Plan Review Notes
Plan Review Notes For Permit 06071193
Permit Number 06071193
Review Stop B
Sequence Number 1
Notes
Date Text
2006-08-16 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 BUILDING
 FBC RFLORIDA BUILDING CODE 2004
 RESIDENTIAL
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED, FS713.13.A NEW
 NOC WILL BE REQUIRED FOR THE NEW
 CONTRACTOR.
  
 2.)THE CONTRACTOR HAS CARPENTRY
 CONTRACTOR AND A WINDOW AND DOOR
 CONTRACTOR LICENSES.THE SCOPE OF WORK
 FOR THIS PROJECT EXCEEDS THE SCOPE OF
 THESE LICENSES (DRYWALL, PAINT, MASONRY,
 CONCRETE, ETC.).SEE ATTACHED FOR WORK
 ALLOWED UNDER THESE LICENSES.
  
 3.)WHEN APPLYING FOR PERMITS, ONLY
 REFER TO ONE LICENSE NUMBER.IF THE
 SCOPE OF WORK INCLUDES BOTH LICENSES,
 TWO PERMIT APPLICATIONS SHOULD BE
 COMPLETED WITH TWO DIFFERENT PERMIT
 NUMBERS GENERATED.
  
 4.)A WINDOW AND DOOR PERMIT HAS BEEN
 ISSUED FOR THIS ADDRESS.THE PLANS SHOW
 THE WINDOWS AND DOORS AS EXISTING.NOTE
 THAT AS THE CONTRACTOR DID NOT ADVISE
 THAT THERE WAS TO BE A CHANGE OF
 OCCUPANCY, THE CONTRACTOR IS PROCEEDING
 AT HIS OR HER OWN RISK AS THAT PLAN WAS
 NOT REVIEWED FOR ACCESSIBILITY, TABLE
 602, AND EGRESS REQUIREMENTS.
  
 5.)THE PLANS STATE THAT THIS IS A
 REMODEL MODIFICATION OF AN EXISTING
 RESIDENCE TO DR. SCHWARZ PSYCHIATRY
 FUNCTION.THIS IS A CHANGE OF
 OCCUPANCY, FROM R3 TO BUSINESS.REMOVE
 ALL REFERENCES TO RESIDENCES AND
 RESIDENTIAL CODE FROM THE PLAN AS THEY
 DO NOT APPLY TO THIS JOB.CHANGE OF
 OCCUPANCY IS TO COMPLY WITH ALL
 REQUIREMENTS OF FLORIDA BUILDING CODE
 2004 EXISTING BUILDING CODE, CHAPTERS 5
 THROUGH 8 AND FLORIDA BUILDING CODE
 2004, BUILDING, 11-4.1.6.
  
 6.)MANY OF THE NOTES ON THE SITE PLAN
 DO NOT APPLY TO THIS JOB.REMOVE FROM
 THE PLAN.
  
 7.)PROVIDE A CODE SUMMARY OF THE
 EXISTING BUILDING; BUILDING HEIGHT,
 CONSTRUCTION TYPE INCLUDING A OR B FBC
 6, FIRE SPRINKLER INFORMATION, GOVERNING
 CODE INCLUDING FBC EB, OCCUPANCY FBC3.
  
  
 8.)PROVIDE AREA CALCULATIONS FOR THE
 STORAGE AREAS.SEE FBC302.1.1, 302.2,
 AND TABLE 302.1.1.
  
 9.)PROVIDE AREA CALCULATIONS;
 EXISTING, PROPOSED NEW, NEW TOTAL.IT
 APPEARS THAT YOU ARE CONVERTING
 UNINHABITABLE SPACE TO BECOME HABITABLE;
 THE AREA CALCULATIONS SHOULD REFLECT
 THIS.THIS IS USED FOR ASSESSMENT OF
 IMPACT FEES BY PALM BEACH COUNTY.
 FAILURE TO PROPERLY ADDRESS THIS WILL
 RESULT IN DELAYS.IF YOU DO NOT
 UNDERSTAND WHAT IS REQUIRED, PLEASE
 CONTACT ME.
  
 10.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, CHANGE OF USE.233-5025
 FOR MORE INFORMATION.
  
 11.)SHOW COMPLIANCE WITH FBC TABLE
 503.
  
 12.)PROVIDE A COPY OF THE SURVEY OF
 THIS PROPERTY SO THAT FBC TABLE 601
 COMPLIANCE CAN BE DETERMINED,
 FBC*106.3.4, FBC EB812.1, FBC704,
 FBC704.5.
  
 13.)INFORMATIONAL ONLY; DUE TO THE
 LACK OF INFORMATION ON THE PLAN, A
 SECOND ROUND OF COMMENTS IS LIKELY.
  
 14.)THE SITE PLAN IS NOT SIGNED AND
 SEALED.THIS IS REQUIRED AS THIS PAGE
 IS REQUIRED TO SHOW CODE COMPLIANCE.
  
 15.)THE SITE PLAN HAS A NOTE, SUBJECT
 MEDICAL USE SHALL BE LIMITED USE PER
 TYPE 1 CATEGORY.WHAT DOES THIS MEAN?
  
 16.)THE SITE PLAN DOES NOT PROVIDE A
 DESIGNATION FOR THE REAR BUILDING.IT
 APPEARS TO BE A GARAGE.CLEARLY
 INDICATE USE FOR THIS STRUCTURE, FBC11.
  
 17.)THE REROOF PERMIT FOR THE HOUSE
 AND GARAGE ARE EXPIRED, PERMIT NUMBER
 99081195.PLEASE ADDRESS.
  
 18.)THE SITE PLAN DOES NOT SHOW THE
 EXIT RAMP SHOWN ON SHEET 2.
  
 19.)GENERAL PROJECT NOTES DESIGN
 CRITERIA REFERS TO 3 SECOND GUESTS.
 PLEASE REVISE.IT APPEARS THAT YOU ARE
 STATING WIND DESIGN CRITERIA, SEE
 FBC1603.1.4 AND PROVIDE ALL INFORMATION.
  
 20.)HAS RAUL LESCANO PE SIGNED THE
 PLANS?SEE FAC61G15-23.002.IT APPEARS
 THAT SOMEONE ELSE HAS SIGNED ON HIS
 BEHALF.THE ENGINEER IS TO SIGN, SEAL,
 AND DATE ALL DOCUMENTS.
  
 21.)ARE THE ROOM DESIGNATIONS LABELED
 CORRECTLY?THE EXISTING SHOWS A WAITING
 ROOM, NOW A SITTING ROOM.THIS DOES NOT
 APPEAR APPROPRIATE FOR BUSINESS USE.
 THERE ARE TWO EXISTING SECOND FLOOR
 PLANS.NO KITCHEN IS SHOWN ANYWHERE ON
 THE PLAN, NO BATHTUB OR SHOWER IS SHOWN.
 IF THIS IS CURRENTLY A RESIDENCE, ISN?T
 THERE A KITCHEN AND BATH WHICH REQUIRES
 DEMOLITION?PLEASE LABEL ALL ROOMS
 CORRECTLY AS TO USE AND REVISE PLANS TO
 ADDRESS INCONSISTENCIES.
  
 22.)WHAT WILL BE STORED IN THE STORAGE
 ROOM?
  
 23.)PRODUCT APPROVALS ARE TO BE
 APPROVED BY DESIGNER OF RECORD,
 FBC*106.3.3.
  
 24.)DECLARE AN OCCUPANCY, FBC 3.
  
 25.)DECLARE OCCUPANT LOAD, FBC1004.
  
 26.)DECLARE OCCUPANT LOAD FOR THE
 SECOND FLOOR.VERTICAL ACCESSIBILITY
 REQUIRED UNLESS EXCEPTED, FBC11-4.1.6.
 GENERAL PROJECT NOTES STATES THAT AN
 ELEVATOR WILL BE INSTALLED BUT NONE
 SHOWN ON THE PLAN.
  
 27.)PARKING IS TO COMPLY WITH CITY OF
 WEST PALM BEACH STANDARD, SEE ATTACHED.
 PROVIDE A DETAIL ON THE PLAN.
  
 28.)SHOW THE ACCESSIBLE ROUTE FROM THE
 PUBLIC WAY, FBC11-4.1.2(1).PROVIDE
 WIDTH, ELEVATION CHANGES.
  
 29.)SHOW THE ACCESSIBLE ROUTE FROM THE
 ACCESSIBLE PARKING SPACE IN THE REAR TO
 THE OFFICE.THE ACCESSIBLE PARKING
 SPACE IS TO COMPLY WITH FBC11-4.6.2.NO
 ACCESS AISLE IS SHOWN FBC11-4.3, NO
 DETAIL FOR THE ACCESSIBLE PARKING
 PROVIDED.
  
