Plan Review Notes For Permit 06071230 |
Permit Number |
06071230 |
|
Review Stop |
E |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2007-02-13 08:53:07 | *** UNSAT *** | | | | | | 1) NOTE: PLANS ARE CURRENTLY TO FAILED STATUS AS SCOPE | | OF WORK AT SITE IS TO BE VERIFIED. THE PLANS CALLS FOR | | SOME AS EXISTING EQUIPMENT FOR UPS ETC , HOWEVER THIS | | SCOPE OF WORK WAS NOT PERMITTED AND IF THIS IS NEW | | EQUIPMENT THEN THE MANUFACTURES SPECS/CUT SHEETS ARE | | NEEDED. | | MUST SHOW AL LISTINGS FROM NRTL. 110.3, 90.7 | | PLEASE KNOW A FIELD INSPECTION WILL BE REQUIRED PRIOR | | TO REVIEW STATUS CHANGE. THE EXISTING ROOMS WHICH WERE | | BEING MADE PART OF THE EXISTING COMPUTER ROOM DID NOT | | CONTAIN ELECTRICAL UPS SYSTEMS ON PREVIOUS PLANS, NOW | | PLANS CALLS FOR THESE AS EXISTING. | | PLEASE SEE ELECTRICAL SHEET WHICH ALSO MENTIONS THIS | | EQUIPMENT AS BEING RELOCATED. | | | | | | ** CALLED CONTRACTOR AND LEFT MESSAGE** | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|