2006-08-16 00:00:00 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBCFLORIDA BUILDING CODE 2004 |
| BUILDING |
| FBC RFLORIDA BUILDING CODE 2004 |
| RESIDENTIAL |
| FBC EBFLORIDA BUILDING CODE 2004 |
| EXISTING BUILDING CODE |
| FBC*CITY OF WEST PALM BEACH |
| AMENDMENTS TO THE FBC2004 |
| |
| |
| 1.)A NOTICE OF COMMENCEMENT MUST BE |
| FILED WITH THE CLERK OF COURTS BEFORE A |
| PERMIT CAN BE ISSUED, FS713.13.A NEW |
| NOC WILL BE REQUIRED FOR THE NEW |
| CONTRACTOR. |
| |
| 2.)THE CONTRACTOR HAS CARPENTRY |
| CONTRACTOR AND A WINDOW AND DOOR |
| CONTRACTOR LICENSES.THE SCOPE OF WORK |
| FOR THIS PROJECT EXCEEDS THE SCOPE OF |
| THESE LICENSES (DRYWALL, PAINT, MASONRY, |
| CONCRETE, ETC.).SEE ATTACHED FOR WORK |
| ALLOWED UNDER THESE LICENSES. |
| |
| 3.)WHEN APPLYING FOR PERMITS, ONLY |
| REFER TO ONE LICENSE NUMBER.IF THE |
| SCOPE OF WORK INCLUDES BOTH LICENSES, |
| TWO PERMIT APPLICATIONS SHOULD BE |
| COMPLETED WITH TWO DIFFERENT PERMIT |
| NUMBERS GENERATED. |
| |
| 4.)A WINDOW AND DOOR PERMIT HAS BEEN |
| ISSUED FOR THIS ADDRESS.THE PLANS SHOW |
| THE WINDOWS AND DOORS AS EXISTING.NOTE |
| THAT AS THE CONTRACTOR DID NOT ADVISE |
| THAT THERE WAS TO BE A CHANGE OF |
| OCCUPANCY, THE CONTRACTOR IS PROCEEDING |
| AT HIS OR HER OWN RISK AS THAT PLAN WAS |
| NOT REVIEWED FOR ACCESSIBILITY, TABLE |
| 602, AND EGRESS REQUIREMENTS. |
| |
| 5.)THE PLANS STATE THAT THIS IS A |
| REMODEL MODIFICATION OF AN EXISTING |
| RESIDENCE TO DR. SCHWARZ PSYCHIATRY |
| FUNCTION.THIS IS A CHANGE OF |
| OCCUPANCY, FROM R3 TO BUSINESS.REMOVE |
| ALL REFERENCES TO RESIDENCES AND |
| RESIDENTIAL CODE FROM THE PLAN AS THEY |
| DO NOT APPLY TO THIS JOB.CHANGE OF |
| OCCUPANCY IS TO COMPLY WITH ALL |
| REQUIREMENTS OF FLORIDA BUILDING CODE |
| 2004 EXISTING BUILDING CODE, CHAPTERS 5 |
| THROUGH 8 AND FLORIDA BUILDING CODE |
| 2004, BUILDING, 11-4.1.6. |
| |
| 6.)MANY OF THE NOTES ON THE SITE PLAN |
| DO NOT APPLY TO THIS JOB.REMOVE FROM |
| THE PLAN. |
| |
| 7.)PROVIDE A CODE SUMMARY OF THE |
| EXISTING BUILDING; BUILDING HEIGHT, |
| CONSTRUCTION TYPE INCLUDING A OR B FBC |
| 6, FIRE SPRINKLER INFORMATION, GOVERNING |
| CODE INCLUDING FBC EB, OCCUPANCY FBC3. |
| |
| |
| 8.)PROVIDE AREA CALCULATIONS FOR THE |
| STORAGE AREAS.SEE FBC302.1.1, 302.2, |
| AND TABLE 302.1.1. |
| |
| 9.)PROVIDE AREA CALCULATIONS; |
| EXISTING, PROPOSED NEW, NEW TOTAL.IT |
| APPEARS THAT YOU ARE CONVERTING |
| UNINHABITABLE SPACE TO BECOME HABITABLE; |
| THE AREA CALCULATIONS SHOULD REFLECT |
| THIS.THIS IS USED FOR ASSESSMENT OF |
| IMPACT FEES BY PALM BEACH COUNTY. |
| FAILURE TO PROPERLY ADDRESS THIS WILL |
| RESULT IN DELAYS.IF YOU DO NOT |
| UNDERSTAND WHAT IS REQUIRED, PLEASE |
| CONTACT ME. |
| |
| 10.)IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY, CHANGE OF USE.233-5025 |
