Plan Review Notes
Plan Review Notes For Permit 06071722
Permit Number 06071722
Review Stop E
Sequence Number 1
Notes
Date Text
2006-08-14 00:00:00******** UNSAT **********
  
 1) NOTE: PLEASE SUBMIT ALL MANUFACTURES
 SPECS/CUT SHEETS ON THE GEN, ATS AND
 DEPENDING ON PRIME MOVER WHETHER OR NOT
 A SUB BSAE TANK IS BEING USED ETC.
 THIS INFORMATION REQUIRED FOR BOTH.
 FBC106.1.2 , NEC110.3,90.8 ETC
  
 2) NOTE; PLEASE INDICATE THE GEN
 LOCATION ON PLANS.IF IN A FLOOD ZONE
 PLEASE SEE BUIDLING REVIEW COMMENTS AS
 ELEVATION IS REQUIRED A 6" MIN ABOVE
 BFE.
 PLEASE ALSO KNOW A FLOOD ELEVATION
 CERTIFICATE WILL BE REQUIRED BEFORE
 FINAL.
  
 3) NOTE: PLEASE SEE 230.2 AS MORE THAN
 ONE SERVICE IS BEING SHOWN FOR THE ONE
 BUILDING, HOWEVER COULD NOT LOCATE ON
 PLANSHOW THE SECOND SERVICE BEING
 PRPOSED CAN BE GRANTED UNDER SPECIAL
 PERMIISION AT THIS TIME.
  
 4) NOTE: PLEASE CLARIFY ON PLANS WHERE
 M1 AND M2 ARE? CAN NOT VERIFY
 240.24,110.26 ETC.
 106.1.2 FBC.
  
 5) NOTE: PLEASECOMPLETE GROUNDING
 ELECTRODE SYSTEM AS REQUIRED PER 250.50.
  
 6) NOTE: PLEASE SHOW ALL CIRCUITING
 PLANS AND CORRELATE WITH THE SUBMITTED
 PANEL SCHEDULES AND PANEL SCHEDULES TO
 BE SUBMITTED.
 PLEASE SEE 700.12E FOR CIRCUITING OF
 EM/EXT LTS.
  
 7) NOTE: PLEASE CLARIFY WHERE THE
 LIGHTING IS FOR ALL STAIRS . PLANS
 APPEAR TO SHOW SOME LIGHTING INCENTER
 STAIRWAY,HOWEVER NOT FOR OTHERS. PLEASE
 ALSO SEE STAIRS ARE BEING SHOWN ON TIMED
 SCHEDULE, HOWEVER CONTROLS FOR LIGHTING
 OUTSIDE TIME SCHEDULING SHALL BE
 PROVIDED BY A MIN OF TWO
 METHODS,(OCCUPANCY SENSORS ON LTS,
 OCCUPANCY SENSORS IN STAIRS , TIMED DOOR
 CONTACTS ETC.) PLEASE KNOW, ENTERING
 INTO THE EXIT STAIR WAY AND AHAVING THE
 LIGHTING SHUT OFF AND LEAVE IN TOTAL
 DARKNESS IS A LIFE SAFETY ISSUE.
 PLEASE ALSO PROVIDE BATTERY BACK UP
 FIXTURES.
 PLEASE ALSO SEE A MINIMUM OF 10 FT
 CANDLES IS REQUIRED UNDER NORMAL AND CAN
 BE RATED DOWN TO 1FT UNDER EM
 CONDITIONS. PLEASE PROVIDE
 PHOTO-METRICS. (CAN BE TYPICAL)
 PLEASE SEE EXSTING FROM STAIRS ON SOUTH
 SIDE OF BUILDING SHOWS EGRESS INTO A
 HALL WAY WITH NO EXIT DIRECTIONALS.
 PLEASE SEE NFPA-101
 7.8,7.8.1.3,7.9,7.9.2.2 ETC.
 PLEASE SEE FIREREVIEW COMMENTS.
 FBC CHAPTER 13
  
 8) NOTE: COULD NOT LCATE THE ELEVATOR
 MACHINE RM.? PLEASE SEE 620.23,620.24,
 700.16. ETC
 COULD NOT LOCATE THE MIN CIRCUTING FOR
 LTS, RECEPTS , CAB ETC.
 PLEASE ALSO KNOW, A BATTERY BACK UP
 FIXTURE OF SOME SORT WILL BE REQUIRED IN
 THE ELEVATOR EQUIPMENT RM.
 7.8,7.9, 700.16
  
 9) NOTE: PLEASE SEE EQUIPMENT LIST,
 MENTIONS PANELBOARD/CIRCUIT AS FPL,
 HOWEVER PLEASE KNOW EQUIPMENT AS SHOWN
 IS NOT BY FPL FOR MAINS, METER ETC.
 106.1.2 FBC
  
 10) NOTE: PLEASE SEE MISSING CIRCUITING
 ON ROOFTOP PLANS FOR UNITS AND GFI
 RECEPTS FOR ROOFTOP EQUIPMENT.
 230.63,210.8
  
 11) NOTE: PLEASE VERIFY WHERE LOAD
 CALCUALTIONS ARE SHOWN AND ALL
 CONTINUOUS LOADS/LARGEST MOTORS AT
 125%.220.3,220.10,220.11,220.13,215.3,
 230.42 ETC
  
 12) NOTE: PLEASE PLEASE PROVIDE PANEL
 SCHEDULES FOR LLC1, AND LLC2 AND
 CORRELATE WITH THE CIRCUITING PLANS.
 FBC 106.1.2
  
 13) NOTE: PLEASE PLACE ALL ROOM AND AREA DESIGNATIONS
 ON PLANS.
 UNABLE TO VERIFY SOME OF THESE ROOMS AT
 THIS TIME.
  
 14) NOTE: PLEASE SEE PLANS MENTIONS "IT"
 ROOM ON SECOND FLR. PLEASE SEE NFPA-75
 AND NFPA-70(NEC) 645 FOR REQUIREMENTS.
  
 15) NOTE: PLEASE SEE 620.51 FOR
 DISCONNECTING OF ELEVATOR EQUIPMENT. AS
 ROOM IS NOT VERIFIED AT THIS TIME, NOT
 SURE WHERE THIS DISCONNECTING MEANS IS?
  
 16) NOTE: PELASE SEE 13-415.2.ABC.1,
 TABLES 415.2.C.1, 415.2.B.1
  
 17) NOTE: PLEASE SEE "EQUIPMENT
 CO-ORDINATION SCHEDULE", PLEASE SEE
 MAINS DISCONNECTS WHICH ARE INDEED MAINS
 AND PLEASE ALSO SEE MAINS FOR EACH FLR
 ALSO BEING LABELED AS "MAINS" 1 AND 2.
 PLEASE ADJUSTED IDENTIFICATION
 ACCORDINLGY.
 230.2E
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved