Date |
Text |
2007-12-20 15:46:00 | REVISION DENIED |
| REFERENCE: FBC-2004 CHAPTER 1 |
| NFPA 99C-99 |
| |
| 1. SUBMITISOMETRIC RISER DIAGRAMS FOR THE VACUUM |
| PIPING AND THE COMPRESSED AIR PIPING. SECTION |
| 106.3.5.1.3. |
| |
| 2. SHT P-3.3 THE VACUUM SYSTEM SHALL COMPLY WITH |
| SECTION 4-5.2 AND ALL SUBSECTIONS. SHOW COMPLIANCE WITH |
| THE FOLLOWING: |
| A. 4-5.2.1.1 SERVICE INLETS SHALL BE EITHER A SHUT |
| OFF VALVE WITH A THREADED FEMALE PIPE CONNECTOR, OR A |
| QUICK-CONNECT FITTING WITH A SINGLE CHECK VALVE. |
| B. 4-5.2.1.2 LIQUID/AIR SEPARATOR (EQUIPMENT SHALL BE |
| OBTAINED FROM AND BE INSTALLED UNDER THE SUPERVISION OF |
| A MANUF. OR SUPPLIER FAMILIAR WITH PROPER PRACTICES FOR |
| ITS CONSTRUCTION AND USE). (SEE FIGS. 4-5.2.1.2 A THRU |
| D. |
| C. 4-5.2.1.3 LIQUIDS FROM A LEVEL VACUUM SYSTEM, PER |
| 4-5.2.2, SHALL BE DIRECTLY CONNECTED TO THE SANITARY |
| DRAINAGE SYSTEM. (SEE FIGURES 4-5.2.1.3(A) THRU(B). |
| (SEE ATTACHED SHEETS). (SHOWN AS INDIRECT CONNECTION ON |
| FIGURE 2 SHT P-3.3). |
| D. 4-5.2.1.5 EXHAUST SHALL BE LOCATED REMOTE FROM ANY |
| DOOR, WINDOW, AIR INTAKE, OR OTHER OPENING IN THE |
| BUILDING ETC. |
| E. 4-5.2.1.6 EXHAUST PROTECT AGAINST ENTRY OF INSECTS |
| ETC. |
| F. 4-5.2.2.1 CLEANOUTS REQUIRED. |
| G. 4-5.2.2.3 CLEANOUTS REQUIRED. |
| H. 4-5.2.2.5 PIPING TO BE SLOPED . |
| |
| 3. SHT P-3.3 THE GAS-POWERED DEVICES LEVEL 3 SHALL |
| COMPLY WITH SECTION 4-5.1.1 AND ALL SUBSECTIONS. SHOW |
| COMPLIANCE WITH THE FOLLOWING: |
| A. 4-5.1.1.3(A)(D)(E)(G)(H) INTAKE SHALL BE FROM THE |
| OUTSIDE WHEN PRACTICAL. |
| B. 4-5.1.3.3(A) THRU (I) |
| |
| 4. SEE ATTACHED SHEETS FOR TYPICAL LEVEL 3 VACUUM AND |
| AND GAS POWERED DEVICES SUPPLY SYSTEMS. |
| |
| 5. A SEPARATE MED-GAS PERMIT IS REQUIRED. |
| CERTIFICATIONS FOR THE QUALIFER, THE BRAZER, & |
| INSTALLER ARE REQUIRED WHEN APPYING FOR THE PERMIT. |
| PICTURE IDENTIFICATION IS REQUIRED ON THE |
| CERTIFICATIONS. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |
| |
| |