2006-08-09 00:00:00 | ***** UNSAT **** |
| |
| 1) NOTE: PLEASE SEE THE 2002 NEC. |
| 225.31-225.39, 230.72 |
| PLEASE SEE THAT THIS OFFICE IS UNABLE TO |
| VERIFY THIS AT THIS TIME. |
| |
| 2) NOTE: PLEASE INDICATE ANY AND ALL |
| CONTINUOOUS LOADS AT 125%. |
| 215.3,230.42 ETC. |
| |
| 3) NOTE: PLEASE UPDATE PANEL SCHEDULES |
| AS THE PANELS DID NOT SEEM TO GET ALL |
| THE NEW CIRCUITS. "E". 408.4 |
| 106.1.2 FBC ADMIN SECT |
| |
| 4) NOTE: PLEASE PROVIDE A LAYOUT OF ALL |
| SERVICE EQUIPMENT. PLEASE PROVIDE AN |
| OVERVIEW AS NO ELECTRICAL EQUIPMENT IS |
| SHOWN. CAN NOT VERIFY ITEMS IN NOTE #1 |
| AT THIS TIME. |
| |
| 5) NOTE: PLEASE SUBMIT SPECS/CUT SHEETS |
| FROM THE MANUFACTURE FOR THE ATS. |
| 110.3, 90.8 |
| PLEASE ALSO SUBMIT THE SPECS/SHEETS FOR |
| THE WP HOUSING AS THE GEN DOES NOT SHOW |
| THIS. |
| |
| 6) NOTE: PLEASE CORRLELATE THE OCP FOR |
| THE NEW TRANSFORMER AS THE PANEL SHOWS |
| ONE AND THE RISER SHOWS ANOTHER. |
| 450.3, |
| FBC 106.1.2 |
| |
| 7) NOTE: PLEASE PROVIDE GROUNDING OF THE |
| NEW TRANSFORMER. |
| 250.30,250.20,250.66 ETC |
| |
| 8) NOTE: PLEASE SEE PLANS/DRAWINGS ARE |
| NOT REQUIRED TO BE NOTARIZED, HOWEVER IF |
| THEY ARE THEN THEY NEED TO BE CORRECTLY |
| NOTARIZED AS REQUIRED PERFS 117.05 |
| PLEASE KNOW ONLY A STAMP AND SIGNATURE |
| IS NOT ACCEPTABLE. |
| |
| 9) NOTE: PLEASE SEE EXISTING MDP, IS |
| BEING SHOWN AS MLO. PLEASE CLARIFY AS |
| THIS CONTAINS MANY MORE THAN 6 MEANS OF |
| DISCONNECT. 230.70 |
| PLEASE KNOW, ALL DISCONNECTING MEANS FOR |
| SEC'S AND FEEDERS COMING INTO THE |
| BUILDING SHALL BE GROUPED. |
| |
| 10) NOTE: PLEASE PROVIDE PROPER LEGAL |
| DOCUMENTATION THAT THIS GENERATOR ECT IS |
| BEING PERMITTED ON THIS PROPERTY BY THE |
| PROPERTY OWNER. |
| PLEASE SEE THIS GEN SEEMS TO BE ONLY FOR |
| ONE TENANT SPACEIN THE BUIDLING. |
| |
| 11) NOTE: PLEASE SEE ALL PLANS, DESIGNS |
| AND LOAD CALULATIONS SHALL CONTAIN A |
| STATEMENT" DRAWN BY: PRINTED NAME AND |
| SIGNATURE OF THE PERSON RESPSOSIBLE FOR |
| SAID PLANS AND DESIGNS. |
| FBC 106.1.2 |
| |
| |
| ** UNABLE TO DO A COMPLETE REVIEW AT |
| THIS TIME AS THERE ARE SOME MISSING |
| ITEMS NEEDED. |
| PLEASE BE SURE TO GO OVER PLANS AND |
| RISER BEFORE RESUBMITTING. |
| |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |