Plan Review Notes For Permit 06071230 |
Permit Number |
06071230 |
|
Review Stop |
E |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2007-05-03 16:12:37 | ****5/3/07*** | | | | | | NEW SHEETS BROUGHT IN BY ENGINEER. | | NEW APC SHEETS ATTACHED TO PLANS AS E-MAILED. ALL | | EQUIPMENT ON LOAD SIDE OF POWERE PANEL IS UNDER UL FILE | | # AND SHALL BE INSTALLED PER LISTING. | | OWES FEES FOR 4X FEE FOR ORIGINAL SCOPE OF WORK WHIHC | | COMMENCED WITHOUT PERMITS. | 2007-04-13 15:29:35 | ** UNSAT ** | | | | *** PROJECT IS CURRENTLY ON HOLD.THE OTHER TRADES MAY | | REVIEW. | | | | | | 1) NOTE: *INFORMATION AS REQUESTED IN MEETING FOR | | LISTED ASSEMBLY OF EQUIPMENT COULD NOT BE LCOATED IN | | PACKAGE. THE DOCUMENTATION DOES NOT INDICATE LISTING OR | | SHOW DETAILS FOR CODE COMPLIANCE , INFACT, NOTES ON | | SHEETS MENTIONS THAT INSTALLATION FOR WIRING WHICH IS | | NOT PART FO THE EQUIPMENT SHALL MEET NATIONAL | | ELECTRICAL CODE. | | | | | | 2) NOTE: * ALSO AN ON-SITE MEETING IS NOW SCHEDULED FOR | | TUESDAY 10:30AM THE 17TH OF APRIL TO GO OVER WORK WHICH | | WAS COMMENCED AND DONE W/OUT PERMIT FOR A CORRECT | | VALUATION OF WORK. CONTRACTOR COULD NOT PROVIDE THE | | VALUE FOR WORK DONE. | | | | 3) NOTE:* CALLED ENGINEER AND LEFT MESSAGE FORFOR | | NOTE NUMBER ONE ABOVE AND TO MEET ON-SITE. |
|