Plan Review Notes
Plan Review Notes For Permit 06071369
Permit Number 06071369
Review Stop B
Sequence Number 1
Notes
Date Text
2006-08-01 00:00:00 
  
 DENIED
  
 1) PLEASE MARK MIAMI-DADE NOA DRAWING
 WITH THE MOUNTING METHOD, ANCHOR TYPE,
 CONST TYPE (WOOD, CONCRETE, ETC)
  
 2) PROVIDE THE MEAN ROOF HEIGHT ALONG
 WITH THE SHUTTER SPANS IN ORDER TO
 DETERMINE THE PRESSURES ON THE PROVIDED
 ENGINEERING
  
 3) MIAMI-DADE NOA 02-0404.01 HAS BEEN
 REVISED NEW NOA 05-1220.12 SHOULD BE
 SUBMITTED
  
 4) THE PRESSURE THAT WAS INDICATED ON
 THE DRAWING FOR ANCHOR SPACING CANNOT BE
 USED FOR SHUTTER BECAUSE THAT WOULD
 LIMIT THE SPAN TO 6'-0" OR LESS. PLEASE
 USE THE DESIGN PRESSURE THAT IS REQUIRED
 BY THE SUBMITTED ENGINEERING
  
 5) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716