Plan Review Notes
Plan Review Notes For Permit 06071596
Permit Number 06071596
Review Stop B
Sequence Number 1
Notes
Date Text
2006-08-05 00:00:00 
  
 DENIED
  
 1) ACCORDIAN SHUTTERS ARE INSTALLED WITH
 SPANS VERTICAL PLEASE CHANGE ORIENTATION
 AND SHUTTER SPANS SEE PAGE 4 OF SHUTTER
 DRAWINGS. NOTE THAT THE SHTTER SPAN
 (WITH 3" E.D.) IS GENERALLY 2" BIGGER
 THAN THE OPENING ON WINDOWS AND APPROX
 THE SAME AS THE OPENING FOR DOORS
  
 2) BECAUSE ALL ATTACHMENT TYPES ARE
 CHOSEN ASSUMPTIONS ARE MADE THAT SHUTTER
 13, 15 AND 16 ARE DOORS AND THAT A FLOOR
 MOUNTED SILL WILL BE USED. PLEASE SEE
 THAT AT 11 AND 12 FT SPANS THE ANCHOR
 SPACING IS LESS THAN THE STATED SPACING
 ON THE INSTALLATION SCEDULE
  
 3) PROVIDE 2 COPIES OF ALL SUBMITTALS
 (INCLUDING INSTALLATION SCHEDULE)
  
 ADRIAN MORSE
 BLDG PLAN REVIEW
 561-805-6716
  
  
  
  