2006-11-22 13:16:44 | ***** UNSAT 2ND REVIEW ******* |
| |
| |
| ** PLEASE SEE SOME NOTES FROM THE PREVIOUS REVIEW AND |
| SOME NEW NOTES BASED ON NEW PLANS SUBMITTED ARE IN NEED |
| OF ADDRESSING. |
| |
| |
| 1) NOTE: PLEASE SEE MISSING FIRM LICENSE NUMBER FROM |
| THE TITLE BLOCKS AS REQUIRED PER FLORIDA ADMINISTRATIVE |
| CODE 61G15-23.002 AND FLORIDA STATUTES 471.023. |
| PLEASE SEE THIS IS ALSO KNOWN AS THE CERTIFICATE OF |
| AUTHORIZATION NUMBER OR THE ENGINEERING BUSINESS |
| LICENSE #. |
| |
| 2) NOTE: PLEASE SHOW MINIMUM EGRESS LIGHTING CONTROL |
| AND FIXTURE(S) REQUIRED AT EGRESS DOOR TO REAR OF |
| DWELLING. |
| 210.70, LS101 7.8 |
| |
| 3) NOTE: PLEASE SEE MISSING THE REQUIRED DISCONNECTS |
| FOR THE AHU AND THE WH UNIT. 422.31, 440.11. |
| PLEASE INDICATE ON PLANS. |
| |
| 4) NOTE: PLEASE SEE AS NEW PANEL SCHEDULE IS PROVIDED, |
| PLEASE CLARIFY THE PANEL BEING SHOWN AS 150A BUS, AND |
| 150A MLO, YET THE LOAD CALCULATIONS MENTIONS A 125A |
| BREAKER FOR MAIN. IS THIS A MAIN DISCONNECT AT THE |
| SERVICE LOCATION WHICH FEEDS THIS PANEL? |
| PLEASE SHOW THE LOCATION OF THE PANEL AS THIS IS NOT |
| SHOWN ON PLANS. |
| PLEASE VERIFY AND SHOW. 110.26, 408.7, 240.24 |
| FBC106.1.2. |
| |
| 5) NOTE: PLEASE SEE PLANS SHALL BE SPECIFIC IN DESIGN |
| FOR THE CURRENT CODE ADOPTED BY THE STATE OF FLORIDA. |
| PLEASE SEE WE ARE UNDER THE 2004 FBC, 2002 NFPA-70, |
| 2002 NFPA-72, THESE ARE REQUIRED FOR ELECTRICAL AT A |
| MIN. |
| MAY NOT STATE THE "LATEST" AS THOSE CODES WHICH ARE OUT |
| ARE NOT YET ADOPTED. |
| |
| 6) NOTE: PLEASE SEE NOC SUBMITTED IS NOT COMPLETE. |
| PLEASE SEE FS 713.13 AS A RECORDED NOC IS REQUIRED |
| BEFORE PICKING UP PERMIT. THIS IS NOT REQUIRED WHEN |
| SUBMITTING PLANS, HOWEVER MAY BE. |
| PLEASE SEE THE NOC IN PACKAGE IS NOT RECORDED AS |
| REQUIRED. |
| PLEASE SEE WE HAVE ATTACHED A SIMPLE ONE PAGE NOC WHICH |
| SHOULD BE USED IN LIEU OF THE TWO PAGES SUBMITTED. |
| PLEASE SEE FS 117.05 |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| **PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. |
| |
| **IF THERE ARE ANY QUESTIONS, COMMENTSOR IF ANY OF |
| THE NOTES TYPEDWHICH ARE UNCLEAR IN ANY WAY, PLEASE |
| DO NOT HESITATEIN CONTACTING THIS REVIEWER. |
| |
| |
| |
| |