Plan Review Notes
Plan Review Notes For Permit 06071278
Permit Number 06071278
Review Stop E
Sequence Number 3
Notes
Date Text
2007-04-25 16:50:08PANEL SCHEDULE "E
  
 SHOWS 2-P 70A BREAKER TO FEED TRANSFORMER
  
 RTU-3 SHOWS NO LOAD ON PANEL SCHEDULE.
  
 LOAD ON PANEL EXCEEDS GENERATOR OUTPUT (90 AMPERES)
  
 TWO OF THE LIGHTING LOADS ARE SHOWN AS 2-POLE 30A
  
 ALL DRAWINGS SHALL HAVE NAME OF PERSON WHO DID THE
 DESIGN
  
 PROVIDE LOADS THAT ARE ON IT PANEL FOR REVIEW.
  
 JAKE LEAHY