Plan Review Notes For Permit 06071649 |
Permit Number |
06071649 |
|
Review Stop |
E |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2007-05-02 12:46:48 | NONCOMPLIANT | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | COMPLIANCE AND RESUBMIT FOR REVIEW | | | | 1} THE RISER DIAGRAM IS INCOMPLETE, IT DOES NOT SHOW | | THE METER LOCATION IN THE SERVICE. PLEASE LOCATE ALL | | SERVICE EQUIPMENT ON THE PLAN, METER ENCLOSURE, | | DISCONNECTS AND PANELS, SO THAT COMPLIANCE WITH | | ARTICLES 225 AND 230 CAN BE REVIEWED. DO THIS ON A SITE | | PLAN, NOT ON THE SURVEY, 106.1.3 FBC. SEE NOTE #2 AND | | 3, PREVIOUS REVIEW. THE GENERATOR AND A DISCONNECT ARE | | ALL THAT'S SHOWN. | | | | 2} 702.5 CAPACITY AND RATING. AN OPTIONAL STANDBY | | SYSTEM SHALL HAVE ADEQUATE CAPACITY AND RATING FOR THE | | SUPPLY OF ALL EQUIPMENT INTENDED TO BE OPERATED AT ONE | | TIME.THE LOAD CALCULATION THAT WAS SUBMITTED IS | | INCORRECT, SEE 220.31(B) IF USING OPTIONAL. THE HEAT | | LOAD IS AT 100%. | | | | 3} THE GENERATOR DOES NOT MEET THE MANUFACTURERS | | RECOMENDED SETBACKS, SEE PAGE 9 OWNERS MANUAL. | | | | 4} THE INFORMATION REGARDING THE TRANSFER SWITCH IS | | INSUFFICIENT. INDICATE THAT THE "PANEL SCHEDULE" | | SUBMITTED WITH 16 CIRCUITS IS IN FACT THE CIRCUITS IN | | THE TRANSFER SWITCH OR IN A GENERATOR PANEL. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 |
|