Plan Review Notes
Plan Review Notes For Permit 06071193
Permit Number 06071193
Review Stop E
Sequence Number 1
Notes
Date Text
2006-08-10 00:00:00****UNSAT ****
  
 1) NOTE: PLEASE SEE THAT PLANS REFLECT
 ALL OF THE FOLLOWING CODES AT A MINIMUM.
 2004 FBC, 2002 NFPA-70, 2002 NFPA-72,
 2003 NFPA-101
  
 2) NOTE: PLEASE SUBMIT PLANS WHICH ARE
 DONE BY A MINIMUM OF AN ARCHITECT,
 SIGNED, DATED AND SEALED BY SAID
 PROFESSIONAL. PLEASE ALSO BE SURE ALL
 TITLE BLOCK INFORMATION IS ON SAID
 PLANS.
 FS 481.229, 481.221, 471.025
 FAC 61G15-23.002, 61G1-16.004.
  
 3) NOTE: PLEASE SSUBMIT ELECTRICAL PLANS
 IN COMPLIANCE WITH THE 2002 NEC.
 PLEASE SEE PLANS FOR SERVICE DO NOT
 CORRELATE, PLEASE SEE LOAD CALCULATIONS
 ARE NOT CORRECT AND THERE ARE MANY ITEMS
 MISSING.
 PLEASE SEE 2002 NEC,
 220.3,220.10,220.11,220.13, ETC, 215.5,
 215.3, 230.42, ETC
  
 4) NOTE: PLEASE SEE MISSING EXIT AND
 EMERGENCY LTS REQUIRED.
 PLEASE ALSO SEE FIRE REVIEW COMMENTS.
 PLEASE SEE NFPA-101 2003 7.8.1.3,
 7.9.2.2 AS THE MIN FT CANDLES REQUIRE
 UNDER NORMAL LIGHTING LEVELS ON THE
 STAIRS AND THE MIN LEVELS REQUIRED UNDER
 EM PWR(BATTERY BACK UP).
 PLEASE ALSO SEE ANY OPENING LEADING TO
 DIRECT GRADE LEVEL ACCESS SHALL ALSO
 CONTAIN CONTROL FOR EGRESS LTS.
  
 ** PLEASE SEE COMMENTS FROM OTHER TRADES
 WHICH AMY HAVE AN AFFECT ON ELECTRICAL
 PLANS.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  
  
2006-07-23 00:00:00*** THIS IS NOT RESIDENTIAL. THIS IS A
 CHANGE IN OCCUPANCY AND PLANS ARE BEING
 ROUTED BACK TOINCOMING.
 PERMIT TYPE HAS BEEN CHANGED IN COMPUTER
 AND FEES ADDED FOR FIRE REVIEW.


Account Summary | Usage Policy | Privacy Policy