2006-08-10 00:00:00 | ****UNSAT **** |
| |
| 1) NOTE: PLEASE SEE THAT PLANS REFLECT |
| ALL OF THE FOLLOWING CODES AT A MINIMUM. |
| 2004 FBC, 2002 NFPA-70, 2002 NFPA-72, |
| 2003 NFPA-101 |
| |
| 2) NOTE: PLEASE SUBMIT PLANS WHICH ARE |
| DONE BY A MINIMUM OF AN ARCHITECT, |
| SIGNED, DATED AND SEALED BY SAID |
| PROFESSIONAL. PLEASE ALSO BE SURE ALL |
| TITLE BLOCK INFORMATION IS ON SAID |
| PLANS. |
| FS 481.229, 481.221, 471.025 |
| FAC 61G15-23.002, 61G1-16.004. |
| |
| 3) NOTE: PLEASE SSUBMIT ELECTRICAL PLANS |
| IN COMPLIANCE WITH THE 2002 NEC. |
| PLEASE SEE PLANS FOR SERVICE DO NOT |
| CORRELATE, PLEASE SEE LOAD CALCULATIONS |
| ARE NOT CORRECT AND THERE ARE MANY ITEMS |
| MISSING. |
| PLEASE SEE 2002 NEC, |
| 220.3,220.10,220.11,220.13, ETC, 215.5, |
| 215.3, 230.42, ETC |
| |
| 4) NOTE: PLEASE SEE MISSING EXIT AND |
| EMERGENCY LTS REQUIRED. |
| PLEASE ALSO SEE FIRE REVIEW COMMENTS. |
| PLEASE SEE NFPA-101 2003 7.8.1.3, |
| 7.9.2.2 AS THE MIN FT CANDLES REQUIRE |
| UNDER NORMAL LIGHTING LEVELS ON THE |
| STAIRS AND THE MIN LEVELS REQUIRED UNDER |
| EM PWR(BATTERY BACK UP). |
| PLEASE ALSO SEE ANY OPENING LEADING TO |
| DIRECT GRADE LEVEL ACCESS SHALL ALSO |
| CONTAIN CONTROL FOR EGRESS LTS. |
| |
| ** PLEASE SEE COMMENTS FROM OTHER TRADES |
| WHICH AMY HAVE AN AFFECT ON ELECTRICAL |
| PLANS. |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CONSTUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
| |
| |
| |
| |
| |
2006-07-23 00:00:00 | *** THIS IS NOT RESIDENTIAL. THIS IS A |
| CHANGE IN OCCUPANCY AND PLANS ARE BEING |
| ROUTED BACK TOINCOMING. |
| PERMIT TYPE HAS BEEN CHANGED IN COMPUTER |
| AND FEES ADDED FOR FIRE REVIEW. |