2007-02-12 14:58:12 | |
| |
| *** UNSAT *** |
| |
| 1) NOTE: PLEASE SEE THE REVISIONS SUBMTTED ARE T DATED |
| 10/23/06., HOWEVER THERE ARE SEVERAL REVISIONS TO THE |
| EXISTING DWELLING. PLANS INDICATE THE ENITER DWELLING |
| BEING REWIRED. PLEASE SEE THAT ANY REVISIONS AFTER THAT |
| DATE WOULD BE REFLECTED ON TITLE BLOCKS AND THEN THE |
| PLANS LABELED WITH THE SAME NUMERICAL DESIGANTION. |
| PLEASE CORRELATE AND SUBMIT REVISIONS AS NEEDED. |
| 106.1, 106.3.5.4 |
| |
| 2) NOTE: PLEASE SEE THE PANEL SCHEDULE SUBMITED IS THE |
| SAME AS THE PREVIOUS PANEL SCHEDULE ISSUED FOR PERMIT. |
| PLEASE LABEL ALL NEW CIRCUITS, ARC FAULT FOR NEW WIRED |
| BEDROOMS, DEDICATED FOR BATH, ETC |
| 210.52, 210.12, 210.11C3. |
| PLEASE SEE PANEL SCHEDULE SHALL BE ROOM AND AREA |
| SPECIFIC. PLEASE SEE THE FOLLOWING TEXT EXTRACTED FROM |
| THE CODE COMMENTARY. |
| *CODE TO REQUIRE THAT THE IDENTIFICATION FOR EVERY |
| CIRCUIT SUPPLIED BY A PANELBOARD OR SWITCHBOARD BE |
| LEGIBLE AND CLEARLY STATE THE SPECIFIC PURPOSE FOR |
| WHICH THE CIRCUIT IS USED. CIRCUITS USED FOR THE SAME |
| PURPOSE MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR |
| EXAMPLE, SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY |
| OUTLETS IN THE KITCHEN, DINING ROOM, AND KITCHEN |
| COUNTERTOPS. IDENTIFYING THE CIRCUITS AS SMALL |
| APPLIANCE BRANCH CIRCUITS IS NOT ACCEPTABLE; INSTEAD, |
| THEY SHOULD BE IDENTIFIED AS ``KITCHEN WALL |
| RECEPTACLES,'' ``DINING ROOM FLOOR RECEPTACLE,'' OR |
| ``KITCHEN COUNTERTOP RECEPTACLES LEFT OF SINK.'' |
| CIRCUIT DIRECTORIES CONTAINING MULTIPLE ENTRIES WITH |
| ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT PROVIDE THE |
| SUFFICIENT DETAIL REQUIRED BY THIS SECTION. |
| 408.4, 310.16, 240.4 |
| |
| 3) NOTE: PLEASE SEE THAT AS THE SCOPE OF WORK FROM THE |
| ORIGINAL PERMITTED SET OF PLANS HAS INCREASED, PLEASE |
| ADJUST THE VALUE FROM THE APPLIED SCOPE OF WORK AND PAY |
| ADDITIONAL FEES. |
| PLEASE SEE THAT REVISED BUILDING SHOULD ALSO BE |
| SUBMITTED FOR NEW WALL AREA. |
| FBC 108.3 |
| |
| IF THERE ARE ANY QUESTIONS, PLEASE CALL. |
| |