| 1) THE CLAIMED VALUATION ON THE PERMIT |
| APPLICATION IS LOW. FOR PERMITTING |
| PURPOSES, VALUATION OF BUILDINGS AND |
| SYSTEMS SHALL BE THE TOTAL REPLACEMENT |
| COST EXCLUDING LAND VALUE. OUR VALUATION |
| REFERENCE IS ICC (BVD), MARSHALL-SWIFT |
| AND MEANS COST ANALYSIS SERVICES PER |
| 108.3 FBC* |
| |
| 2) THE STATE OF FLORIDA REQUIRES |
| COLLECTION OF A RADON SURCHARGE ON ALL |
| NEW CONSTRUCTION COMPUTED ON UNDER ROOF |
| FLOOR SPACE PER 10D-91 FAC. THESE FEES |
| WILL BE ADDED TO THE PERMIT APPLICATION |
| FEES |
| |
| 3) IN AREAS OF QUESTIONABLE SOILS AS |
| SHOWN IN THE OFFICIAL ZONING MAP OF THE |
| CITY OF WEST PALM BEACH, 2 COPIES OF A |
| SOIL TEST REPORT SHALL BE SUBMITTED PER |
| R401.4 |
| |
| 4) SUBMIT ENERGY CALC'S PER 13-101.2.2 |
| FBC. BE SURE THAT THEY ARE SIGNED AND |
| DATED BY PREPARER AND OWNER/AGENT PRIOR |
| TO SUBMITTAL |
| *****NOTE THE CALC'S THAT WERE SUBMITTED |
| HAVE WRONG INFORMATION 8B IS NOT |
| APPLICABLE BECAUSE FLOOR TYPE IS 8A AND |
| WALL TYPE IS WOOD FRAME AND REQUIRES |
| R-11, PLEASE CORRECT***** |
| |
| 5) CONTRACTOR DID NOT SIGN APPLICATION |
| |
| 6) PRODUCT APPROVAL FOR WINDOWS |
| INCORRECT, FLORIDA COVER SHEET FOR |
| TR-9100 WINDOWS NOT 240 AS MIAMI-DADE |
| NOA. IF USING 240 WINDOWS THE CORRECT |
| FL# IS 6738 AND THE MIAMI-DADE REPORT |
| THAT ACCOMPANIES THE COVER IS 05-0930.03 |
| |