 ******DENIED******
 REFERENCE: FBC-2004 FUEL GAS
  
 PRIOR PERMIT INFORMATION SEARCH
 INDICATES GASAT THE ADDRESS, PLEASE
 PROVIDE THE FOLLOWING INFORMATION FOR
 GAS PLAN REVIEW:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.(NOTE: PLEASE INDICATE
 EXISTING AND NEW ON ISOMETRIC DRAWING)
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 3. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).(NOTE: THIS INCLUDES THE
 EXISTING BTU'S AS WELL. TOTAL BTU'S)
 4. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).(NOTE: THIS
 INCLUDES EXISTING SYSTEM, LONGEST LENGTH
 METHOD USED TO SIZE AND FOR PLAN REVIEW
 TO CHECK SYSTEM)
 5. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.( PLEASE
 INDICATE ON DRAWING AS EXISTING ON
 RESUBMITTAL.)
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN
 RESUBMITTING, PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
  
 END OF COMMENTS:
  