Plan Review Notes
Plan Review Notes For Permit 06071246
Permit Number 06071246
Review Stop E
Sequence Number 2
Notes
Date Text
2006-11-22 13:16:44***** UNSAT 2ND REVIEW *******
  
  
 ** PLEASE SEE SOME NOTES FROM THE PREVIOUS REVIEW AND
 SOME NEW NOTES BASED ON NEW PLANS SUBMITTED ARE IN NEED
 OF ADDRESSING.
  
  
 1) NOTE: PLEASE SEE MISSING FIRM LICENSE NUMBER FROM
 THE TITLE BLOCKS AS REQUIRED PER FLORIDA ADMINISTRATIVE
 CODE 61G15-23.002 AND FLORIDA STATUTES 471.023.
 PLEASE SEE THIS IS ALSO KNOWN AS THE CERTIFICATE OF
 AUTHORIZATION NUMBER OR THE ENGINEERING BUSINESS
 LICENSE #.
  
 2) NOTE: PLEASE SHOW MINIMUM EGRESS LIGHTING CONTROL
 AND FIXTURE(S) REQUIRED AT EGRESS DOOR TO REAR OF
 DWELLING.
 210.70, LS101 7.8
  
 3) NOTE: PLEASE SEE MISSING THE REQUIRED DISCONNECTS
 FOR THE AHU AND THE WH UNIT. 422.31, 440.11.
 PLEASE INDICATE ON PLANS.
  
 4) NOTE: PLEASE SEE AS NEW PANEL SCHEDULE IS PROVIDED,
 PLEASE CLARIFY THE PANEL BEING SHOWN AS 150A BUS, AND
 150A MLO, YET THE LOAD CALCULATIONS MENTIONS A 125A
 BREAKER FOR MAIN. IS THIS A MAIN DISCONNECT AT THE
 SERVICE LOCATION WHICH FEEDS THIS PANEL?
 PLEASE SHOW THE LOCATION OF THE PANEL AS THIS IS NOT
 SHOWN ON PLANS.
 PLEASE VERIFY AND SHOW. 110.26, 408.7, 240.24
 FBC106.1.2.
  
 5) NOTE: PLEASE SEE PLANS SHALL BE SPECIFIC IN DESIGN
 FOR THE CURRENT CODE ADOPTED BY THE STATE OF FLORIDA.
 PLEASE SEE WE ARE UNDER THE 2004 FBC, 2002 NFPA-70,
 2002 NFPA-72, THESE ARE REQUIRED FOR ELECTRICAL AT A
 MIN.
 MAY NOT STATE THE "LATEST" AS THOSE CODES WHICH ARE OUT
 ARE NOT YET ADOPTED.
  
 6) NOTE: PLEASE SEE NOC SUBMITTED IS NOT COMPLETE.
 PLEASE SEE FS 713.13 AS A RECORDED NOC IS REQUIRED
 BEFORE PICKING UP PERMIT. THIS IS NOT REQUIRED WHEN
 SUBMITTING PLANS, HOWEVER MAY BE.
 PLEASE SEE THE NOC IN PACKAGE IS NOT RECORDED AS
 REQUIRED.
 PLEASE SEE WE HAVE ATTACHED A SIMPLE ONE PAGE NOC WHICH
 SHOULD BE USED IN LIEU OF THE TWO PAGES SUBMITTED.
 PLEASE SEE FS 117.05
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 **PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW.
  
 **IF THERE ARE ANY QUESTIONS, COMMENTSOR IF ANY OF
 THE NOTES TYPEDWHICH ARE UNCLEAR IN ANY WAY, PLEASE
 DO NOT HESITATEIN CONTACTING THIS REVIEWER.
  
  
  
  