Notes |
Date |
Text |
2007-04-25 16:50:08 | PANEL SCHEDULE "E | | | | SHOWS 2-P 70A BREAKER TO FEED TRANSFORMER | | | | RTU-3 SHOWS NO LOAD ON PANEL SCHEDULE. | | | | LOAD ON PANEL EXCEEDS GENERATOR OUTPUT (90 AMPERES) | | | | TWO OF THE LIGHTING LOADS ARE SHOWN AS 2-POLE 30A | | | | ALL DRAWINGS SHALL HAVE NAME OF PERSON WHO DID THE | | DESIGN | | | | PROVIDE LOADS THAT ARE ON IT PANEL FOR REVIEW. | | | | JAKE LEAHY |
|