2006-08-09 00:00:00IN ELEC FOR REVIEW, IN PROGRESS.
 *** UNSAT ****
  
 1) NOTE: PLEASE SEE CODE REFERENCED IN
 NOTES MENTIONS THE 1996 NEC?
 PLEASE SEE THIS SHOULD READ 2002 NEC.
  
 2) NOTE: PLEASE SEE MISSING RECEPTS PER
 210.52. (REDLINED)
  
 3) NOTE: PLEASE SEE RISER DOES NOT SEEM
 TO CORRELATE WITH PLANS AND PANEL NOTE.
 PLEASE SEE RISER SHOWS THIS AS A NEW
 PROPOSED SERVICE WITH A NEW MAIN LOCATED
 OUTSIDE ,PLANS DO NOT SHOW ANY MAIN AND
 PANEL NOTE MENTIONS THIS IS EXSITING.
 PLEASE EXPLAIN HOW THE SERVICE IS
 EXISTING AS SHOWN AS THE ADDITION HAS
 NOT YET BEEN BUILT?
 PLEASE CORRELATE AND REVISE AS NEEDED.
 FBC 106.1.2 ADMIN SECT.
  
 4) NOTE: PLEASE SEE AN "EQUIPMENT
 GROUNDING CONDUCTOR" IS BEING SHOWN WITH
 THE SEC'S. PLEASE SEE 250.24B, 250.6 FOR
 OBJECTIONABLE CURRENTS AND THE
 "EQUIPMENT GROUNDING CONDUCTOR" BEING
 INSTALLED "AFTER" THE FIRST MEANS OF
 DISCONNECT.
  
 5) NOTE: PLEASE SEE MISSING A/C CU
 DISCONNECT PER 440.11.
  
 6) NOTE: PLEASE SE EMISSING GFI RECEPT
 FOR CU. 210.63,210.8A.
  
 7) NOTE: PLEASE SEE LOAD CALCULATIONS
 WHICH INDICATE THE CU AT THE LOAD LARGER
 THAN HEAT AT 8KW, YET THE AHU'S HEAT IS
 THE 8KW WHICH IS LARGER.
 PLEASE ADJUST.
 PLEASE SEE 220.21, 220.30C
  
 8) NOTE: PLEASE SEE MISSING KITCHEN
 COUNTER SPACE GFI RECEPT REQUIRED PER
 210.52C1, 210.8A6
  
 9) NOTE: PLEASE SEE WALL SPACE IN
 KITCHEN WHICH IS 2' OR MORE IS REQUIRED
 TO CONTAIN A RECEPT. PLEASE SEE
 210.52B1, 210.11C1, AS THIS IS REQUIRED
 OT BE ON ONE OR MORE OF THE SMALL
 APPLIANCE CIRCUITS.
  
 10) NOTE: PLEASE SEE PLANS IDNICATE A
 NEW DISPOSAL, HOWEVER THIS COULD NOT BE
 LOCATED ON PANEL SCHEDULE OR IN LOAD
 CALCULATIONS.
  
 11) NOTE: PLEASE SE MIN OCP FOR THE AHU
 SHALL BE SIZED AT 125% PER 424.3B.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. PLEASE DO NOT LEAVE ANY
 OLD/VOIDED SHEETS INNEW SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  