Plan Review Notes
Plan Review Notes For Permit 06071461
Permit Number 06071461
Review Stop B
Sequence Number 2
Notes
Date Text
2006-10-20 11:10:41 
  
 DENIED
  
 1) ENERGY CALC'SSECTION 9A, EXTERIOR WOOD WALLS REQUIRE
 R11 INSULATION VALUE PLEASE CORRECT AND RESUBMIT. BLOCK
 STEM WALL IS NOT APPLICABLE
  
 2) PER 713.13(2) F.S.
 IF THE IMPROVEMENT DESCRIBED IN THE NOC HAS NOT
 COMMENCED WITHIN 90 DAYS OF RECORDING THE NOTICE IS
 VOID
  
 3) IF NO FURTHER CORRECTIONS ARE TO BE MADE TO DRAWING
 PLEASE SUBMIT 2 COMPLETE CORRECTED COPIES FOR REVEIW
 AND STAMPING WITH ONE LOOSE COPY OF ANY OLD/VOIDED
 SHEETS
  
 BLDG PLAN REVIEW