Plan Review Notes
Plan Review Notes For Permit 06071278
Permit Number 06071278
Review Stop G
Sequence Number 2
Notes
Date Text
2007-03-06 10:14:25DENIED
 REFERENCE: FBC-2004 FUEL GAS:
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS,
 SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING
 REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT
 MADE ON PREVIOUS REVIEWS.
  
 ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW WITH A NO, OK OR A NO/OK.
 THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE
 PREVIOUS REVIEW NOTES.
  
 A NO IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR
 FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS
 ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER
 EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT.
  
 AN OK WILL BE LABELED AS SUCH ON THE SAME NUMERICAL
 COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS.
  
 A NO/OK MEANS PART OF THE COMMENT MAY HAVE BEEN
 ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW
 COMMENT MAY HAVE BEEN FULLY ADDRESSED.
  
 ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF
 THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH.
  
 THE FOLLOWING ARE FROM THE PREVIOUS REVIEW DATED
 8/21/06
  
 1. OK
 2. OK
 3. OK
 4. OK
 5. OK
 6. OK
 7. NO,SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2
 NOTE: PLEASE PROVIDE MANUFACTURER SHEETS FOR THE
 FOLLOWING.
 A} MP REGULATOR
 B} GENERATOR
 9. OK, N/A
 10. OK, N/A
  
 THE FOLLOWING ARE NEW COMMENTS:
  
 11. PLEASE PROVIDE 2 COPIES OF SITE PLAN OR SURVEY AT
 THE TIME OF PERMIT APPLICATION THAT INCLUDE THE
 FOLOWING INFORMATION.
 A} THE CLEARLY MARKED PROPOSED LOCATION FOR THE
 INSTALLATION OF THE GENERATOR.
 B} INDICATION OF ALL DIMENTIONS FROM PROPERTY LINES
 AND DISTANCES FROM ADJACENT DWELLING STRUCTURES.
 C} INDICATION THAT THE GENERATOR EXHAUST IS NOT
 INSTALLED CLOSER THAN TEN FEET FROM ANY OPENING INTO
 THE DWELLING STRUCTURE. THIS INCLCES DOORS, WINDOWS AND
 ATTIC VENTILATION OPENINGS.
  
 12. PLEASE SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS/CUT SHEETS FOR GENERATOR, SHOWING
 LISTINGS FROM A NATIONALLY RECOGNIZED TESTING
 LABORATORY (NRTL). PLEASE INCLUDE INSTALLATIN
 INSTRUCTIONS INDICATING CLEARENCES TO DWELLINGS.
  
 END OF COMMENTS:
  