2006-08-18 00:00:00 | **** UNSAT *** |
| |
| 1) NOTE: PLEASE CORRELATE RISER WITH |
| INFORMATION FOR PANELS AND MAINS. |
| PLEASE SEE RISER SHOWS ONE SIZE FOR THIS |
| MAINS AND PANELS, AND THE PANELS SHOW A |
| DIFFERENT SIZE. |
| PLEASE COMPLETE RISER DIAGRAM AT HOUSE, |
| AS THE PANEL IS NOT SHOWN WITH |
| CONDUCTORS, CONDUITS ETC. |
| PLEASE SUBMIT PANEL SCHEDULES FOR ALL |
| MINIMUM REQUIRED CIRCUITS PER NEC. |
| PLEASE SEE SEC'S ARE NOT LARGE ENOUGH |
| FOR LOAD CALCULATIONS SHOWN. |
| PLEASE COMPLETE GROUNDING ELECTRODE |
| SYSTEM AT SERVICE AND AT MAIN HOUSE. |
| PLEASE SEE THAT PLANS ARE NOT COMPLETE |
| AT THIS TIME. |
| PLEASE SEE; |
| 210.11,220.16,210.11C1,C2, C3, , |
| 240.4,310.16, 408.4, 215.5, 250.32, |
| 250.50, 220.31, 210.12, 210.52B1, ETC |
| ETC. |
| |
| 2) NOTE: PLEASE KNOW WHEN PLANS ARE NOT |
| DONE BY AN ARCHITECT OR ENGINEER AND |
| SCOPE OF WORK DOES NOT REQUIRE THIS, |
| PLANS STILL MUST CONTAIN THE PRINTED |
| ANDME AND SIGNATURE OF THE PERSON TAKING |
| RESPONSIBILITY OF PLANS AND DESIGN/ |
| PLANS ONLY CONTAIN THE PRINTED NAME. |
| FBC 106.1.2 |
| |
| 3) NOTE: PLEASE SEE ZONING COMMENTS AS |
| THIS WILL AFFECT ELECTRICAL RISER AND |
| DESIGN. |
| |
| 4) NOTE: PLEASE SEE ELECTRICAL RISER AS |
| SHOWN ON PLAN LAYOUT SEEMS TO BE LOCATED |
| OFF THE BUILDING, PLEASE INDICATE IF |
| SERVICE IS BEING BUILT DETACHED FROM |
| STRUCTURE. IF SO, PLEASE SEE |
| 225.31-225.39 |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |