Plan Review Notes
Plan Review Notes For Permit 06071591
Permit Number 06071591
Review Stop B
Sequence Number 1
Notes
Date Text
2006-08-05 00:00:00 
  
 DENIED
  
 1) ACCORDIAN SHUTTERS ARE INSTALLED WITH
 SPANS VERTICAL PLEASE CHANGE ORIENTATION
 AND SHUTTER SPANS SEE PAGE 4 OF SHUTTER
 DRAWINGS. NOTE THAT THE SHTTER SPAN
 (WITH 3" E.D.) IS GENERALLY 2" BIGGER
 THAN THE OPENING ON WINDOWS AND APPROX
 THE SAME AS THE OPENING FOR DOORS
 (SEE MAX SHUTTER SPAN ON PAGE 9, 534" =
 44.5 FT AND MAX SPAN IS 11 FT)
  
 2) PROVIDE 2 COPIES OF ALL SUBMITTALS
 (INCLUDING INSTALLATION SCHEDULE)
  
 3) SIGNED AND SEALED ENGINEERING IS
 REQUIRED FOR BUILDINGS OVER 60 FT IN
 HEIGHT PER 1609.1.1 FBC
  
 4) SEE ATTACHED PROPERTY APPRAISERS
 SHEET, THE OWNER ONOUR SYSTEM MATCHES
 THIS. IF THE OWNER IS INDEED AS STATED
 ON THE APPLICATION PROOF OF OWNERSHIP IS
 REQUIRED (COPY OF DEED, ETC)
  
 ADRIAN MORSE
 BLDG PLAN REVIEW