Plan Review Notes
Plan Review Notes For Permit 06071230
Permit Number 06071230
Review Stop M
Sequence Number 2
Notes
Date Text
2007-01-08 12:10:29*** DENIED ***
 1) PLEASE PROVIDE A DETAIL ON THE PLANS SHOWING HOW THE
 CONDENSER UNIT STAND IS TO BE MOUNTED TO THE ROOF TO
 WITH STAND140 MPH WIND LOADS, PER 2004 FBC 1609.
 AND HOW THE CONDENSER UNIT IS TO BE SECURED TO THE
 STAND.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.