| FOR MORE INFORMATION. |
| |
| 11.)SHOW COMPLIANCE WITH FBC TABLE |
| 503. |
| |
| 12.)PROVIDE A COPY OF THE SURVEY OF |
| THIS PROPERTY SO THAT FBC TABLE 601 |
| COMPLIANCE CAN BE DETERMINED, |
| FBC*106.3.4, FBC EB812.1, FBC704, |
| FBC704.5. |
| |
| 13.)INFORMATIONAL ONLY; DUE TO THE |
| LACK OF INFORMATION ON THE PLAN, A |
| SECOND ROUND OF COMMENTS IS LIKELY. |
| |
| 14.)THE SITE PLAN IS NOT SIGNED AND |
| SEALED.THIS IS REQUIRED AS THIS PAGE |
| IS REQUIRED TO SHOW CODE COMPLIANCE. |
| |
| 15.)THE SITE PLAN HAS A NOTE, SUBJECT |
| MEDICAL USE SHALL BE LIMITED USE PER |
| TYPE 1 CATEGORY.WHAT DOES THIS MEAN? |
| |
| 16.)THE SITE PLAN DOES NOT PROVIDE A |
| DESIGNATION FOR THE REAR BUILDING.IT |
| APPEARS TO BE A GARAGE.CLEARLY |
| INDICATE USE FOR THIS STRUCTURE, FBC11. |
| |
| 17.)THE REROOF PERMIT FOR THE HOUSE |
| AND GARAGE ARE EXPIRED, PERMIT NUMBER |
| 99081195.PLEASE ADDRESS. |
| |
| 18.)THE SITE PLAN DOES NOT SHOW THE |
| EXIT RAMP SHOWN ON SHEET 2. |
| |
| 19.)GENERAL PROJECT NOTES DESIGN |
| CRITERIA REFERS TO 3 SECOND GUESTS. |
| PLEASE REVISE.IT APPEARS THAT YOU ARE |
| STATING WIND DESIGN CRITERIA, SEE |
| FBC1603.1.4 AND PROVIDE ALL INFORMATION. |
| |
| 20.)HAS RAUL LESCANO PE SIGNED THE |
| PLANS?SEE FAC61G15-23.002.IT APPEARS |
| THAT SOMEONE ELSE HAS SIGNED ON HIS |
| BEHALF.THE ENGINEER IS TO SIGN, SEAL, |
| AND DATE ALL DOCUMENTS. |
| |
| 21.)ARE THE ROOM DESIGNATIONS LABELED |
| CORRECTLY?THE EXISTING SHOWS A WAITING |
| ROOM, NOW A SITTING ROOM.THIS DOES NOT |
| APPEAR APPROPRIATE FOR BUSINESS USE. |
| THERE ARE TWO EXISTING SECOND FLOOR |
| PLANS.NO KITCHEN IS SHOWN ANYWHERE ON |
| THE PLAN, NO BATHTUB OR SHOWER IS SHOWN. |
| IF THIS IS CURRENTLY A RESIDENCE, ISN?T |
| THERE A KITCHEN AND BATH WHICH REQUIRES |
| DEMOLITION?PLEASE LABEL ALL ROOMS |
| CORRECTLY AS TO USE AND REVISE PLANS TO |
| ADDRESS INCONSISTENCIES. |
| |
| 22.)WHAT WILL BE STORED IN THE STORAGE |
| ROOM? |
| |
| 23.)PRODUCT APPROVALS ARE TO BE |
| APPROVED BY DESIGNER OF RECORD, |
| FBC*106.3.3. |
| |
| 24.)DECLARE AN OCCUPANCY, FBC 3. |
| |
| 25.)DECLARE OCCUPANT LOAD, FBC1004. |
| |
| 26.)DECLARE OCCUPANT LOAD FOR THE |
| SECOND FLOOR.VERTICAL ACCESSIBILITY |
| REQUIRED UNLESS EXCEPTED, FBC11-4.1.6. |
| GENERAL PROJECT NOTES STATES THAT AN |
| ELEVATOR WILL BE INSTALLED BUT NONE |
| SHOWN ON THE PLAN. |
| |
| 27.)PARKING IS TO COMPLY WITH CITY OF |
| WEST PALM BEACH STANDARD, SEE ATTACHED. |
| PROVIDE A DETAIL ON THE PLAN. |
| |
| 28.)SHOW THE ACCESSIBLE ROUTE FROM THE |
| PUBLIC WAY, FBC11-4.1.2(1).PROVIDE |
| WIDTH, ELEVATION CHANGES. |
| |
| 29.)SHOW THE ACCESSIBLE ROUTE FROM THE |
| ACCESSIBLE PARKING SPACE IN THE REAR TO |
| THE OFFICE.THE ACCESSIBLE PARKING |
| SPACE IS TO COMPLY WITH FBC11-4.6.2.NO |
| ACCESS AISLE IS SHOWN FBC11-4.3, NO |
