Date |
Text |
2006-10-13 19:57:17 | ******** UNSAT2ANDREVIEW ********* |
| |
| ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW STILL |
| NEED TO BE ADDRESSED ALONG WITH NEW NOTES DUE TO |
| CHANGES MADE TO PLANS FROM PREVIOUS REVIEW. |
| PLEASE SEE NOTES BELOW ARE TAKEN DIRECTLY FROM PREVIOUS |
| REVIEW WITH NEW ADDED TO BOTTOM OFREVIEW. |
| |
| 1) NOTE:OK. |
| |
| 2) NOTE:NO, PLEASE SEE ALL SEALS ON ALL SHEETS ON |
| BOTH SETS SHALL BE CLEAR AND VISIBLE AS REQUIRED UNDER |
| FLORIDA ADMINISTRATIVE CODE AND FLORIDA STATUES AS |
| PREVIOUSLY NOTED. THIS IS REQUIRED AS THE SEALS ARE NOT |
| CLEAR. PLEASE OBTAIN NEW SEAL IF NEEDED. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE BE SURE TITLE BLOCKS |
| CONTAIN ALL INFORMATION AS REQUIRED BY |
| FAC 61G1-16.004. PLEASE SEE MISSING THE |
| PRINTED NAME AND LICENSE NUMBER OF SAID |
| ARCHITECT. |
| PLEASE ALSO BE SURE ALL SEALS ARE |
| RAISED, CLEAR AND VISABLE WITH ALL |
| INFORMATION ON SAID SEALS. PLEASE SEE |
| THAT MANY OF THE SEALS ARE NOT CLEAR. |
| FS 481.221 |
| |
| 3)NOTE: NO, NOTHING SUBMITTED. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SUBMIT AIC RATINGS FOR |
| ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| RATED FOR THE AVAILABLE FAULT CURRENT. |
| PER 110.9. FBC 106.1.2 |
| |
| 4) NOTE: NO, PLEASE SEE AS NOTED ON PREVIOUS REVIEW, |
| 424.3B. MIN OCP REQUIRED. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE CORRELATE AND COMPLETE |
| INFORMATION FOR AHU KW RATING. PLEASE |
| SEE LOAD CALCS INDICATE 100% = 6500VA , |
| YET THE OCP AND CONDUCTOR SIZES LEND TO |
| THIS AS A 10KW HEAT STRIP? PLEASE |
| CORRELATE AS THE MECH SHEETS SHOW |
| ANOTHER SIZE. PLEASE ADJUST ALL ONCE THE |
| KW RATING IS SET. |
| 424.3B.,220,310.16,240.4 ETC |
| |
| 5) NOTE:NO, PLEASE SEE NOTE STILL MENTIONS TO WIRE |
| INTO KITCHEN LIGHTING CIRCUIT ALTHOUGH NEW NOTE WAS |
| ADDED. |
| THIS COULD HAVE BEEN REDLINED, HOWEVER PLANS ARE COMING |
| BACK FOR CORRECTIONS AT THIS TIME. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE IDICATE ALL CIRCUITS ON |
| PANELS WHICH ARE REQUIRED TO CONTAIN ARC |
| FAULT PROTECTION. PLEASE SEE NOTES FOR |
| ARC FAULT MENTIONS ONLY RECEPTS, LTS AND |
| FANS. (NO FANS SHOWN ) ALTHOUGH |
| PROTECTION OF SD'S IS ALSO REQUIRED. |
| PELASE SEE NOTE ABOVE MENTIONS AND PLANS |
| SHOWS SD'S CIRCUITED TO KITCHEN AND BATH |
| RM LIGHTING, WHICH IS OK, HOWEVER THIS |
| CIRCUIT WOULD ALSO REQUIRED ARC FAULT |
| PROTECTION. |
| 210.12B, 408.4 |
| |
| 6) NOTE: OK. |
| |
| 7) NOTE: OK. |
| |
| 8) NOTE: OK, HOWEVER SEE NEW NOTE. |
| |
| ** PREVIOUS NEWNOTE ** |
| PLEASE SEE MISSING GFI RECEPT |
| FOR CU. 210.63,210.8A2 |
| |
| 9) NOTE: OK. |
| |
| 10) NOTE: OK. |
| |
| 11) NOTE: OK. |
| |
| ** NEW NOTES ** |
| |
| 12) NOTE: PLEASE SEE NOTE" ** IMPORTANT** "NOTE BELOW |
| WHICH WAS AT THE END OF THE PREVIOUS REVIEW NOTES WHICH |
| ASKED FOR ALL OLD SHEETS TO BE REMOVED. PLEASE SEE THIS |
| WAS NOT DONE. PLEASE DO SO BEFORE RESUBMITTING PLANS |
| FOR NEXT REVIEW AS THIS WILL HELP IN NOT DELAYING |
| PROJECT. |
| ** NOTED PREVIOUS REVIEW** |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE, PLANS WILL BE |
| PICKED UP FOR CORRECTIONS. PLEASE KNOW, |
| BEFORE RESUBMITTING PLANS, ALL |
| OLD/VOIDED SHEETS MUST BE COMPLETELY |
| REMOVED FROM SETS AND ONLY NEW REVISED |
| SHEETS SHOULD BE INSERTED INTO COMPLETE |
| SETS FOR REVIEW AND STAMPING. ONLY ONE |
| COPY OF THE OLD/VOIDED SHEETS SHOULD BE |
| SUBMITTED SEAPARATELY FOR REFERENCE. |
| |
| 13) NOTE: PLEASE SEE THE NEW GFI RECEPT REQUIRED FOR |
| THE OUTSIDE CU WHICH WAS ADDED TO THESE PLANS IS BEING |
| SHOWN CIRCUITED TO THE #1, WHICH ALSO FEEDS THE AHU. |
| MAY NOT BE TAPPED FROM THIS 220VA CIRCUIT . |
| 310.16,240.4., 240.21 ETC |
| |
| 14) NOTE: PLEASE SEE THE RECORDED NOTICE OF COMMENCMENT |
| SUBMITTED IS NO LONGER VALID AS IS HAS EXCEEDING THE |
| 90DAYS SINCE BEING RECORD AND WORK HAS NOT COMMENCED. |
| PLEASE SEE FS 713.13(2). PLEASE KNOW, THE RECORDED NOC |
| IS ONLY REQUIRED AFTER PERMIT IS ISSUED AND BEFORE |
| PICKING UP PERMIT. |
| |
| 15) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| DESIGN PROFESSIONALS AND REPEAT COMMENTS FOR CODE |
| COMPLIANCE. THIS IS ONLY A NOTICE GIVEN AT THIS TIME. |
| PLEASE KNOW ONE SET OF ELECTRICAL SHEETS FROM EACH |
| SUBMITTED SET IS BEING RETAINED BY THIS OFFICE. |
| |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CITY OF WEST PALM BEACH |
| CONSTUCTION SERVICES DEPT. |
| 561-805-6717 |
| [email protected] |
| |
| |
| |
| |