Plan Review Notes
Plan Review Notes For Permit 06071193
Permit Number 06071193
Review Stop P
Sequence Number 1
Notes
Date Text
2006-08-21 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FBC-2004 EXISTING BLDG.
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. REMODEL IS A CHANGE OF OCCUPANCY. AS
 SUCH ALL PROVISIONS SHALL BE COMPLIED
 WITH FOR THE NEW OCCUPANCY. SECTION
 810.1.
  
 2. PLANS SHALL BE DESIGNED BY A DESIGN
 PROFESSIONAL. FS481.229(C) AND SHALL BE
 SIGNED, SEALED, DATED AND HAVE A TITLE
 BLOCK WITH ALL REQUIRED INFORMATION. FAC
 61G1-23.004 & FS481.2055.
  
 3. PER TABLE 403.1 A DRINKING FOUNTAIN
 IS REQUIRED. PLEASE SHOW CONNECTION TO
 SANITARY RISER DIAGRAM AND THE WATER
 RISER DIAGRAM THAT REFLECTS THE FLOOR
 PLAN. SECTION 106.3.5.1.3. SHOW ALL PIPE
 SIZES, TRAPS, VENTS, ON SANT. AND ALL
 PIPE SIZES, VALVES, ETC. ON WATER. -
 SUBMIT A DETAIL FOR THE DRINKING
 FOUNTAIN SHOWING COMPLIANCE WITH 11-4.15
 AND ALL SUBSECTIONS AS WELL AS
 11-4..3(10)(A) PROVISIONS FOR THOSE WHO
 HAVE DIFFICULTY BENDING OR STOOPING.
  
 4. GENERAL PROJECT NOTES INDICATE AN
 EXISTING RESIDENCE. AS A RESIDENCE, A
 KITCHEN SINK IS REQUIRED. PLEASE
 INDICATE THE LOCATION OF THE SINK AS IT
 IS NOT SHOWN ON THE EXISTING FLOOR PLAN.
 IF THE SINK IS TO BE RETAINED, IT SHALL
 COMPLY WITH SECTION 11-4.24 AND ALL
 SUBSECTIONS. ALSO REQUIRED IN A
 RESIDENCE IS A WASH MACHINE HOOK UP FOR
 WATER AND SANIT. DWV. THIS IS NOT SHOWN
 ON THE EXISTING FLOOR PLAN. PLEASE
 SUBMIT A FLOOR PLAN THAT SHOWS THE
 EXISTING FLOOR PLAN WITH ALL FIXTURES,
 EXISTING BEDROOMS, EXISTING KITCHEN ETC.
 SECTION 106.1.1.
  
 5. IF TOILET ROOMS ARE PROVIDED, THEN
 EACH PUBLIC AND COMMON USE TOILET ROOM
 SHALL COMPLY WITH SECTION 11-4.22.
 SUBMIT A DETAIL SHOWING COMPLIANCE WITH
 SECTIONS 11-4.16, 11-4.19, & 11-4.22
 WITH ALL SUBSECTIONS.
  
 6. AN RPZV BACKFLOW IS REQUIRED ON THE
 WATER SERVICE TO THE BUILDING. SECTION
 608. INDICATE ON PLANS.
  
 7. THERMAL EXPANSION CONTROL IS REQUIRED
 PER SECTION 607.3.2.
  
 8. INDICATE THE SQUARE FOOTAGE OF THE
 FLOOR PLAN TO CHECK MINIMUM FACILITIES
 REQUIRED PER TABLES 1004.1.2 & 403.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved