Date Text
2006-09-10 00:00:00*** UNSAT ***
  
 1) NOTE: PLEASE SEE MISSING GFI RECEPTS
 PER 210.52C1 ALONG KITCHEN COUNTER
 SPACE.
 PLEASE SEE IS DIFFICULT TO SCALE AS
 PLANS SUBMITTED ARE NOT SCALED OR DONE
 TO THE MIN 1/8" SCALE AS REQUIRED UNDER
 THE FBC 106.1
  
 2) NOTE: PLEASE SEE MISSING AHU'S AND
 CU'S ON PLANS ALONG WITH DISCONNECTS PER
 440.11, 110.26
  
 3) NOTE: PLEASE SEE AS THE A/C CU'S ARE
 NOT SHOWN, UNABLE TO VERIFY THE GFI
 RECEPTS REQUIRED PER 210.63/210.8A
  
 4) NOTE: PLEASE SEE PLANS DO NOT SHOW
 WATER HEATERS AND DISCONNECTS REQUIRED.
 PLEASE SEE 422.31, 422.17
  
 5) NOTE: PLEASE SEE LOAD CALCULATIONS
 STILL BE TO BE REVISED TO NEC 220.31
 PLEASE SEE THE A/C HEAT MAY NOT BE
 FIGURED IN WITH THE GEN LTS AND RECEPTS
 .
  
 6) NOTE: PLEASE SEE 408.6, THE PANEL
 SCHEDULE SHALL BE SPECIFIC TO THE ROOMS
 AND AREAS IN WHICH THEY ARE FEEDING, IT
 IS KNOWN THAT THESE WILL MOST LIKELY BE
 REVISED DURING CONSTRUCTION, HOWEVER IF
 KNOWN AT THIS TIME PLEASE SHOW, AS THEY
 CAN BE REVISED AT A LATER DATE.
  
 7) NOTE: PLEASE SEE GROUNDING ELECTRODE
 CONDUCTOR TO BE SIZED PER 250.66.
 #2 MIN).
  
 8) NOTE: PLEASE SEE THAT ALL PLANS AND
 DESIGNS SHALL CONTAIN THE PRINTED NAME
 AND SIGNATURE OF THE PERSON RESPOSIBLE
 FOR PLANS/DESIGNS.
 DRAWN BY: ETC,,,,
 THIS IS FOR ALL DOCUMENTS.
 FBC 106.1.21
  
 9) NOTE: PLEASE KNOW ALL SD'S WITHIN 20'
 OF COOKING APPLIANCES SHALL BE RESETTING
 /PHOTO-ELECTRIC TYPE PER NFPA-72 11.8.3
 PLEASE ALSO KNOW ALL SD'S MUST BE
 ATLEAST 3' FROM BATH DOOR.
  
 10) NOTE: PLEASE SEE 410.8FOR CLOSET
 LTS WHICH ARE BEING SHOWN IN SHELVING
 AREA.
  
 11) NOTE: PLEASE SEE 210.52B1 AS THE
 DINING ROOMS AND AREAS ARE REQUIRED TO
 BE ON ONE OR MORE OF THE SMALL APPLIANCE
 CIRUITS. PLEASE SEE 210.11C1, 220.16
  
 12) NOTE: PLEASE INCLUDE AIC RATINGS FOR
 ALL NEW MAINS PER 110.9.
  
 13) NOTE: PLEASE SEE GAS PIPE REQUIRED
 TO BE BONDEDTO THE GROUNDING ELECTRODE
 SYSTEM.250.104
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717