2006-08-02 00:00:00DENIED
  
 1) SUBMIT SIGNED AND SEALED CALCULATIONS
 INDICATING HOW THE REQUIRED DESIGN
 PRESSURES WERE CALCULATED. THE SPECIFIED
 ROOF DESIGN PRESSURES DO NOT AGREE WITH
 THE PRESSURES LISTED IN FBC TABLE
 1609.6B.
  
 2) PRODUCT APPROVAL (NOA #01-0919.11)
 HAS NO LIMITATION #7 AS REFERED TO IN
 THE ENGINEER'S LETTER. LIMITATION #1 ON
 PAGE 5 OF 5 ALLOWS RATIONAL ANALYSIS FOR
 INCREASING THE PRODUCT DESIGN PRESSURES.
  
 3) SUBMIT SIGNED AND SEALED RATIONAL
 ANALYSIS COMPUTATIONS PREPARED BY A
 FLORIDA REGISTERED ENGINEER, ARCHITECT
 OR ROOF CONSULTANT AS REQUIRED BY SYSTEM
 LIMITATIONS #1 ON PAGE 5. THIS IS
 REQUIRED IN ADDITION TO THE LETTER FROM
 TURQUOISE CONSULTING INC.
  