Plan Review Notes For Permit 06071689
Permit Number 06071689
Review Stop E
Sequence Number 1
Notes
Date Text
2006-07-28 00:00:00******* UNSAT *********
  
 1) NOTE: PLEASE COMPLETE RISER WITH ALL
 BRNACH CIRCUIT CONDUCTOR SIZES AS
 REQUIRED. PLEASE LIST THE OCP FOR EACH
 UNIT BEING FED.
 240.4,310.16, 408.4
 FBC 106.1.2
  
 2) NOTE: PLEASE 220.31B FOR MIN LOAD
 CALCULATIONS TO BE DONE.
 PLEASE SEE NO SM APPL CIRCUITS SHOWN
 ETC.220.16
 PLEASE SEE 220.18 FOR MIN KW FOR DRYER.
  
 3) NOTE: PLEASE SEE MISSING NEW OR
 EXISTING GFI FOR CU.
 210.63
  
 4) NOTE: PLEASE SEE MISSING THE PRINTED
 NAME AND SIGNATURE OF THE PRESON
 RESPONSIBLE FOR SAID PLANS/DESIGN.
 FBC106.1.2 ADMIN SECT.
  
 5) NOTE: PLEASE SUBMIT TWO SETS, ONE
 WILL COME BACK FOR INSPECTION AND ONE
 WILL REMAIN ONFILE.
 106.1
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  