Plan Review Notes
Plan Review Notes For Permit 06071722
Permit Number 06071722
Review Stop B
Sequence Number 1
Notes
Date Text
2006-08-25 00:00:00 
  
 DENIED
  
 1) PER ARTICLE 13 OF THE UNIFIED LAND
 DEVELOPMENT CODE, IMPACT FEES ARE
 PAYABLE ON CHANGE OF USE. BEFORE A
 PERMIT TO CONSTRUCT, IS ISSUED IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE ACTUAL PERMIT SETS OF PLANS MUST BE
 STAMPED BY THAT OFFICE, AND A COPY OF
 THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION.PLEASE CALL (561) 233-5025
 FOR MORE INFORMATION
  
 2) PROVIDE DETAILS ON THE OCCUPANCY OF
 BUILDING #1 AS IT EXITS INTO THE SAME
 ENCLOSED CORRIDOR BETWEEN THE TWO
 BUILDINGS. VERIFY THAT THE EXITS WILL
 MEET THE REQUIRED EXIT DISCHARGE
 CAPACITY FOR BOTH BUILDINGS
  
 3) PROVIDE EXISTING FLOOR PLAN AND DEMO
 PLAN WITH THE CONSTRUCTION SET TO BETTER
 UNDERSTAND THE MODIFICATIONS, ALSO
 PROVIDE THE PREVIOUS OCCUPANCY TYPE
  
 4) THE EXIT PASSAGEWAY BETWEEN BUILDINGS
 1 AND 2 HAS 2 EXITS DOES THE WEST EXIT
 ENTER INTO AN EGRESS COURT THAT PROVIDE
 ACCESS TO THE PUBLIC WAY AS DEFINED IN
 CHAPTER 10, OR IS IT A FENCED AREA,
 PLEASE CLARIFY
  
 5) PROVIDE DETAILS OF WALKWAY TO
 EXISTING BUILDING 3 IS IT ALSO ENCLOSED
 OR OPEN
  
 6) PROVIDE DETAILS FOR ALL STRUCTURAL
 MODIFICATIONS TO THE EXTERIOR WALLS
 (INFILL OF ELEVATORS EXTERIOR DOOR,
 MODIFICATIONS TO ACCEPT NEW DOORS OR
 WINDOWS, ETC.)
  
 7) THE PERMIT APPLICATION SHALL INCLUDE
 TWO COPIES OF EACH PRODUCT APPROVAL THAT
 IS RELEVANT PER 9B-72. THESE SHOULD
 INCLUDE THE FLORIDA STATE APPROVAL COVER
 PAGES, AND THE PRODUCT NOA THAT LISTS
 THE SYSTEM COMPONENTS/ FASTENER LIST
 PAGES, THE PAGES WITH THE CHOSEN
 ASSEMBLY/ SYSTEM TO BE USED AND THE
 GENERAL LIMITATIONS PAGE. ALL CAN BE
 FOUND ON WWW.FLORIDABUILDING.ORG
 (WILL BE REQUIRED FOR ROOFING, A/C OR
 OTHER EQUIPMENT STANDS AND ALL EXTERIOR
 DOORS, WINDOWS, STOREFRONTS, ROLL UP
 DOORS, ETC.)
  
 8) THOSE PRODUCTS WHICH ARE REGULATED BY
 DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
 9) PANIC HARDWARE SHALL COMPLY WITH
 THE REQUREMENTS OF 1027.2.1 FBC
  
 10) DOOR 106C SHALL MEET THE
 REQUIREMENTS OF 1027.3 AND 1005.2 FBC
  
 11) FLOORS AND WALLS OF TOILET ROOMS
 SHALL COMPLY WITH 1210 FBC
  
 12) TOILET ROOMS, FIXTURES AND
 ACCESSORIES SHALL COMPLY WITH CHAPTER 11
 OF THE 2004 FBC (A6.01 LISTS 1997 ED.)
  
 13) PROPOSED GENERATOR WILL REQUIRE A
 SOIL REPORT,ENGINEERED EQUIPMENT BASE,
 SURVEY THAT PROPOSED BASE IS 6" ABOVE
 THE BASE FLOOD ELEVATION FOR LOCATION.
 ALSO BE AWARE THAT ALL SUBS ARE
 SIGNED ON TO GENERATOR PERMIT AT TIME OF
 APPLICATION (GAS, ELECT, PLUMBING, ETC)
  
 14) GENERAL FINISH NOTES ON A2.01 SHOWS
 GROUP AS A3, AND THE EXIT ACCESS AS
 CLASS 'C' THIS DOES NOT CORRESPOND WITH
 THE TABLE 803.5 FBC PLEASE CLARIFY
  
 15) SEE PLUMBING NOTES ON ACCESSABLE
 SINKS IN THE BREAK ROOM AND STAFF LOUNGE
  
 16) PROVIDE MIN MANUVERING DISTANCE OF
 18" AT DOORS 121A, 218A AND 225A PER
 11-4.13.6 AND FIG.25(A). ALSO IF THE MIN
 DISTANCE PROVIDED AT DOOR 202A IS 12" ON
 THE PUSH SIDE THIS DOOR SHALL BE
 PROVIDED WITH A CLOSER AND LATCH PER
 NOTE: FIG. 25(A)
  
 17) GENERAL DOOR NOTES ON A2.01 SHALL
 PROVIDE HARDWARE THAT MEETS THE
 REQUIREMENTS OF 11-4.13.8 FBC FOR
 ACCESSABLE HARDWARE
  
 18) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  