Date |
Text |
2007-03-06 10:14:25 | DENIED |
| REFERENCE: FBC-2004 FUEL GAS: |
| |
| ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL |
| IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS, |
| SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING |
| REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT |
| MADE ON PREVIOUS REVIEWS. |
| |
| ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM |
| PREVIOUS REVIEW WITH A NO, OK OR A NO/OK. |
| THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE |
| PREVIOUS REVIEW NOTES. |
| |
| A NO IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR |
| FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS |
| ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER |
| EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT. |
| |
| AN OK WILL BE LABELED AS SUCH ON THE SAME NUMERICAL |
| COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS. |
| |
| A NO/OK MEANS PART OF THE COMMENT MAY HAVE BEEN |
| ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW |
| COMMENT MAY HAVE BEEN FULLY ADDRESSED. |
| |
| ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF |
| THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH. |
| |
| THE FOLLOWING ARE FROM THE PREVIOUS REVIEW DATED |
| 8/21/06 |
| |
| 1. OK |
| 2. OK |
| 3. OK |
| 4. OK |
| 5. OK |
| 6. OK |
| 7. NO,SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2004 FUEL GAS CODE SEC 402.2 |
| NOTE: PLEASE PROVIDE MANUFACTURER SHEETS FOR THE |
| FOLLOWING. |
| A} MP REGULATOR |
| B} GENERATOR |
| 9. OK, N/A |
| 10. OK, N/A |
| |
| THE FOLLOWING ARE NEW COMMENTS: |
| |
| 11. PLEASE PROVIDE 2 COPIES OF SITE PLAN OR SURVEY AT |
| THE TIME OF PERMIT APPLICATION THAT INCLUDE THE |
| FOLOWING INFORMATION. |
| A} THE CLEARLY MARKED PROPOSED LOCATION FOR THE |
| INSTALLATION OF THE GENERATOR. |
| B} INDICATION OF ALL DIMENTIONS FROM PROPERTY LINES |
| AND DISTANCES FROM ADJACENT DWELLING STRUCTURES. |
| C} INDICATION THAT THE GENERATOR EXHAUST IS NOT |
| INSTALLED CLOSER THAN TEN FEET FROM ANY OPENING INTO |
| THE DWELLING STRUCTURE. THIS INCLCES DOORS, WINDOWS AND |
| ATTIC VENTILATION OPENINGS. |
| |
| 12. PLEASE SUBMIT TWO COPIES OF THE MANUFACTURER'S |
| SPECIFICATIONS/CUT SHEETS FOR GENERATOR, SHOWING |
| LISTINGS FROM A NATIONALLY RECOGNIZED TESTING |
| LABORATORY (NRTL). PLEASE INCLUDE INSTALLATIN |
| INSTRUCTIONS INDICATING CLEARENCES TO DWELLINGS. |
| |
| END OF COMMENTS: |
| |