Plan Review Notes
Plan Review Notes For Permit 06071403
Permit Number 06071403
Review Stop M
Sequence Number 2
Notes
Date Text
2006-08-10 00:00:00*** DENIED ***
 1) AS NOTED IN LAST REVIEW 7-28-06 NOTE
 #3. TWO 10" RETURN AIR DUCTS IS NOT
 ENOUGH FOR A 3 1/2 TON SUSTEM WITH A 16"
 SUPPLY AIR DUCT, WHITE-OUT MAY NOT BE
 USED ON PLANS, SIGN AND DATE EACH
 CORRECTION ON PLANS AND "ALL" COPYS
 SUBMITTED.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.