Plan Review Notes For Permit 06071230 |
Permit Number |
06071230 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-08-05 00:00:00 | *** UNSAT *** | | | | 1) NOTE: PLEASE PROVIDE MORE DETAIL ON | | ELECTRICAL PLANS. PLEASE SEE PLANS SHOWS | | ON PANEL BEING MOVED, YET SHOWS THREE | | PANELS? | | PLEASE PROVIDE CIRCUITING AND CORRELATE | | WITH MINIMUM PANEL SCHEDULE(S) TO BE | | SUBMITTED. | | PLEASE SEE NEC 645 AND NFPA-75 FOR | | REQUIREMENTS OF IT ROOM. | | PLEASE SEE MISSING DISCONNECTING MEANS, | | GROUNDING SHUT OFF'S, FOR A/C EQUIPMENT | | AND ALL ELECTRICAL. | | IF A/C SYSTEM ARE DUCTED IN, PLEASE BE | | SURE TO PROVIDE FIRE DAMPERS AS | | REQUIRED.(MAY BE PART OF MECH REVIEW) | | PLEASE SEE BLDG REVIEW COMMENTS FOR MIN | | RATINGS OF ALL WALLS TO BE CLARIFIED. | | | | ** PLANS ARE NOT CLEAR AT THIS TIME FOR | | ALL MIN REQUIRMENTS PER ABOVE. | | | | 408.4,240.4,240.24,408.7,110.26 ETC | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] | | | | | | |
|