2007-01-11 15:26:29 | *** REDLINED PLANS*** | | | | | | 1) RISER STILL SHOWS OCP FOR AHU AT 35A, WHERE 424.4B | | REQUIRES 125% MIN. PLEASE SEE PANEL SCHEDULE SHOWS 50A | | BREAKER. | | 2) PLEASE ALSO SEE CODE REQUIRES SMOKE ALARMS.NFPA-72 | | 11.5.1.1, 11.8.3 |
|