Plan Review Notes For Permit 06071495 |
Permit Number |
06071495 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-07-28 00:00:00 | *** DENIED *** | | 1) MECHANICAL PLANS NEED THE JOB ADDRESS | | ON THEM. | | | | 2) ALL INFORMATION, DRAWINGS, | | SPECIFICATIONS AND ACCOMPANYING DATA | | SHALL BEAR THE NAME AND SIGNATURE OF THE | | PERSON RESPONSIBLE FOR THE DESIGN. PER | | FBC 104.2.1 . | | | | 3) SEE CONDENSER DETAIL, 18GA. STRAP IS | | NOT PERMITTED, MUST USE CLIPS, PLEASE | | CORRECT. | | | | 4) MECHANICAL PLANS MUST ALSO HAVE ON | | THEM THE A/C EQUIPMENT LISTING WITH ALL | | THE PERTINENT INFORMATION. | | | | 5) CLOTHES DRYER VENT TERMINATION MUST | | BE A MIN. OF 4 FT. FROM A/C CONDENSER | | UNIT, PER 2004 FBC/M 501.2 , PLEASE | | CORRECT. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|