Date |
Text |
2006-08-14 00:00:00 | ******** UNSAT ********** |
| |
| 1) NOTE: PLEASE SUBMIT ALL MANUFACTURES |
| SPECS/CUT SHEETS ON THE GEN, ATS AND |
| DEPENDING ON PRIME MOVER WHETHER OR NOT |
| A SUB BSAE TANK IS BEING USED ETC. |
| THIS INFORMATION REQUIRED FOR BOTH. |
| FBC106.1.2 , NEC110.3,90.8 ETC |
| |
| 2) NOTE; PLEASE INDICATE THE GEN |
| LOCATION ON PLANS.IF IN A FLOOD ZONE |
| PLEASE SEE BUIDLING REVIEW COMMENTS AS |
| ELEVATION IS REQUIRED A 6" MIN ABOVE |
| BFE. |
| PLEASE ALSO KNOW A FLOOD ELEVATION |
| CERTIFICATE WILL BE REQUIRED BEFORE |
| FINAL. |
| |
| 3) NOTE: PLEASE SEE 230.2 AS MORE THAN |
| ONE SERVICE IS BEING SHOWN FOR THE ONE |
| BUILDING, HOWEVER COULD NOT LOCATE ON |
| PLANSHOW THE SECOND SERVICE BEING |
| PRPOSED CAN BE GRANTED UNDER SPECIAL |
| PERMIISION AT THIS TIME. |
| |
| 4) NOTE: PLEASE CLARIFY ON PLANS WHERE |
| M1 AND M2 ARE? CAN NOT VERIFY |
| 240.24,110.26 ETC. |
| 106.1.2 FBC. |
| |
| 5) NOTE: PLEASECOMPLETE GROUNDING |
| ELECTRODE SYSTEM AS REQUIRED PER 250.50. |
| |
| 6) NOTE: PLEASE SHOW ALL CIRCUITING |
| PLANS AND CORRELATE WITH THE SUBMITTED |
| PANEL SCHEDULES AND PANEL SCHEDULES TO |
| BE SUBMITTED. |
| PLEASE SEE 700.12E FOR CIRCUITING OF |
| EM/EXT LTS. |
| |
| 7) NOTE: PLEASE CLARIFY WHERE THE |
| LIGHTING IS FOR ALL STAIRS . PLANS |
| APPEAR TO SHOW SOME LIGHTING INCENTER |
| STAIRWAY,HOWEVER NOT FOR OTHERS. PLEASE |
| ALSO SEE STAIRS ARE BEING SHOWN ON TIMED |
| SCHEDULE, HOWEVER CONTROLS FOR LIGHTING |
| OUTSIDE TIME SCHEDULING SHALL BE |
| PROVIDED BY A MIN OF TWO |
| METHODS,(OCCUPANCY SENSORS ON LTS, |
| OCCUPANCY SENSORS IN STAIRS , TIMED DOOR |
| CONTACTS ETC.) PLEASE KNOW, ENTERING |
| INTO THE EXIT STAIR WAY AND AHAVING THE |
| LIGHTING SHUT OFF AND LEAVE IN TOTAL |
| DARKNESS IS A LIFE SAFETY ISSUE. |
| PLEASE ALSO PROVIDE BATTERY BACK UP |
| FIXTURES. |
| PLEASE ALSO SEE A MINIMUM OF 10 FT |
| CANDLES IS REQUIRED UNDER NORMAL AND CAN |
| BE RATED DOWN TO 1FT UNDER EM |
| CONDITIONS. PLEASE PROVIDE |
| PHOTO-METRICS. (CAN BE TYPICAL) |
| PLEASE SEE EXSTING FROM STAIRS ON SOUTH |
| SIDE OF BUILDING SHOWS EGRESS INTO A |
| HALL WAY WITH NO EXIT DIRECTIONALS. |
| PLEASE SEE NFPA-101 |
| 7.8,7.8.1.3,7.9,7.9.2.2 ETC. |
| PLEASE SEE FIREREVIEW COMMENTS. |
| FBC CHAPTER 13 |
| |
| 8) NOTE: COULD NOT LCATE THE ELEVATOR |
| MACHINE RM.? PLEASE SEE 620.23,620.24, |
| 700.16. ETC |
| COULD NOT LOCATE THE MIN CIRCUTING FOR |
| LTS, RECEPTS , CAB ETC. |
| PLEASE ALSO KNOW, A BATTERY BACK UP |
| FIXTURE OF SOME SORT WILL BE REQUIRED IN |
| THE ELEVATOR EQUIPMENT RM. |
| 7.8,7.9, 700.16 |
| |
| 9) NOTE: PLEASE SEE EQUIPMENT LIST, |
| MENTIONS PANELBOARD/CIRCUIT AS FPL, |
| HOWEVER PLEASE KNOW EQUIPMENT AS SHOWN |
| IS NOT BY FPL FOR MAINS, METER ETC. |
| 106.1.2 FBC |
| |
| 10) NOTE: PLEASE SEE MISSING CIRCUITING |
| ON ROOFTOP PLANS FOR UNITS AND GFI |
| RECEPTS FOR ROOFTOP EQUIPMENT. |
| 230.63,210.8 |
| |
| 11) NOTE: PLEASE VERIFY WHERE LOAD |
| CALCUALTIONS ARE SHOWN AND ALL |
| CONTINUOUS LOADS/LARGEST MOTORS AT |
| 125%.220.3,220.10,220.11,220.13,215.3, |
| 230.42 ETC |
| |
| 12) NOTE: PLEASE PLEASE PROVIDE PANEL |
| SCHEDULES FOR LLC1, AND LLC2 AND |
| CORRELATE WITH THE CIRCUITING PLANS. |
| FBC 106.1.2 |
| |
| 13) NOTE: PLEASE PLACE ALL ROOM AND AREA DESIGNATIONS |
| ON PLANS. |
| UNABLE TO VERIFY SOME OF THESE ROOMS AT |
| THIS TIME. |
| |
| 14) NOTE: PLEASE SEE PLANS MENTIONS "IT" |
| ROOM ON SECOND FLR. PLEASE SEE NFPA-75 |
| AND NFPA-70(NEC) 645 FOR REQUIREMENTS. |
| |
| 15) NOTE: PLEASE SEE 620.51 FOR |
| DISCONNECTING OF ELEVATOR EQUIPMENT. AS |
| ROOM IS NOT VERIFIED AT THIS TIME, NOT |
| SURE WHERE THIS DISCONNECTING MEANS IS? |
| |
| 16) NOTE: PELASE SEE 13-415.2.ABC.1, |
| TABLES 415.2.C.1, 415.2.B.1 |
| |
| 17) NOTE: PLEASE SEE "EQUIPMENT |
| CO-ORDINATION SCHEDULE", PLEASE SEE |
| MAINS DISCONNECTS WHICH ARE INDEED MAINS |
| AND PLEASE ALSO SEE MAINS FOR EACH FLR |
| ALSO BEING LABELED AS "MAINS" 1 AND 2. |
| PLEASE ADJUSTED IDENTIFICATION |
| ACCORDINLGY. |
| 230.2E |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CONSTUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
| |
| |