| DETAIL FOR THE ACCESSIBLE PARKING |
| PROVIDED. |
| |
| 30.)IT IS NOT CLEAR WHY THE RAMP GOES |
| TO A STORAGE ROOM; IS THIS A LOADING |
| RAMP RATHER THAN A RAMP FOR |
| ACCESSIBILITY, FBC1 1-4.8?ACCESSIBLE |
| RAMPS ARE TO HAVE A LANDING AT THE TOP |
| AND BOTTOM, FBC11-4.8.4. |
| |
| 31.)MEANS OF EGRESS CANNOT GO THROUGH |
| A BATHROOM (A ROOM THAT CAN BE LOCKED) |
| OR ASTORAGE ROOM, FBC1013.2.IT IS |
| NOT CLEAR WHERE THE ACCESSIBLE ENTRANCE |
| IS. |
| |
| 32.)PROVIDE A LIFE SAFETY PLAN FOR |
| BOTH THE FIRST AND SECOND FLOOR.THE |
| DIMENSIONS FOR ALL MEANS OF EGRESS WHICH |
| ARE CURRENTLY SHOWN AS EXISTING IS |
| REQUIRED; DOORWAYS, STAIRS, FBC CHAPTER |
| 10.OVERALL DIMENSIONS ARE NOT SHOWN ON |
| THE FLOOR PLAN. |
| |
| 33.)SHOW EXIT LIGHTS IN COMPLIANCE |
| WITH FBC1006.3. |
| |
| 34.)PROVIDE A DETAIL AND A SECTION FOR |
| THE EXISTING STAIRS SHOWING CONSTRUCTION |
| AND ALL DIMENSIONS, INCLUDING HEAD |
| CLEARANCE AND LANDING SIZE, FBC 1009, |
| FBC11-4.9. |
| |
| 35.)PROVIDE A HANDRAIL AND GUARDRAIL |
| (IF APPLICABLE) DETAIL FOR THE STAIRS, |
| FBC1012, FBC1009, FBC11-4.9.4. |
| |
| 36.)THE ENTRY DOOR DOES NOT APPEAR TO |
| COMPLY WITH FBC11-4.13.4, DOUBLE-LEAF |
| DOORWAYS. |
| |
| 37.)SECOND FLOOR EXISTING BATH IS TO |
| BE ACCESSIBLE.PROVIDE ALL DETAILS, ALL |
| DIMENSIONS, FOR BOTH BATHROOMS, FIRST |
| AND SECOND FLOOR, RELATED TO |
| ACCESSIBILITY; TOILET, GRAB BARS, |
| TURNING RADIUS, SINK, CLEAR FLOOR SPACE |
| FOR FIXTURES. |
| |
| 38.)THE SECOND FLOOR BATH DOOR |
| ENCROACHES INTO THE CLEAR FLOOR SPACE |
| FOR THE SINK, FBC11-4.24.5. |
| |
| 39.)AN EXISTING A/C VENT IS SHOWN IN |
| THE NEW BATH.IS THIS IN THE FLOOR? |
| GRATING IS TO COMPLY WITH FBC11-4.5.4. |
| |
| 40.)DOORS ARE TO COMPLY WITH |
| MANEUVERING CLEARANCE, FBC11-4.13.6, FBC |
| FIGURE 11-25.THE FOLLOWING DOORS DO |
| NOT APPEAR TO COMPLY WITH THE PULL SIDE |
| MANEUVERING CLEARANCE REQUIREMENT; FIRST |
| FLOOR STORAGE EXTERIOR NEW DOOR, NEW |
| BATH EXTERIOR DOOR, SECOND FLOOR |
| EXISTING SITTING ROOM, EXISTING LIBRARY |
| CLOSET DOOR. |
| |
| 41.)HOW DOES THE LINTEL TIE INTO THE |
| EXISTING?AS DRAWN, IT SITS ON TOP OF |
| TWO NEW COLUMNS BUT IS NOT STRUCTURALLY |
| CONNECTED. |
| |
| 42.)PROVIDE DESIGN LOAD INFORMATION |
| FOR THE LINTEL, LINTEL SIZE AND REBAR |
| INFORMATION. |
| |
| 43.)PROVIDE DESIGN LOAD INFORMATION |
| FOR THE FIRST FLOOR, SECOND FLOOR, AND |
| STAIRS.CERTIFY THAT THE EXISTING |
| FLOORS AND STAIRS COMPLY WITH THE NEW |
| DESIGN LOAD REQUIREMENTS. |
| |
| 44.)FBC*110.1.1, CERTIFICATE OF |
| OCCUPANCY REQUIRED AS THIS IS A CHANGE |
| FROM R3 TO B. |
| |
| 45.)INFORMATIONAL - CODE COMPLIANCE |
| CANNOT BE SHOWN BY REFERRING TO CODE |
| SECTIONS ONLY.DESIGNER IS TO PROVIDE |
| DESIGN CRITERIA WITH DETAILS, NOT CODE |
| REFERENCES. |