 30.)IT IS NOT CLEAR WHY THE RAMP GOES
 TO A STORAGE ROOM; IS THIS A LOADING
 RAMP RATHER THAN A RAMP FOR
 ACCESSIBILITY, FBC1 1-4.8?ACCESSIBLE
 RAMPS ARE TO HAVE A LANDING AT THE TOP
 AND BOTTOM, FBC11-4.8.4.
  
 31.)MEANS OF EGRESS CANNOT GO THROUGH
 A BATHROOM (A ROOM THAT CAN BE LOCKED)
 OR ASTORAGE ROOM, FBC1013.2.IT IS
 NOT CLEAR WHERE THE ACCESSIBLE ENTRANCE
 IS.
  
 32.)PROVIDE A LIFE SAFETY PLAN FOR
 BOTH THE FIRST AND SECOND FLOOR.THE
 DIMENSIONS FOR ALL MEANS OF EGRESS WHICH
 ARE CURRENTLY SHOWN AS EXISTING IS
 REQUIRED; DOORWAYS, STAIRS, FBC CHAPTER
 10.OVERALL DIMENSIONS ARE NOT SHOWN ON
 THE FLOOR PLAN.
  
 33.)SHOW EXIT LIGHTS IN COMPLIANCE
 WITH FBC1006.3.
  
 34.)PROVIDE A DETAIL AND A SECTION FOR
 THE EXISTING STAIRS SHOWING CONSTRUCTION
 AND ALL DIMENSIONS, INCLUDING HEAD
 CLEARANCE AND LANDING SIZE, FBC 1009,
 FBC11-4.9.
  
 35.)PROVIDE A HANDRAIL AND GUARDRAIL
 (IF APPLICABLE) DETAIL FOR THE STAIRS,
 FBC1012, FBC1009, FBC11-4.9.4.
  
 36.)THE ENTRY DOOR DOES NOT APPEAR TO
 COMPLY WITH FBC11-4.13.4, DOUBLE-LEAF
 DOORWAYS.
  
 37.)SECOND FLOOR EXISTING BATH IS TO
 BE ACCESSIBLE.PROVIDE ALL DETAILS, ALL
 DIMENSIONS, FOR BOTH BATHROOMS, FIRST
 AND SECOND FLOOR, RELATED TO
 ACCESSIBILITY; TOILET, GRAB BARS,
 TURNING RADIUS, SINK, CLEAR FLOOR SPACE
 FOR FIXTURES.
  
 38.)THE SECOND FLOOR BATH DOOR
 ENCROACHES INTO THE CLEAR FLOOR SPACE
 FOR THE SINK, FBC11-4.24.5.
  
 39.)AN EXISTING A/C VENT IS SHOWN IN
 THE NEW BATH.IS THIS IN THE FLOOR?
 GRATING IS TO COMPLY WITH FBC11-4.5.4.
  
 40.)DOORS ARE TO COMPLY WITH
 MANEUVERING CLEARANCE, FBC11-4.13.6, FBC
 FIGURE 11-25.THE FOLLOWING DOORS DO
 NOT APPEAR TO COMPLY WITH THE PULL SIDE
 MANEUVERING CLEARANCE REQUIREMENT; FIRST
 FLOOR STORAGE EXTERIOR NEW DOOR, NEW
 BATH EXTERIOR DOOR, SECOND FLOOR
 EXISTING SITTING ROOM, EXISTING LIBRARY
 CLOSET DOOR.
  
 41.)HOW DOES THE LINTEL TIE INTO THE
 EXISTING?AS DRAWN, IT SITS ON TOP OF
 TWO NEW COLUMNS BUT IS NOT STRUCTURALLY
 CONNECTED.
  
 42.)PROVIDE DESIGN LOAD INFORMATION
 FOR THE LINTEL, LINTEL SIZE AND REBAR
 INFORMATION.
  
 43.)PROVIDE DESIGN LOAD INFORMATION
 FOR THE FIRST FLOOR, SECOND FLOOR, AND
 STAIRS.CERTIFY THAT THE EXISTING
 FLOORS AND STAIRS COMPLY WITH THE NEW
 DESIGN LOAD REQUIREMENTS.
  
 44.)FBC*110.1.1, CERTIFICATE OF
 OCCUPANCY REQUIRED AS THIS IS A CHANGE
 FROM R3 TO B.
  
 45.)INFORMATIONAL - CODE COMPLIANCE
 CANNOT BE SHOWN BY REFERRING TO CODE
 SECTIONS ONLY.DESIGNER IS TO PROVIDE
 DESIGN CRITERIA WITH DETAILS, NOT CODE
 REFERENCES.