Plan Review Notes For Permit 06071722 |
Permit Number |
06071722 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-10-10 15:15:58 | ***DENIED*** | | | | 1) EXIT SIGNS SHALL BE MOUNTED AT DISTANCES NOT TO | | EXCEED 100'. SHT A1.01. | | | | 2) PLEASE CLEARLY IDENTIFY EMERGENCY LIGHTING IN ALL | | COMPONENTS OF MEANS OF EGRESS INCLUDING STAIRS. | | | | 3) 2A-10B,C RATED FIRE EXTINGUISHERS SHALL BE MOUNTED | | NOT TO EXCEED 75' TRAVEL DISTANCE. | | | | 4) SEPARATE SHOP DRAWINGS AND PERMITS ARE REQUIRED FOR | | FIRE SPRINKLER AND FIRE ALARM REMODEL. | | | | 5) CLASSROOMS AND SIMILAR SPACES SHALL MEET | | REQUIREMENTS FOR RESCUE WINDOWS. | | | | 6) PLEASE SHOW ADDRESS ON BUILDING THAT SHALL BE A | | MINIMUM OF 6" IN HEIGHT, 1" WIDTH AND CONTRASTING TO | | THE BACKGROUND. | | | | 7) NEW FIRE DAMPER INSTALLATIONS SHALL BE DROP TESTED | | PRIOR TO FINAL INSPECTION. | | | | 8) DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE | | ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS. | | | | 9) FIRE ALARM SYSTEM TO BE UL CERTIFIED FOR CENTRAL | | STATION SERVICE. | | | | 10) FIRE ALARM PANEL SHALL BE ACCESSIBLE FOR EMERGENCY | | PERSONNEL. SIGNAGE TO BE DISPLAYED ON ELECTRICAL ROOM | | DOOR INDICATING FACP INSIDE. | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | FIRE PLAN REVIEW (561) 805-6722 |
|