2006-08-25 00:00:00 | |
| |
| DENIED |
| |
| 1) PER ARTICLE 13 OF THE UNIFIED LAND |
| DEVELOPMENT CODE, IMPACT FEES ARE |
| PAYABLE ON CHANGE OF USE. BEFORE A |
| PERMIT TO CONSTRUCT, IS ISSUED IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. |
| THE ACTUAL PERMIT SETS OF PLANS MUST BE |
| STAMPED BY THAT OFFICE, AND A COPY OF |
| THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION.PLEASE CALL (561) 233-5025 |
| FOR MORE INFORMATION |
| |
| 2) PROVIDE DETAILS ON THE OCCUPANCY OF |
| BUILDING #1 AS IT EXITS INTO THE SAME |
| ENCLOSED CORRIDOR BETWEEN THE TWO |
| BUILDINGS. VERIFY THAT THE EXITS WILL |
| MEET THE REQUIRED EXIT DISCHARGE |
| CAPACITY FOR BOTH BUILDINGS |
| |
| 3) PROVIDE EXISTING FLOOR PLAN AND DEMO |
| PLAN WITH THE CONSTRUCTION SET TO BETTER |
| UNDERSTAND THE MODIFICATIONS, ALSO |
| PROVIDE THE PREVIOUS OCCUPANCY TYPE |
| |
| 4) THE EXIT PASSAGEWAY BETWEEN BUILDINGS |
| 1 AND 2 HAS 2 EXITS DOES THE WEST EXIT |
| ENTER INTO AN EGRESS COURT THAT PROVIDE |
| ACCESS TO THE PUBLIC WAY AS DEFINED IN |
| CHAPTER 10, OR IS IT A FENCED AREA, |
| PLEASE CLARIFY |
| |
| 5) PROVIDE DETAILS OF WALKWAY TO |
| EXISTING BUILDING 3 IS IT ALSO ENCLOSED |
| OR OPEN |
| |
| 6) PROVIDE DETAILS FOR ALL STRUCTURAL |
| MODIFICATIONS TO THE EXTERIOR WALLS |
| (INFILL OF ELEVATORS EXTERIOR DOOR, |
| MODIFICATIONS TO ACCEPT NEW DOORS OR |
| WINDOWS, ETC.) |
| |
| 7) THE PERMIT APPLICATION SHALL INCLUDE |
| TWO COPIES OF EACH PRODUCT APPROVAL THAT |
| IS RELEVANT PER 9B-72. THESE SHOULD |
| INCLUDE THE FLORIDA STATE APPROVAL COVER |
| PAGES, AND THE PRODUCT NOA THAT LISTS |
| THE SYSTEM COMPONENTS/ FASTENER LIST |
| PAGES, THE PAGES WITH THE CHOSEN |
| ASSEMBLY/ SYSTEM TO BE USED AND THE |
| GENERAL LIMITATIONS PAGE. ALL CAN BE |
| FOUND ON WWW.FLORIDABUILDING.ORG |
| (WILL BE REQUIRED FOR ROOFING, A/C OR |
| OTHER EQUIPMENT STANDS AND ALL EXTERIOR |
| DOORS, WINDOWS, STOREFRONTS, ROLL UP |
| DOORS, ETC.) |
| |
| 8) THOSE PRODUCTS WHICH ARE REGULATED BY |
| DCA RULE 9B-72 SHALL BE REVIEWED AND |
| APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL PER 106.3.3 FBC* |
| |
| 9) PANIC HARDWARE SHALL COMPLY WITH |
| THE REQUREMENTS OF 1027.2.1 FBC |
| |
| 10) DOOR 106C SHALL MEET THE |
| REQUIREMENTS OF 1027.3 AND 1005.2 FBC |
| |
| 11) FLOORS AND WALLS OF TOILET ROOMS |
| SHALL COMPLY WITH 1210 FBC |
| |
| 12) TOILET ROOMS, FIXTURES AND |
| ACCESSORIES SHALL COMPLY WITH CHAPTER 11 |
| OF THE 2004 FBC (A6.01 LISTS 1997 ED.) |
| |
| 13) PROPOSED GENERATOR WILL REQUIRE A |
| SOIL REPORT,ENGINEERED EQUIPMENT BASE, |
| SURVEY THAT PROPOSED BASE IS 6" ABOVE |
| THE BASE FLOOD ELEVATION FOR LOCATION. |
| ALSO BE AWARE THAT ALL SUBS ARE |
| SIGNED ON TO GENERATOR PERMIT AT TIME OF |
| APPLICATION (GAS, ELECT, PLUMBING, ETC) |
| |
| 14) GENERAL FINISH NOTES ON A2.01 SHOWS |
| GROUP AS A3, AND THE EXIT ACCESS AS |
| CLASS 'C' THIS DOES NOT CORRESPOND WITH |
| THE TABLE 803.5 FBC PLEASE CLARIFY |
| |
| 15) SEE PLUMBING NOTES ON ACCESSABLE |
| SINKS IN THE BREAK ROOM AND STAFF LOUNGE |
| |
| 16) PROVIDE MIN MANUVERING DISTANCE OF |
| 18" AT DOORS 121A, 218A AND 225A PER |
| 11-4.13.6 AND FIG.25(A). ALSO IF THE MIN |
| DISTANCE PROVIDED AT DOOR 202A IS 12" ON |
| THE PUSH SIDE THIS DOOR SHALL BE |
| PROVIDED WITH A CLOSER AND LATCH PER |
| NOTE: FIG. 25(A) |
| |
| 17) GENERAL DOOR NOTES ON A2.01 SHALL |
| PROVIDE HARDWARE THAT MEETS THE |
| REQUIREMENTS OF 11-4.13.8 FBC FOR |
| ACCESSABLE HARDWARE |
| |
| 18) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT IS REQUIRED PRIOR TO |
| A PERMIT BEING ISSUED |
| |