FBC-2004 CHAPTER 1
 NFPA 99C-99
  
 1. SUBMITISOMETRIC RISER DIAGRAMS FOR THE VACUUM
 PIPING AND THE COMPRESSED AIR PIPING. SECTION
 106.3.5.1.3.
  
 2. SHT P-3.3 THE VACUUM SYSTEM SHALL COMPLY WITH
 SECTION 4-5.2 AND ALL SUBSECTIONS. SHOW COMPLIANCE WITH
 THE FOLLOWING:
 A. 4-5.2.1.1 SERVICE INLETS SHALL BE EITHER A SHUT
 OFF VALVE WITH A THREADED FEMALE PIPE CONNECTOR, OR A
 QUICK-CONNECT FITTING WITH A SINGLE CHECK VALVE.
 B. 4-5.2.1.2 LIQUID/AIR SEPARATOR (EQUIPMENT SHALL BE
 OBTAINED FROM AND BE INSTALLED UNDER THE SUPERVISION OF
 A MANUF. OR SUPPLIER FAMILIAR WITH PROPER PRACTICES FOR
 ITS CONSTRUCTION AND USE). (SEE FIGS. 4-5.2.1.2 A THRU
 D.
 C. 4-5.2.1.3 LIQUIDS FROM A LEVEL VACUUM SYSTEM, PER
 4-5.2.2, SHALL BE DIRECTLY CONNECTED TO THE SANITARY
 DRAINAGE SYSTEM. (SEE FIGURES 4-5.2.1.3(A) THRU(B).
 (SEE ATTACHED SHEETS). (SHOWN AS INDIRECT CONNECTION ON
 FIGURE 2 SHT P-3.3).
 D. 4-5.2.1.5 EXHAUST SHALL BE LOCATED REMOTE FROM ANY
 DOOR, WINDOW, AIR INTAKE, OR OTHER OPENING IN THE
 BUILDING ETC.
 E. 4-5.2.1.6 EXHAUST PROTECT AGAINST ENTRY OF INSECTS
 ETC.
 F. 4-5.2.2.1 CLEANOUTS REQUIRED.
 G. 4-5.2.2.3 CLEANOUTS REQUIRED.
 H. 4-5.2.2.5 PIPING TO BE SLOPED .
  
 3. SHT P-3.3 THE GAS-POWERED DEVICES LEVEL 3 SHALL
 COMPLY WITH SECTION 4-5.1.1 AND ALL SUBSECTIONS. SHOW
 COMPLIANCE WITH THE FOLLOWING:
 A. 4-5.1.1.3(A)(D)(E)(G)(H) INTAKE SHALL BE FROM THE
 OUTSIDE WHEN PRACTICAL.
 B. 4-5.1.3.3(A) THRU (I)
  
 4. SEE ATTACHED SHEETS FOR TYPICAL LEVEL 3 VACUUM AND
 AND GAS POWERED DEVICES SUPPLY SYSTEMS.
  
 5. A SEPARATE MED-GAS PERMIT IS REQUIRED.
 CERTIFICATIONS FOR THE QUALIFER, THE BRAZER, &
 INSTALLER ARE REQUIRED WHEN APPYING FOR THE PERMIT.
 PICTURE IDENTIFICATION IS REQUIRED ON THE
 CERTIFICATIONS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved