2007-01-11 15:26:29*** REDLINED PLANS***
  
  
 1) RISER STILL SHOWS OCP FOR AHU AT 35A, WHERE 424.4B
 REQUIRES 125% MIN. PLEASE SEE PANEL SCHEDULE SHOWS 50A
 BREAKER.
 2) PLEASE ALSO SEE CODE REQUIRES SMOKE ALARMS.NFPA-72
 11.5.1.1, 11.8.3