Plan Review Notes
Plan Review Notes For Permit 06071230
Permit Number 06071230
Review Stop E
Sequence Number 1
Notes
Date Text
2006-08-05 00:00:00*** UNSAT ***
  
 1) NOTE: PLEASE PROVIDE MORE DETAIL ON
 ELECTRICAL PLANS. PLEASE SEE PLANS SHOWS
 ON PANEL BEING MOVED, YET SHOWS THREE
 PANELS?
 PLEASE PROVIDE CIRCUITING AND CORRELATE
 WITH MINIMUM PANEL SCHEDULE(S) TO BE
 SUBMITTED.
 PLEASE SEE NEC 645 AND NFPA-75 FOR
 REQUIREMENTS OF IT ROOM.
 PLEASE SEE MISSING DISCONNECTING MEANS,
 GROUNDING SHUT OFF'S, FOR A/C EQUIPMENT
 AND ALL ELECTRICAL.
 IF A/C SYSTEM ARE DUCTED IN, PLEASE BE
 SURE TO PROVIDE FIRE DAMPERS AS
 REQUIRED.(MAY BE PART OF MECH REVIEW)
 PLEASE SEE BLDG REVIEW COMMENTS FOR MIN
 RATINGS OF ALL WALLS TO BE CLARIFIED.
  
 ** PLANS ARE NOT CLEAR AT THIS TIME FOR
 ALL MIN REQUIRMENTS PER ABOVE.
  
 408.4,240.4,240.24,408.7,110.26 ETC
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  