Plan Review Notes
Plan Review Notes For Permit 06071495
Permit Number 06071495
Review Stop E
Sequence Number 2
Notes
Date Text
2006-10-13 19:57:17******** UNSAT2ANDREVIEW *********
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW STILL
 NEED TO BE ADDRESSED ALONG WITH NEW NOTES DUE TO
 CHANGES MADE TO PLANS FROM PREVIOUS REVIEW.
 PLEASE SEE NOTES BELOW ARE TAKEN DIRECTLY FROM PREVIOUS
 REVIEW WITH NEW ADDED TO BOTTOM OFREVIEW.
  
 1) NOTE:OK.
  
 2) NOTE:NO, PLEASE SEE ALL SEALS ON ALL SHEETS ON
 BOTH SETS SHALL BE CLEAR AND VISIBLE AS REQUIRED UNDER
 FLORIDA ADMINISTRATIVE CODE AND FLORIDA STATUES AS
 PREVIOUSLY NOTED. THIS IS REQUIRED AS THE SEALS ARE NOT
 CLEAR. PLEASE OBTAIN NEW SEAL IF NEEDED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE BE SURE TITLE BLOCKS
 CONTAIN ALL INFORMATION AS REQUIRED BY
 FAC 61G1-16.004. PLEASE SEE MISSING THE
 PRINTED NAME AND LICENSE NUMBER OF SAID
 ARCHITECT.
 PLEASE ALSO BE SURE ALL SEALS ARE
 RAISED, CLEAR AND VISABLE WITH ALL
 INFORMATION ON SAID SEALS. PLEASE SEE
 THAT MANY OF THE SEALS ARE NOT CLEAR.
 FS 481.221
  
 3)NOTE: NO, NOTHING SUBMITTED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9. FBC 106.1.2
  
 4) NOTE: NO, PLEASE SEE AS NOTED ON PREVIOUS REVIEW,
 424.3B. MIN OCP REQUIRED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE CORRELATE AND COMPLETE
 INFORMATION FOR AHU KW RATING. PLEASE
 SEE LOAD CALCS INDICATE 100% = 6500VA ,
 YET THE OCP AND CONDUCTOR SIZES LEND TO
 THIS AS A 10KW HEAT STRIP? PLEASE
 CORRELATE AS THE MECH SHEETS SHOW
 ANOTHER SIZE. PLEASE ADJUST ALL ONCE THE
 KW RATING IS SET.
 424.3B.,220,310.16,240.4 ETC
  
 5) NOTE:NO, PLEASE SEE NOTE STILL MENTIONS TO WIRE
 INTO KITCHEN LIGHTING CIRCUIT ALTHOUGH NEW NOTE WAS
 ADDED.
 THIS COULD HAVE BEEN REDLINED, HOWEVER PLANS ARE COMING
 BACK FOR CORRECTIONS AT THIS TIME.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE IDICATE ALL CIRCUITS ON
 PANELS WHICH ARE REQUIRED TO CONTAIN ARC
 FAULT PROTECTION. PLEASE SEE NOTES FOR
 ARC FAULT MENTIONS ONLY RECEPTS, LTS AND
 FANS. (NO FANS SHOWN ) ALTHOUGH
 PROTECTION OF SD'S IS ALSO REQUIRED.
 PELASE SEE NOTE ABOVE MENTIONS AND PLANS
 SHOWS SD'S CIRCUITED TO KITCHEN AND BATH
 RM LIGHTING, WHICH IS OK, HOWEVER THIS
 CIRCUIT WOULD ALSO REQUIRED ARC FAULT
 PROTECTION.
 210.12B, 408.4
  
 6) NOTE: OK.
  
 7) NOTE: OK.
  
 8) NOTE: OK, HOWEVER SEE NEW NOTE.
  
 ** PREVIOUS NEWNOTE **
 PLEASE SEE MISSING GFI RECEPT
 FOR CU. 210.63,210.8A2
  
 9) NOTE: OK.
  
 10) NOTE: OK.
  
 11) NOTE: OK.
  
 ** NEW NOTES **
  
 12) NOTE: PLEASE SEE NOTE" ** IMPORTANT** "NOTE BELOW
 WHICH WAS AT THE END OF THE PREVIOUS REVIEW NOTES WHICH
 ASKED FOR ALL OLD SHEETS TO BE REMOVED. PLEASE SEE THIS
 WAS NOT DONE. PLEASE DO SO BEFORE RESUBMITTING PLANS
 FOR NEXT REVIEW AS THIS WILL HELP IN NOT DELAYING
 PROJECT.
 ** NOTED PREVIOUS REVIEW**
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE, PLANS WILL BE
 PICKED UP FOR CORRECTIONS. PLEASE KNOW,
 BEFORE RESUBMITTING PLANS, ALL
 OLD/VOIDED SHEETS MUST BE COMPLETELY
 REMOVED FROM SETS AND ONLY NEW REVISED
 SHEETS SHOULD BE INSERTED INTO COMPLETE
 SETS FOR REVIEW AND STAMPING. ONLY ONE
 COPY OF THE OLD/VOIDED SHEETS SHOULD BE
 SUBMITTED SEAPARATELY FOR REFERENCE.
  
 13) NOTE: PLEASE SEE THE NEW GFI RECEPT REQUIRED FOR
 THE OUTSIDE CU WHICH WAS ADDED TO THESE PLANS IS BEING
 SHOWN CIRCUITED TO THE #1, WHICH ALSO FEEDS THE AHU.
 MAY NOT BE TAPPED FROM THIS 220VA CIRCUIT .
 310.16,240.4., 240.21 ETC
  
 14) NOTE: PLEASE SEE THE RECORDED NOTICE OF COMMENCMENT
 SUBMITTED IS NO LONGER VALID AS IS HAS EXCEEDING THE
 90DAYS SINCE BEING RECORD AND WORK HAS NOT COMMENCED.
 PLEASE SEE FS 713.13(2). PLEASE KNOW, THE RECORDED NOC
 IS ONLY REQUIRED AFTER PERMIT IS ISSUED AND BEFORE
 PICKING UP PERMIT.
  
 15) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 DESIGN PROFESSIONALS AND REPEAT COMMENTS FOR CODE
 COMPLIANCE. THIS IS ONLY A NOTICE GIVEN AT THIS TIME.
 PLEASE KNOW ONE SET OF ELECTRICAL SHEETS FROM EACH
 SUBMITTED SET IS BEING RETAINED BY THIS OFFICE.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  