Plan Review Notes
Plan Review Notes For Permit 06071230
Permit Number 06071230
Review Stop E
Sequence Number 3
Notes
Date Text
2007-02-13 08:53:07*** UNSAT ***
  
  
 1) NOTE: PLANS ARE CURRENTLY TO FAILED STATUS AS SCOPE
 OF WORK AT SITE IS TO BE VERIFIED. THE PLANS CALLS FOR
 SOME AS EXISTING EQUIPMENT FOR UPS ETC , HOWEVER THIS
 SCOPE OF WORK WAS NOT PERMITTED AND IF THIS IS NEW
 EQUIPMENT THEN THE MANUFACTURES SPECS/CUT SHEETS ARE
 NEEDED.
 MUST SHOW AL LISTINGS FROM NRTL. 110.3, 90.7
 PLEASE KNOW A FIELD INSPECTION WILL BE REQUIRED PRIOR
 TO REVIEW STATUS CHANGE. THE EXISTING ROOMS WHICH WERE
 BEING MADE PART OF THE EXISTING COMPUTER ROOM DID NOT
 CONTAIN ELECTRICAL UPS SYSTEMS ON PREVIOUS PLANS, NOW
 PLANS CALLS FOR THESE AS EXISTING.
 PLEASE SEE ELECTRICAL SHEET WHICH ALSO MENTIONS THIS
 EQUIPMENT AS BEING RELOCATED.
  
  
 ** CALLED CONTRACTOR AND LEFT MESSAGE**
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  