Plan Review Notes
Plan Review Notes For Permit 06071495
Permit Number 06071495
Review Stop E
Sequence Number 1
Notes
Date Text
2006-07-27 00:00:00******** UNSAT *********
  
 1) NOTE: PLEASE SEE THAT THE FOLLOWING
 CODES ARE REFELCTED ON ELECTRICAL PLANS
 AT A MINIMUM. NFPA-70 2002 (NEC) AND
 NFPA-72 2002.
 PLEASE SEE PLANS MENTIONS , "LATEST
 EDITIONS", HOWEVER THE LATEST EDITIONS
 ARE NOT YET ADOPTED BY THE STATE OF
 FLORIDA.
  
 2) NOTE: PLEASE BE SURE TITLE BLOCKS
 CONTAIN ALL INFORMATION AS REQUIRED BY
 FAC 61G1-16.004. PLEASE SEE MISSING THE
 PRINTED NAME AND LICENSE NUMEBR OF SAID
 ARCHIECT.
 PLEASE ALSO BE SURE ALL SEALS ARE
 RAISED, CLEAR AND VISSABLE WITH ALL
 INFORMATION ON SAID SEALS. PLEASE SEE
 THAT MANY OF THE SEALS ARE NOT CELAR.
 FS 481.221
  
 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9. FBC 106.1.2
  
 4) NOTE: PLEASE CORRELATE AND COMPLETE
 INFORMATION FOR AHU KW RATING. PLEASE
 SEE LOAD CALCS INDICATE 100% = 6500VA ,
 YET THE OCP AND CONDUCTOR SIZES LEND TO
 THIS AS A 10KW HEAT STRIP? PLEASE
 CORRELATE AS THE MECH SHEETS SHOW
 ANOTHER SIZE. PLEASE ADJUST ALL ONCE THE
 KW RATING IS SET.
 424.3B.,220,310.16,240.4 ETC
  
 5) NOTE: PLEASE IDICATE ALL CIRCUITS ON
 PANELS WHICH ARE REQUIRED TO CONTAIN ARC
 FAULT PROTECTION. PLEASE SEE NOTES FOR
 ARC FAULT MENTIONS ONLY RECEPTS, LTS AND
 FANS. (NO FANS SHOWN ) ALTHOUGH
 PROTECTION OF SD'S IS ALSO REQUIRED.
 PELASE SEE NOTE ABOVE MENTIONS AND PLANS
 SHOWS SD'S CIRCUITED TO KITCHEN AND BATH
 RM LIGHTING, WHICH IS OK, HOWEVER THIS
 CIRCUIT WOULD ALSO REQUIRED ARC FAULT
 PROTECTION.
 210.12B, 408.4
  
 6) NOTE: PLEASE COMPLETE PANEL SCHEDULE
 SPECIFIC TO ALL AREAS. IE LIVING RM
 RECEPTS, BATH LTS, BEDRM #3, ETC.
 408.4
 IT IS KNOW TO THIS OFFICE THESE WILL
 MOST LIKELY BE REVISED DURING
 CONSTRUCTION.
  
 7) NOTE: PLEASE SEE A CIRCUIT #17 SEEM
 TO BE IN THE CLOSET IN BEDRM #2 WHICH
 DOES NOT SEEM TO FEED ANYTHING?
 PLEASE CLARIFY.
 106.1.2
  
 8) NOTE: PLEASE SEE MISSING GFI RECEPT
 FOR CU. 210.63,210.8A2
  
 9) NOTE: PLEASE SEE MISSING GFI RECEPT
 FOR KITCHEN COUNTER SPACE. 210.52C1,
 210.8A6
  
 10) NOTE: PLEASE SEE MISSING RECEPTS FOR
 MORE THAN 2' OF WALL SPACE.
 210.52
 *REDLINED**
  
 11) NOTE: PLEASE CLARIFY SERVICE. IS
 THIS A SEPARATE METER OR A METERMAIN
 COMBO?
 106.1.2
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE, PLANS WILL BE
 PICKED UP FOR CORRECTIONS. PLEASE KNOW,
 BEFORE RESUBMITTING PLANS, ALL
 OLD/VOIDED SHEETS MUST BE COMPLETELY
 REMOVED FROM SETS AND ONLY NEW REVISED
 SHEETS SHOULD BE INSERTED INTO COMPLETE
 SETS FOR REVIEW AND STAMPING. ONLY ONE
 COPY OF THE OLD/VOIDED SHEETS SHOULD BE
 SUBMITTED SEAPARATELY FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  