2006-10-15 20:29:44 | ** UNSAT 2ND REVIEW *** |
| |
| PLEASE SEE ONE NOTE FROM PREVIOUS REVIEW AND NEW |
| NOTE(S). |
| |
| 1) NOTE: PLEASE CORRELATE RISER AND PLANS. PLEASE SEE |
| PLANS NOW SHOWS A J-BOX WHERE RISER SHOWS AND NEW MAIN |
| DISCONNECT?? |
| FBC 106.1.2, NEC 2002 |
| |
| 2) NOTE: PLEASE PLACE PLANS INTO TWO COMPLETE SETS |
| ATTACHED AND BOTH SIGNED BY THE PERSON RESPONSIBLE FOR |
| PLANS AND DESIGN. |
| FBC 106.1.2, 106.1.3 |
| |
| 3) NOTE: PLEASE SEE A/ C LOAD IN LOAD CALCS STILL |
| MENTIONS "COMP" , HOWEVER THE HEAT IS THE LARGER OF THE |
| TWO LOADS. 220.21. |
| PLEASE CORRELATE. |
| |
| 4) NOTE: PLEASE SEE ALL THREE COPIES OF SURVEY'S HAVE |
| BEEN "VOIDED" AS THEY DO NOT CONTAIN AN ORIGINAL |
| SIGNATURE AND SEAL AS REQUIRED UNDER FAC 61G17, FS |
| 472.025. PLEASE SEE STATEMENT ON SURVEY EVEN SAYS NOT |
| VALID W/OUT SEAL. |
| |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |