Plan Review Notes For Permit 06071278
Permit Number 06071278
Review Stop E
Sequence Number 1
Notes
Date Text
2006-08-09 00:00:00***** UNSAT ****
  
 1) NOTE: PLEASE SEE THE 2002 NEC.
 225.31-225.39, 230.72
 PLEASE SEE THAT THIS OFFICE IS UNABLE TO
 VERIFY THIS AT THIS TIME.
  
 2) NOTE: PLEASE INDICATE ANY AND ALL
 CONTINUOOUS LOADS AT 125%.
 215.3,230.42 ETC.
  
 3) NOTE: PLEASE UPDATE PANEL SCHEDULES
 AS THE PANELS DID NOT SEEM TO GET ALL
 THE NEW CIRCUITS. "E". 408.4
 106.1.2 FBC ADMIN SECT
  
 4) NOTE: PLEASE PROVIDE A LAYOUT OF ALL
 SERVICE EQUIPMENT. PLEASE PROVIDE AN
 OVERVIEW AS NO ELECTRICAL EQUIPMENT IS
 SHOWN. CAN NOT VERIFY ITEMS IN NOTE #1
 AT THIS TIME.
  
 5) NOTE: PLEASE SUBMIT SPECS/CUT SHEETS
 FROM THE MANUFACTURE FOR THE ATS.
 110.3, 90.8
 PLEASE ALSO SUBMIT THE SPECS/SHEETS FOR
 THE WP HOUSING AS THE GEN DOES NOT SHOW
 THIS.
  
 6) NOTE: PLEASE CORRLELATE THE OCP FOR
 THE NEW TRANSFORMER AS THE PANEL SHOWS
 ONE AND THE RISER SHOWS ANOTHER.
 450.3,
 FBC 106.1.2
  
 7) NOTE: PLEASE PROVIDE GROUNDING OF THE
 NEW TRANSFORMER.
 250.30,250.20,250.66 ETC
  
 8) NOTE: PLEASE SEE PLANS/DRAWINGS ARE
 NOT REQUIRED TO BE NOTARIZED, HOWEVER IF
 THEY ARE THEN THEY NEED TO BE CORRECTLY
 NOTARIZED AS REQUIRED PERFS 117.05
 PLEASE KNOW ONLY A STAMP AND SIGNATURE
 IS NOT ACCEPTABLE.
  
 9) NOTE: PLEASE SEE EXISTING MDP, IS
 BEING SHOWN AS MLO. PLEASE CLARIFY AS
 THIS CONTAINS MANY MORE THAN 6 MEANS OF
 DISCONNECT. 230.70
 PLEASE KNOW, ALL DISCONNECTING MEANS FOR
 SEC'S AND FEEDERS COMING INTO THE
 BUILDING SHALL BE GROUPED.
  
 10) NOTE: PLEASE PROVIDE PROPER LEGAL
 DOCUMENTATION THAT THIS GENERATOR ECT IS
 BEING PERMITTED ON THIS PROPERTY BY THE
 PROPERTY OWNER.
 PLEASE SEE THIS GEN SEEMS TO BE ONLY FOR
 ONE TENANT SPACEIN THE BUIDLING.
  
 11) NOTE: PLEASE SEE ALL PLANS, DESIGNS
 AND LOAD CALULATIONS SHALL CONTAIN A
 STATEMENT" DRAWN BY: PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPSOSIBLE FOR
 SAID PLANS AND DESIGNS.
 FBC 106.1.2
  
  
 ** UNABLE TO DO A COMPLETE REVIEW AT
 THIS TIME AS THERE ARE SOME MISSING
 ITEMS NEEDED.
 PLEASE BE SURE TO GO OVER PLANS AND
 RISER BEFORE RESUBMITTING.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]