2007-05-02 12:46:48NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW
  
 1} THE RISER DIAGRAM IS INCOMPLETE, IT DOES NOT SHOW
 THE METER LOCATION IN THE SERVICE. PLEASE LOCATE ALL
 SERVICE EQUIPMENT ON THE PLAN, METER ENCLOSURE,
 DISCONNECTS AND PANELS, SO THAT COMPLIANCE WITH
 ARTICLES 225 AND 230 CAN BE REVIEWED. DO THIS ON A SITE
 PLAN, NOT ON THE SURVEY, 106.1.3 FBC. SEE NOTE #2 AND
 3, PREVIOUS REVIEW. THE GENERATOR AND A DISCONNECT ARE
 ALL THAT'S SHOWN.
  
 2} 702.5 CAPACITY AND RATING. AN OPTIONAL STANDBY
 SYSTEM SHALL HAVE ADEQUATE CAPACITY AND RATING FOR THE
 SUPPLY OF ALL EQUIPMENT INTENDED TO BE OPERATED AT ONE
 TIME.THE LOAD CALCULATION THAT WAS SUBMITTED IS
 INCORRECT, SEE 220.31(B) IF USING OPTIONAL. THE HEAT
 LOAD IS AT 100%.
  
 3} THE GENERATOR DOES NOT MEET THE MANUFACTURERS
 RECOMENDED SETBACKS, SEE PAGE 9 OWNERS MANUAL.
  
 4} THE INFORMATION REGARDING THE TRANSFER SWITCH IS
 INSUFFICIENT. INDICATE THAT THE "PANEL SCHEDULE"
 SUBMITTED WITH 16 CIRCUITS IS IN FACT THE CIRCUITS IN
 THE TRANSFER SWITCH OR IN A GENERATOR PANEL.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  