2006-08-09 00:00:00 | IN ELEC FOR REVIEW, IN PROGRESS. |
| *** UNSAT **** |
| |
| 1) NOTE: PLEASE SEE CODE REFERENCED IN |
| NOTES MENTIONS THE 1996 NEC? |
| PLEASE SEE THIS SHOULD READ 2002 NEC. |
| |
| 2) NOTE: PLEASE SEE MISSING RECEPTS PER |
| 210.52. (REDLINED) |
| |
| 3) NOTE: PLEASE SEE RISER DOES NOT SEEM |
| TO CORRELATE WITH PLANS AND PANEL NOTE. |
| PLEASE SEE RISER SHOWS THIS AS A NEW |
| PROPOSED SERVICE WITH A NEW MAIN LOCATED |
| OUTSIDE ,PLANS DO NOT SHOW ANY MAIN AND |
| PANEL NOTE MENTIONS THIS IS EXSITING. |
| PLEASE EXPLAIN HOW THE SERVICE IS |
| EXISTING AS SHOWN AS THE ADDITION HAS |
| NOT YET BEEN BUILT? |
| PLEASE CORRELATE AND REVISE AS NEEDED. |
| FBC 106.1.2 ADMIN SECT. |
| |
| 4) NOTE: PLEASE SEE AN "EQUIPMENT |
| GROUNDING CONDUCTOR" IS BEING SHOWN WITH |
| THE SEC'S. PLEASE SEE 250.24B, 250.6 FOR |
| OBJECTIONABLE CURRENTS AND THE |
| "EQUIPMENT GROUNDING CONDUCTOR" BEING |
| INSTALLED "AFTER" THE FIRST MEANS OF |
| DISCONNECT. |
| |
| 5) NOTE: PLEASE SEE MISSING A/C CU |
| DISCONNECT PER 440.11. |
| |
| 6) NOTE: PLEASE SE EMISSING GFI RECEPT |
| FOR CU. 210.63,210.8A. |
| |
| 7) NOTE: PLEASE SEE LOAD CALCULATIONS |
| WHICH INDICATE THE CU AT THE LOAD LARGER |
| THAN HEAT AT 8KW, YET THE AHU'S HEAT IS |
| THE 8KW WHICH IS LARGER. |
| PLEASE ADJUST. |
| PLEASE SEE 220.21, 220.30C |
| |
| 8) NOTE: PLEASE SEE MISSING KITCHEN |
| COUNTER SPACE GFI RECEPT REQUIRED PER |
| 210.52C1, 210.8A6 |
| |
| 9) NOTE: PLEASE SEE WALL SPACE IN |
| KITCHEN WHICH IS 2' OR MORE IS REQUIRED |
| TO CONTAIN A RECEPT. PLEASE SEE |
| 210.52B1, 210.11C1, AS THIS IS REQUIRED |
| OT BE ON ONE OR MORE OF THE SMALL |
| APPLIANCE CIRCUITS. |
| |
| 10) NOTE: PLEASE SEE PLANS IDNICATE A |
| NEW DISPOSAL, HOWEVER THIS COULD NOT BE |
| LOCATED ON PANEL SCHEDULE OR IN LOAD |
| CALCULATIONS. |
| |
| 11) NOTE: PLEASE SE MIN OCP FOR THE AHU |
| SHALL BE SIZED AT 125% PER 424.3B. |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. PLEASE DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS INNEW SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CONSTUCTION SERVICES DEPT. |