Plan Review Notes
Plan Review Notes For Permit 06071230
Permit Number 06071230
Review Stop E
Sequence Number 2
Notes
Date Text
2007-01-05 18:33:40** UNSAT **
  
  
 1) NOTE: PLEASE SEE PLANS SHALL BEAR THE CORRECT
 ADDRESS ON TITLE BLOCKS.
 PLEASE SEE THE PERMIT APPLICATION AND THE ADDRESS IN
 OUR SYSTEM APPLIED TO IS 205 N. DIXIE.
 FAC 61G1-16.004, 61G15-23.002
  
 2) NOTE: PLEASE SEE PLANS SHALL REFERENCE ALL CODES
 WHICH ARE CURRENTLY RELEVANT TO THE DESIGN OF SAID
 PLANS AND WHICH SHALL ALSO BE STATED ON PLANS. PLEASE
 BE SURE TO SEE ALL OF THESE NEW SECTIONS WHICH ARE
 RELEVANT TO THE DESIGNS FOR THE SCOPE OF WORK BEING
 SHOWN AND PROPOSED.
 PLEASE ALSO SEE THAT THE FOLLOWING SHALL BE STATED ON
 THE PLANS AT A MINIMUM.
 2004 FBC W/2006 REVISIONS.
 2002 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
 2003 NFPA-75
  
 ** SIDE NOTE, AS OF 12/8/06 THE STATE OF FLORIDA HAS
 ADOPTED THE 2005 NFPA-70 (NEC) AND THE 2006 REVISIONS
 TO THE 2004 FBC. THIS IS GIVEN FOR INFORMATION ONLY.
 ALL PERMIT APPLICATIONS ON 12/8/06 OR LATER SHALL BE
 UNDER THE NEW CODES.
  
 3) NOTE: PLEASE SEE THE VALUE FOR THE COMPLETE SCOPE OF
 WORK SHALL INCLUDE ALL LABOR AND MATERIALS. PLEASE ALSO
 SEE BUILDING REVIEW COMMENTS AS BASED ON THE SCOPE OF
 WORK SHOWN THE APPLIED VALUE IS LOW. PLEASE SEE THE
 VALUE HAS NOT CHANGED, HOWEVER THE SCOPE OF WORK HAS
 SUBSTANTIALLY INCREASED EVEN WITHOUT THE EQUIPMENT
 BEING INSTALLED.
 FBC 108.3
  
 4) NOTE: PLEASE SHOW AND INDICATE THE ACTUAL ATTACHMENT
 FOR THE GROUNDING OF THE TRANSFORMER PER 250.30,
 250.20. QUOTING GROUNDING "PER NEC 250" IS NOT
 PERMITTED. PLEASE SUBMIT DETAIL IN LIEU OF QUOTING THE
 CODE(S).
 FBC 106.1.2 ADMIN SECTION.
  
 5) NOTE: PLEASE SEE PANEL ON PLANS MENTIONS "EXISTING
 IT PANEL" YET THIS IS NOT POSSIBLE AS THIS PANEL WAS
 NOT LOCATED IN THE OLD COMPUTER ROOM. PLEASE CLARIFY
 THIS ON PLANS.
 FBC 106.1.2.
  
 6) NOTE: PLEASE SEE 450.3 FOR THE MAXIMUM OVER CURRENT
 PROTECTION PERMITTED ON THE TRANSFORMER AS SHOWN. (125%
 MAX).
  
  
 7) NOTE: PLEASE PROVIDE CALCULATIONS ON NEUTRAL
 CONDUCTORS FOR ALL NON-LINEAR CIRCUITS. PLEASE SEE ALL
 CIRCUITS WHICH CONTAIN THESE LOADS SHALL MEET THE
 SIZING REQUIREMENTS TO HANDLE AND ALLEVIATE THE OVER
 LOADING OF THE NEUTRAL ON A 3-PHASE 4-WIRE SYSTEM WITH
 PREDOMINATELY OR ACTUALLY IN MANY CASES ALL NON-LINEAR
 LOADS. PLEASE SEE THIS CAN BE DONE BY USING MANY
 METHODS, K-RATED TRANSFORMERS, FULL NEUTRAL LOAD
 CALCULATION ON EACH CIRCUIT AND FEEDERS BASED ON ALL
 NON-LINEAR LOADS OR THE SIZING OF THE NEUTRAL(S) AT
 200%.
 PLEASE SEE THE RISK OF FIRE, LIFE SAFETY AND CAUSE TO
 PROPERTY DAMAGE CAN BE SUBSTANTIAL AND IT IS THE
 CONCERN OF THE OFFICE BASED ON OUR INFORMATION KNOWN
 AND PLEASE SEE STUDIES IN WHITE PAPERS FROM NUMEROUS
 MANUFACTURES OF ELECTRONIC/COMPUTER EQUIPMENT WHICH
 INDICATE AS MUCH AS 1.7 TIMES THE RATED LOAD OF THE
 CONDUCTOR OR CIRCUIT AND FEEDERS.
 PLEASE SEE THE FOLLOWING CODES: THIS OFFICE IS AWARE OF
 WHAT A FPN MEANS, HOWEVER SEE SOME SECTIONS GIVEN WHICH
 DO NOT CONTAIN FPN.PLEASE SEE 210.4A (FPN), 220.22
 (FPN(2), 310.10, 310.15B4(C), 400.5, 520.44, 408.16,
 AND FBC 104.6ADMINISTRATIVE SECTION AS ADOPTED BY THE
 CITY OF WEST PALM BEACH.
 PLEASE PROVIDE MORE INFORMATION ON WHAT STEPS WILL BE
 TAKEN TO ALLEVIATE THESES RISKS.
  
 8) NOTE: PLEASE SEE PANEL "HA", THE AIC RATING AS SHOWN
 IS BEING SHOWN AT 35K WHICH IS OK; HOWEVER IS THIS FOR
 ALL BRANCH BREAKERS?
 110.9,
 FBC 106.1.2 ADMIN SECTION
  
 9) NOTE: PLEASE SHOW/ INDICATE ANY AND ALL SMOKE
 DETECTION DEVICES ON PLANS (SHOWN) AND NOTE FOR BEING
 CONNECTED. SEPARATE PERMIT PLANS.
 PLEASE SEE FBC 11-4.28.2, .3(4) FOR ANY HORN AND STROBE
 DEVICES. PLEASE BE SURE THESE STATE THE MINIMUM
 LEVELS.
 75CD FOR STROBES.
  
 10) NOTE: PLESE ADJUST THE PERMIT APPLICATION FOR SCOPE
 OF WORK.
  
 ** PLEASE KNOW, PLANS PERMIT APPLICATION, MANUFACTURE
 SPECS/CUT SHEETS WILL BE REQUIRED FOR THE FUTURE
 EQUIPMENT FOR THE ROOM.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]