2006-09-10 00:00:00 | *** UNSAT *** |
| |
| 1) NOTE: PLEASE SEE MISSING GFI RECEPTS |
| PER 210.52C1 ALONG KITCHEN COUNTER |
| SPACE. |
| PLEASE SEE IS DIFFICULT TO SCALE AS |
| PLANS SUBMITTED ARE NOT SCALED OR DONE |
| TO THE MIN 1/8" SCALE AS REQUIRED UNDER |
| THE FBC 106.1 |
| |
| 2) NOTE: PLEASE SEE MISSING AHU'S AND |
| CU'S ON PLANS ALONG WITH DISCONNECTS PER |
| 440.11, 110.26 |
| |
| 3) NOTE: PLEASE SEE AS THE A/C CU'S ARE |
| NOT SHOWN, UNABLE TO VERIFY THE GFI |
| RECEPTS REQUIRED PER 210.63/210.8A |
| |
| 4) NOTE: PLEASE SEE PLANS DO NOT SHOW |
| WATER HEATERS AND DISCONNECTS REQUIRED. |
| PLEASE SEE 422.31, 422.17 |
| |
| 5) NOTE: PLEASE SEE LOAD CALCULATIONS |
| STILL BE TO BE REVISED TO NEC 220.31 |
| PLEASE SEE THE A/C HEAT MAY NOT BE |
| FIGURED IN WITH THE GEN LTS AND RECEPTS |
| . |
| |
| 6) NOTE: PLEASE SEE 408.6, THE PANEL |
| SCHEDULE SHALL BE SPECIFIC TO THE ROOMS |
| AND AREAS IN WHICH THEY ARE FEEDING, IT |
| IS KNOWN THAT THESE WILL MOST LIKELY BE |
| REVISED DURING CONSTRUCTION, HOWEVER IF |
| KNOWN AT THIS TIME PLEASE SHOW, AS THEY |
| CAN BE REVISED AT A LATER DATE. |
| |
| 7) NOTE: PLEASE SEE GROUNDING ELECTRODE |
| CONDUCTOR TO BE SIZED PER 250.66. |
| #2 MIN). |
| |
| 8) NOTE: PLEASE SEE THAT ALL PLANS AND |
| DESIGNS SHALL CONTAIN THE PRINTED NAME |
| AND SIGNATURE OF THE PERSON RESPOSIBLE |
| FOR PLANS/DESIGNS. |
| DRAWN BY: ETC,,,, |
| THIS IS FOR ALL DOCUMENTS. |
| FBC 106.1.21 |
| |
| 9) NOTE: PLEASE KNOW ALL SD'S WITHIN 20' |
| OF COOKING APPLIANCES SHALL BE RESETTING |
| /PHOTO-ELECTRIC TYPE PER NFPA-72 11.8.3 |
| PLEASE ALSO KNOW ALL SD'S MUST BE |
| ATLEAST 3' FROM BATH DOOR. |
| |
| 10) NOTE: PLEASE SEE 410.8FOR CLOSET |
| LTS WHICH ARE BEING SHOWN IN SHELVING |
| AREA. |
| |
| 11) NOTE: PLEASE SEE 210.52B1 AS THE |
| DINING ROOMS AND AREAS ARE REQUIRED TO |
| BE ON ONE OR MORE OF THE SMALL APPLIANCE |
| CIRUITS. PLEASE SEE 210.11C1, 220.16 |
| |
| 12) NOTE: PLEASE INCLUDE AIC RATINGS FOR |
| ALL NEW MAINS PER 110.9. |
| |
| 13) NOTE: PLEASE SEE GAS PIPE REQUIRED |
| TO BE BONDEDTO THE GROUNDING ELECTRODE |
| SYSTEM.250.104 |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |