2007-04-23 14:43:33 | BUILDING PLAN REVIEW |
| PERMIT: 06071278 |
| ADD: 2400CENTREPARK WEST #100 |
| CONT: DAVCO ELECTRICAL CONTRACTORS, INC. |
| TEL: (561)732-3434 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2006 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVIEW 3RD |
| ACTION: DENIED |
| |
| 1)61G1-16.004 TITLE BLOCK. INFORMATION REQUIRED ON |
| TITLE BLOCK. |
| A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR |
| INTERIOR DESIGN DRAWINGS AND SPECIFICATION |
| IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A |
| MINIMUM, CONTAIN THE FOLLOWING INFORMATION: |
| (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER. |
| (2) FIRM LICENSE NUMBER. |
| (3) NAME OR IDENTIFICATION OF PROJECT. |
| (4) DATE PREPARED. |
| (5) A SPACE FOR THE SIGNATURE AND DATED SEAL. |
| (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING |
| THE DOCUMENT. |
| |
| 2)2004 FL. BLD CODE 1603.1.4 THE |
| FOLLOWING INFORMATION RELATED TO WIND |
| SHALL BE SHOWN ON THE CONSTRUCTION |
| DRAWINGS, |
| 1)- BASIC WIND SPEED, MPH |
| 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| CATEGORY |
| 3)- WIND EXPOSURE |
| 4)- INTERNAL PRESSURE COEFFICIENT, |
| 5)- COMPONENTS & CLADDING, THE DESIGN |
| WIND PRESSURES IN TERMS OF PSF. |
| |
| 3)FL S S 713.13 |
| NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF |
| THE COURT. |
| NOTE: 713.13(2) |
| IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS |
| NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE |
| RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: |
| 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT |
| THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| |
| MYRON JACOBS |
| BUILDING PLAN REVIEWER |