2006-08-08 00:00:00 | |
| |
| DENIED |
| |
| 1) THE CLAIMED VALUATION ON THE PERMIT |
| APPLICATION IS LOW. FOR PERMITTING |
| PURPOSES, VALUATION OF BUILDINGS AND |
| SYSTEMS SHALL BE THE TOTAL REPLACEMENT |
| COST EXCLUDING LAND VALUE. OUR VALUATION |
| REFERENCE IS ICC (BVD), MARSHALL-SWIFT |
| AND MEANS COST ANALYSIS SERVICES PER |
| 108.3 FBC* |
| |
| 2) THE STATE OF FLORIDA REQUIRES |
| COLLECTION OF A RADON SURCHARGE ON ALL |
| NEW CONSTRUCTION COMPUTED ON UNDER ROOF |
| FLOOR SPACE PER 10D-91 FAC. THESE FEES |
| WILL BE ADDED TO THE PERMIT APPLICATION |
| FEES |
| |
| 3) A TITLE BLOCK WITH THE INFORMATION |
| SPECIFIED PER 61G1-16.004 FAC SHALL BE |
| PRESENT ON DRAWINGS ISSUED BY THE |
| RESPONSIBLE ARCHITECT AND MUST,AT A |
| MINIMUM CONTAIN |
| 1)FIRM NAME,ADDRESS, AND TELEPHONE # |
| 2)FIRM LICENCE # |
| 3)NAME OF PROJECT |
| 4)DATE PREPARED |
| 5)A SPACE FOR SIGNATURE & DATED SEAL |
| 6)A SPACE FOR PRINTED NAME AND LICENCE# |
| OF PERSON SEALING THE DOCUMENT |
| |
| 4) SUBMIT ENGINEERED TRUSS DRAWINGS THAT |
| COMPLY WITH R802.10.1 FBC WITH PERMIT |
| APPLICATION OR BEFORE INSTALLATION THAT |
| HAVE BEEN REVIEWED AND APPROVED BY THE |
| DESIGNER OF RECORD |
| |
| 5) PROVIDE A SITE PLAN THAT SHOWS |
| DRAINAGE IN COMPLIANCE WITH THE |
| REQUIREMENTS OF R403.1 |
| |
| 6) MINIMUM DESIGN LOADS ON DRAWINGS |
| REFERENCED TO ASCE 7-98, PLEASE SEE |
| REFFERENCE ADOPTED BY THE 2004 FBC IS |
| ASCE 7-02. DRAWINGS TO REFLECT THIS SEE |
| A/3, A/4 AND A/6 |
| |
| 7) GENERAL NOTES A/6 STATE R30 |
| INSULATION IN CEILING ABOVE CONDITIONED |
| SPACE BUT WALL SECTION SHOWS R19 PLEASE |
| CLARIFY |
| |
| 8) PROVIDE SILL DETAIL |
| |
| 9) DRAWINGS SHOW TOP OF BEAM AT 8'-2" |
| BUT GARAGE DOOR IS A 7'-0" AND THE |
| LINTEL PC-1 IS 24" DEEP PLEASE CLARIFY. |
| |
| 10) BEFORE A PERMIT TO CONSTRUCT, MAY |
| BE ISSUED, IMPACT FEES MUST BE PAID TO |
| PALM BEACH COUNTY. THE ACTUAL PERMIT |
| SETS OF PLANS MUST BE STAMPED BY THAT |
| OFFICE, AND A COPY OF THE PAID RECEIPT |
| ATTACHED TO THE PERMIT APPLICATION. |
| PLEASE CALL (561) 233-5025 FOR MORE |
| INFORMATION. |
| |
| 11) SUBMIT ENERGY CALC'S PER 13-101.2.2 |
| FBC. BE SURE THAT THEY ARE SIGNED AND |
| DATED BY PREPARER AND OWNER/AGENT PRIOR |
| TO SUBMITTAL. PLEASE SUBMIT ON FORM |
| 600A-2004 AND BE SURE CEILING INSULATION |
| VALUE MATCHES DRAWINGS |
| |
| 12) THE FOLLOWING PRODUCT APPROVALS |
| REQUIRE CORRECTIONS |
| A) THURMA-TRU DOES NOT HAVE STATE |
| APPROVAL FOR THIS PRODUCT (WILL GIVE |
| MIAMI-DADE NOA A LOCAL PROD. APPROVAL) |
| B) GARAGE DOOR DESIGN PRESSURE DOES NOT |
| MEET THE DESIGN PRESSURE IN THE DOOR |
| SCHEDULE |
| C) TIMBERLINE SELECT 40 SHINGLE NOA HAS |
| BEEN REVISED (04-0305.04) |
| D) KINCO NOA FOR SGD HAS EXPIRED SEE |
| STATE APPROVAL CLICK ON PDF FILE AND |
| PRINT INSTALLATION FOR 1X BUCK AND 2X |
| BUCK BOTH ARE GOOD TO -70 PSF (FLORIDA |
| SHEET OK) |
| E) STATE PRODUCT APPROVAL DOES NOT COVER |
| M40 XHP ONLY HP PLEASE SUBMIT REVISED |
| MIAMI-DADE NOA (06-0413.06) FOR LOCAL |
| PROD APPROVAL |
| |
| THOSE PRODUCTS WHICH ARE REGULATED BY |
| DCA RULE 9B-72 SHALL BE REVIEWED AND |
| APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL PER 106.3.3 FBC* |
| (PLEASE CHECK CORRECTED COPIES) |
| |
| 13)A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT IS REQUIRED PRIOR TO |
| A PERMIT BEING ISSUED |
| |
| BLDG PLAN REVIEW |
| ADRIAN MORSE |
| 561-805-6716 |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |