2006-07-27 00:00:00 | ******** UNSAT ********* |
| |
| 1) NOTE: PLEASE SEE THAT THE FOLLOWING |
| CODES ARE REFELCTED ON ELECTRICAL PLANS |
| AT A MINIMUM. NFPA-70 2002 (NEC) AND |
| NFPA-72 2002. |
| PLEASE SEE PLANS MENTIONS , "LATEST |
| EDITIONS", HOWEVER THE LATEST EDITIONS |
| ARE NOT YET ADOPTED BY THE STATE OF |
| FLORIDA. |
| |
| 2) NOTE: PLEASE BE SURE TITLE BLOCKS |
| CONTAIN ALL INFORMATION AS REQUIRED BY |
| FAC 61G1-16.004. PLEASE SEE MISSING THE |
| PRINTED NAME AND LICENSE NUMEBR OF SAID |
| ARCHIECT. |
| PLEASE ALSO BE SURE ALL SEALS ARE |
| RAISED, CLEAR AND VISSABLE WITH ALL |
| INFORMATION ON SAID SEALS. PLEASE SEE |
| THAT MANY OF THE SEALS ARE NOT CELAR. |
| FS 481.221 |
| |
| 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| RATED FOR THE AVAILABLE FAULT CURRENT. |
| PER 110.9. FBC 106.1.2 |
| |
| 4) NOTE: PLEASE CORRELATE AND COMPLETE |
| INFORMATION FOR AHU KW RATING. PLEASE |
| SEE LOAD CALCS INDICATE 100% = 6500VA , |
| YET THE OCP AND CONDUCTOR SIZES LEND TO |
| THIS AS A 10KW HEAT STRIP? PLEASE |
| CORRELATE AS THE MECH SHEETS SHOW |
| ANOTHER SIZE. PLEASE ADJUST ALL ONCE THE |
| KW RATING IS SET. |
| 424.3B.,220,310.16,240.4 ETC |
| |
| 5) NOTE: PLEASE IDICATE ALL CIRCUITS ON |
| PANELS WHICH ARE REQUIRED TO CONTAIN ARC |
| FAULT PROTECTION. PLEASE SEE NOTES FOR |
| ARC FAULT MENTIONS ONLY RECEPTS, LTS AND |
| FANS. (NO FANS SHOWN ) ALTHOUGH |
| PROTECTION OF SD'S IS ALSO REQUIRED. |
| PELASE SEE NOTE ABOVE MENTIONS AND PLANS |
| SHOWS SD'S CIRCUITED TO KITCHEN AND BATH |
| RM LIGHTING, WHICH IS OK, HOWEVER THIS |
| CIRCUIT WOULD ALSO REQUIRED ARC FAULT |
| PROTECTION. |
| 210.12B, 408.4 |
| |
| 6) NOTE: PLEASE COMPLETE PANEL SCHEDULE |
| SPECIFIC TO ALL AREAS. IE LIVING RM |
| RECEPTS, BATH LTS, BEDRM #3, ETC. |
| 408.4 |
| IT IS KNOW TO THIS OFFICE THESE WILL |
| MOST LIKELY BE REVISED DURING |
| CONSTRUCTION. |
| |
| 7) NOTE: PLEASE SEE A CIRCUIT #17 SEEM |
| TO BE IN THE CLOSET IN BEDRM #2 WHICH |
| DOES NOT SEEM TO FEED ANYTHING? |
| PLEASE CLARIFY. |
| 106.1.2 |
| |
| 8) NOTE: PLEASE SEE MISSING GFI RECEPT |
| FOR CU. 210.63,210.8A2 |
| |
| 9) NOTE: PLEASE SEE MISSING GFI RECEPT |
| FOR KITCHEN COUNTER SPACE. 210.52C1, |
| 210.8A6 |
| |
| 10) NOTE: PLEASE SEE MISSING RECEPTS FOR |
| MORE THAN 2' OF WALL SPACE. |
| 210.52 |
| *REDLINED** |
| |
| 11) NOTE: PLEASE CLARIFY SERVICE. IS |
| THIS A SEPARATE METER OR A METERMAIN |
| COMBO? |
| 106.1.2 |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE, PLANS WILL BE |
| PICKED UP FOR CORRECTIONS. PLEASE KNOW, |
| BEFORE RESUBMITTING PLANS, ALL |
| OLD/VOIDED SHEETS MUST BE COMPLETELY |
| REMOVED FROM SETS AND ONLY NEW REVISED |
| SHEETS SHOULD BE INSERTED INTO COMPLETE |
| SETS FOR REVIEW AND STAMPING. ONLY ONE |
| COPY OF THE OLD/VOIDED SHEETS SHOULD BE |
| SUBMITTED SEAPARATELY FOR REFERENCE. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CITY OF WEST PALM BEACH |
| CONSTUCTION SERVICES DEPT. |
| 561-805-6717 |
| [email protected] |
| |
| |
| |
| |