Plan Review Notes For Permit 06071278 |
Permit Number |
06071278 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2007-01-24 17:32:30 | BUILDING PLAN REVIEW | | PERMIT: | | ADD: | | CONT: | | TEL: (561)###-#### | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2006 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | REVIEW | | ACTION: DENIED | | | | 1)) GENERATOR SLAB & ANCHOR REQUIREMENT | | PLEASE PROVIDE SIZE OF GENERATOR(WXL), | | PLUS PROVIDE PLANS WITH THE INFORMATION | | DEPICTING HOLD DOWN BRACKETS, TYPE OF | | FASTENER, AND THE MINIMUM EDGE DISTANCE | | THE DEVICE REQUIRES WITHOUT LOAD | | REDUCTION. | | SECOND, PROVIDE INFORMATION ON THE | | SLAB, THICKNESS, WIDTH AND LENGTH, IF | | WIREMESH, FIBER MESH OR IF STEEL REBAR | | WILL BEUSED. | | THE NEW SLAB AND HOLD DOWN DETAILS: | | 104.2.1* ALL INFORMATION, DRAWINGS, | | SPECIFICATIONS AND ACCOMPANYING DATA | | SHALL BEAR THE NAME AND SIGNATURE OF THE | | PERSON RESPONSIBLE FOR THE DESIGN. | | | | 2) 2004 FL. BLD CODE 1603.1.4 THE | | FOLLOWING INFORMATION RELATED TO WIND | | SHALL BE SHOWN ON THE CONSTRUCTION | | DRAWINGS, | | 1)- BASIC WIND SPEED, MPH | | 2)- WIND IMPORTANCE FACTOR, & BUILDING | | CATEGORY | | 3)- WIND EXPOSURE | | 4)- INTERNAL PRESSURE COEFFICIENT, | | 5)- COMPONENTS & CLADDING, THE DESIGN | | WIND PRESSURES IN TERMS OF PSF. | | | | MYRON JACOBS | | BUILDING PLAN REVIEWER | | 805-6726 | | | | | | |
|